For the Allen-Bradley 1788-CN2DN

Page 17

ControlNet-to-DeviceNet Linking Device 17

Module Status Use the following table to interpret your Module Status LED indicators and determine if corrective action is necessary.

Module Status Indicators LED Indicator Off

Device Status No power to device.

Green, flashing

The CN2DN device is functioning but not communicating with devices. Fully operational. The CN2DN device is communicating with all configured DeviceNet nodes or there are no configured devices. The linking device is not 1. Verify that DeviceNet switches are not set at PGM. communicating with one or more 2. Verify that connected devices are functioning properly. modules. 3. Verify that devices have been configured properly. See Additional Resources on page 30 for publications with more information about configuring the CN2DN device. Unrecoverable communication 1. Verify that the CN2DN device has been assigned a unique node fault. address during configuration. 2. Verify that all devices are set at the same baud rate. 3. Cycle CN2DN power. 4. Replace the CN2DN device.

Green, steady

Red, flashing

Red, steady

Recommended Action 1. Verify that the power supply is functioning properly. 2. Cycle power supply. 3. Remove power and check input power wiring. Reapply power. 4. Replace the CN2DN linking device. Use RSNetworx software to configure the CN2DN device. See Additional Resources on page 30 for publications with more information about configuring the CN2DN device. None. The device has passed self-tests and is functioning properly if devices have been configured.

Linking Activity Status The Linking Activity LED indicator displays the status of communication between the DeviceNet and ControlNet networks as well as the amount of traffic. Use the following table to interpret the Linking Activity LED indicator.

Linking Activity LED Indicator LED Indicator

Linking Activity Status

Off

No network traffic is occurring between the ControlNet to DeviceNet networks. I/O traffic may be present.

Green, flashing

ControlNet to DeviceNet (non-I/O) communication traffic present (flash rate indicates amount of traffic).

Red and green, flashing

Module is running boot code only (used for FLASH upgrades).

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 18

18 ControlNet-to-DeviceNet Linking Device

ControlNet Network Status The CNet A and CNet B LED indicators display the status of the ControlNet network and individual channels. The ControlNet network may recognize more than one network status a time. If more than one status is present, the CN2DN linking device will display the highest priority status. Use the following table to interpret the ControlNet LED indicators.

ControlNet LED Indicators, CNet A and CNet B LED Indicator State

LED View

Priority Level

ControlNet Network Status

Off

Both CNet A and CNet B

1 (highest priority)

No power.

Red, steady

Both CNet A and CNet B

2

No ControlNet network found.

Red and green, alternating

Both CNet A and CNet B

3

Device self-testing.

Red, alternating

Both CNet A and CNet B

4

Incorrect ControlNet node configuration.

Off

One, CNet A or CNet B

5

ControlNet channel disabled or not supported.

Red and green, flashing

One, CNet A or CNet B

6

Incorrect ControlNet network configuration.

Red, flashing

One, CNet A or CNet B

7

No data received from network.

Green, flashing

One, CNet A or CNet B

8

Temporary channel error or listen-only channel.

Green, steady

One, CNet A or CNet B

9 (lowest)

Normal network operation.

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 19

ControlNet-to-DeviceNet Linking Device 19

DeviceNet Network Status The DeviceNet network indicators, DNet Network Status and DNet I/O Status, indicate the state of the DeviceNet network and the state of DeviceNet I/O modules. Use the following tables to interpret your DeviceNet LED indicators located at the top right corner of the CN2DN device.

DNet Network Status Indicator LED Indicator

DeviceNet Network Status

Recommended Action

Off

No DeviceNet connection.

If a DeviceNet connection has been made, do the following. 1. Verify that the DeviceNet network is powered. 2. Check DeviceNet cables and connections.

Green, flashing

DeviceNet network found, not communicating with devices.

1. Check DeviceNet cables and connections. 2. Verify that all devices on the DeviceNet network are functioning properly.

Green, steady

One or more devices connected and communicating.

None needed.

Red, flashing

One or more connections timed-out.

Use programming software to view tags specific to the devices in order to troubleshoot the DeviceNet network. See DeviceNet Modules in Logix5000 Control Systems, publication DNET-UM004, for more information about using controller tags to troubleshoot connection errors.

Red, steady

Communication error (bus off condition).

1. Verify that each device has be assigned a unique node address. 2. Verify that specified DeviceNet baud rates are the same. 3. Cycle power to the CN2DN device. See DeviceNet Modules in Logix5000 Control Systems, publication DNET-UM004, for more information about using controller tags to troubleshoot connection errors.

DNet I/O Status Indicator LED Indicator

I/O Device Status

Recommended Action

Off

No connection to device.

1. Verify that the DeviceNet network is powered. 2. Verify the connected device is functioning properly.

Green, flashing

Device is in program mode (idle).

To put the device in run mode, use programming software.

Green, steady

Device is in run mode.

To put the device in program mode, use programming software.

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 20

20 ControlNet-to-DeviceNet Linking Device

Troubleshoot the DeviceNet Network If DeviceNet network communications fail, you need to complete one or both of these tasks to troubleshoot the DeviceNet network.

