ControlNet-to-DeviceNet Linking Device Installation Instructions, Catalog Number 1788-CN2DN, pages 25 to 32

Pages 25 to 32 of 32

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1788-CN2DN

Page 25

ControlNet-to-DeviceNet Linking Device 25 Use the following examples as references when determining which tags to view. .

1756-DNB Tag Title Example Tag Titled Local:3:I:StausRegister used to troubleshoot a problem specific to the DeviceNet module or network.

Tag Titled Local:3:S used to troubleshoot a problem specific to a device connected to the DeviceNet network.

Tag Titled Local:3:O.CommandRegister to determine the command of the DeviceNet scanner and its effect on the DeviceNet network.

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 26

26 ControlNet-to-DeviceNet Linking Device

1788-CN2DN Tag Title Example Tag Titled As_You_Name:I:StausRegister used to troubleshoot a problem specific to the DeviceNet module or network.

Tag Titled As_You_Name:S used to troubleshoot a problem specific to a device connected to the DeviceNet network.

Tag Titled As_You_Name:O.CommandReg ister to determine the command of the CN2DN device and its effect on the DeviceNet network.

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 27

ControlNet-to-DeviceNet Linking Device 27 5. If need to troubleshoot Status Register tags, use the following table as a reference to interpret module or network status.

Status Register Tag Values If Tag Member

Displays Value

Then Status Is

Run

0

Scanner in idle mode.

Run

1

Scanner in run mode.

Fault

0

Scanner not faulted.

Fault

1

Scanner faulted.

DisableNetwork

0

Scanner not disabled.

DisableNetwork

1

Scanner disabled.

DeviceFailure

0

Scanner communicating with all devices.

DeviceFailure

1

Scanner not communicating with at least 1 device.

AutoVerify

0

Data size of each device matches the amount of memory allocated for the device in the scanner.

AutoVerify

1

Data size of at least 1 device does not match the amount of memory allocated for the device in the scanner.

CommFailure

0

No network-wide communication problem exists

CommFailure

1

Network-wide communication problem exists

DupNodeFail

0

Scanner is on the network at a unique address

DupNodeFail

1

Scanner is trying to get on the network at an address that is already in use.

DnetPowerDetect

0

Network connector of the scanner has power.

DnetPowerDetect

1

Network connector of the scanner does not have power.

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 28

28 ControlNet-to-DeviceNet Linking Device 6. If you need to troubleshoot Status Tags (:S), use the following table as a reference to interpret device status. If You Want Information About

Then See Member

Data Type

I/O scans count.

ScanCounter

DINT

Indication that a device is not communicating on the network. Use the following information to interpret status: • There is 1 bit for each address on the DeviceNet network (0 -63). • The position of a bit = address of a device. • If a bit = 1, then the device at that address has failed.

DeviceFailureRegister

SINT[8]

Indication that the data size of a device does not match the amount of memory allocated for the device in the scanner. Use the following information to interpret status: • There is 1 bit for each address on the DeviceNet network (0 -63). • The position of a bit = address of a device. • If a bit = 1, then their is a mismatch with that address.

AutoverifyFailureRegister

SINT[8]

Indication that a device is idle. Use the following information to interpret status: • There is 1 bit for each address on the DeviceNet network (0 -63). • The position of a bit = address of a device. • If a bit = 1, then the device at that address is idle.

DeviceIdleRegister

SINT[8]

Indication that a device is online. Use the following information to interpret status: • There is 1 bit for each address on the DeviceNet network (0 -63). • The position of a bit = address of a device. • If a bit = 1, then the device at that address is online.

ActiveNodeRegister

SINT[8]

ASCII representation of scanner status/display.

StatusDisplay

SINT[4]

Address of the scanner.

ScannerAddress

SINT

Status code of scanner.

ScannerStatus

SINT

Address with an error. Use the following information to interpret status: • Scrolls through the addresses with errors. • ScrollingDeviceStatus member shows the status code.

ScrollingDeviceAddress

SINT

A status code of an address with an error. Use the following information to interpret status: • Scrolls through addresses with errors. • ScrollingDeviceAddress member shows the address.

ScrollingDeviceStatus

SINT

Status code of all devices – 1 byte per device.

DeviceStatus

SINT[64]

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 29

ControlNet-to-DeviceNet Linking Device 29 7. If you need to troubleshoot the CommandRegister tags, use the following table to interpret or change the status associated with the data bit. If Bit

Bit Name

Status Indicates

0

Run

Device and network: 1 = Run mode 0 = Idle mode

1

Fault

Network: 1 = fault present 0 = normal

2

Disable Network

Network: 1 = disabled 0 = normal

3

Halt Scanner

Device: 1 = halt device (stops all functions) 0 = normal operation

4

Reset

Device: 1 = need to reset device (change to 0) 0 = normal

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 30

30 ControlNet-to-DeviceNet Linking Device

Troubleshoot the ControlNet Network If ControlNet network communications fail, you need to complete one or more of the following tasks to troubleshoot the ControlNet network.

• Interpret the LED Indicators of ControlNet devices on the network. • View and interpret the status indicators displayed on the ControlNet network devices. • Check ControlNet network for media problems. For more information about completing each troubleshooting task, consult the following publications. Task

Publication Title

Publication

Interpret LED indicators of a ControlNet module

Installation instructions specific to the module - or ControlNet Modules in Logix5000 Control Systems User Manual

Varies by module - or CNET-UM001

View and interpret ControlNet network status indicators

ControlNet Modules in Logix5000 Control Systems User Manual

CNET-UM001

Check for ControlNet media problems

ControlNet Fiber Media Planning and Installation Guide

CNET-IN001

Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource

Description

ControlNet Modules in Logix5000 Control Systems, publication CNET-UM001

Describes how to program, configure, use, and troubleshoot ControlNet modules.

ControlNet Coax Media Planning and Installation Guide, publication CNET-IN002

Provides details for planning and installing a ControlNet network.

DeviceNet Media Design and Installation Guide, publication DNET-UM072

Provides details for planning and installing a DeviceNet network.

DeviceNet Modules in Logix5000 Control Systems, publication DNET-UM004

Describes how to program, configure, use, and troubleshoot DeviceNet modules.

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

Provides general guidelines for installing a Rockwell Automation industrial system.

Product Certifications website, http://www.ab.com

Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 31

ControlNet-to-DeviceNet Linking Device 31

Notes:

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 32

Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support you can find technical and application notes, sample code, and links to software service packs. You can also visit our Support Center at https://rockwellautomation.custhelp.com/ for software updates, support chats and forums, technical information, FAQs, and to sign up for product notification updates. In addition, we offer multiple support programs for installation, configuration, and troubleshooting. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/services/online-phone.

Installation Assistance If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running. United States or Canada Outside United States or Canada

1.440.646.3434 Use the Worldwide Locator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local Rockwell Automation representative.

New Product Satisfaction Return Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States Outside United States

Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process. Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

Rockwell Automation maintains current product environmental information on its website at http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-compliance.page. Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400