• View and interpret DeviceNet network status codes. • View and interpret the controller status tags using RSLogix5000 software.

View and Interpret DeviceNet Status Codes on the DeviceNet Scanner In order to view the DeviceNet status code, locate the scanner on the DeviceNet network. The status code is viewed on the character display on the front of the scanner module, for example a 1756-DNB, DeviceNet bridge module. IMPORTANT

The DeviceNet status codes display only on the DeviceNet scanner module. Status codes do not display on the 1788-CN2DN linking device.

Use the DeviceNet Status Codes table to interpret your status code.

DeviceNet Status Codes Status Code

Description of Status

Recommended Action

0-63

Scanner’s DeviceNet node address.

None.

65

The AutoScan option is on and the device is in idle mode.

None.

67

Scanner is Secondary scanner.

None.

68

Primary scanner has detected no Secondary scanner.

Configure another scanner to be the Secondary scanner.

69

Primary and Secondary configurations are mismatched.

Check configuration of the Secondary scanner.

70

The address of the device is already in use by another device on the network. The scanner failed the duplicate node address check.

Change the address of the device to an unused address.

71

Invalid data in scan list.

Use RSNetworx software to reconfigure the scan list.

72

Slave device stopped communicating. If the slave device does not recover communication during next scan, status code changes to 78.

• Verify slave device’ power and communication connections. • If the slave device is polled, verify that the interscan delay time is adequate for the device to return data.

73

Slave device’s identity information does not match electronic key in scanner.

• Make sure that the correct device is connected at this address. • Make sure that the device matches the specified electronic key (vendor, product code, product type).

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 21

ControlNet-to-DeviceNet Linking Device 21

DeviceNet Status Codes Status Code

Description of Status

Recommended Action

74

Scanner detected data overrun on DeviceNet communication port.

• Modify your configuration and check for invalid data. • Check network communication traffic.

75

Either or both of the following: • The device does not have a scan list. • The device has not received communication from any other device.

Verify that the device has the following: • A configured scan list • A properly-wired connection to the network

76

No direct network traffic for scanner. The scanner hears other network communication but does not hear any directed to it.

None.

77

During initialization, the data size expected by the device does not match the scan list entry.

Use RSNetWorx software to check the slave device and the scan list for the correct input and output sizes for the slave device.

78

Device is configured in scan list, but not communicating. It has failed to communicate during the scanner’s second scan, which followed the display of status error code 72.

• Verify device’s power and communication connections. • If the device is polled, make sure the interscan delay is long enough for the device to return its data. • If needed, use RSNetWorx software to do the following: – Add the device to the DeviceNet network. – Delete the device from scanner’s scan list. – Inhibit the device in the scanner’s scan list.

79

Scanner has failed to transmit a message. The error status usually displays after the duplicate node check completes at power-up.

• Make sure that your scanner is connected to a valid network. • Check for disconnected cables. • Verify network baud rate.

80

Scanner is in idle mode.

If desired, put network in run mode by completing the following steps. 1. Put the controller in run or remote run mode using the keyswitch on the controller or through RSLogix5000 software. 2. Turn on the bit O.CommandRegister.Run for the scanner.

81

Controller has set the scanner to the faulted mode. The Command bit also indicates a DeviceNet network fault state.

Bit O.CommandRegister.Fault for the scanner is on. Correct condition that caused controller to set this bit and then turn this bit off.

82

Error detected in sequence of fragmented I/O messages from device.

Use RSNetWorx software to do the following: • Check scan list of the device to make sure that its input and output data sizes are correct. • Check the configuration of the device.

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 22

22 ControlNet-to-DeviceNet Linking Device

DeviceNet Status Codes Status Code

Description of Status

Recommended Action

83

Device returns error responses when the scanner attempts to communicate with it.

Use RSNetWorx software to do the following: • Check the accuracy of the scan list. • Check the configuration of the device. The device may be in another scanner’s scan list. • Use the slave device’s documentation to verify that the device supports the message type used by the scanner. If the device’s message type does not match the scanner’s, then use RSNetWorx to access the scanner’s scanlist and change the scanner’s message type to one that is compatible with the slave device. • Cycle power to the device.

84

Scanner is initializing the DeviceNet network.

None. This code clears itself once the scanner attempts to initialize all the devices on the network.

85

During runtime, the data size sent by the slave device does not match the size in the corresponding scan list entry.

Since variable length poll data is not supported, verify that the slave device is functioning properly.

86

The device is in idle mode, or not producing data, while the scanner is in run mode.

• Check the configuration and status of the device. • If you set up an interlock between 2 scanners (controllers), make sure both scanners are in run mode.

87

Scanner cannot listen to shared inputs from slave device because the owning scanner has not established communication with that slave device.

• Verify primary scanner connection and configuration. • Slave device may not be producing data.

88

Scanner cannot listen to shared inputs from slave device because I/O parameters (for example, polled or strobed, electronic key, data size) for that slave device are configured differently between this scanner and the owning scanner.

In this scanner, reconfigure the I/O parameters for the shared inputs scan list entry so that they match those same parameters in the owning scanner.

89

Scanner failed to configure a device using the Automatic Device Recovery (ADR) parameters.

• Make sure that you installed a compatible device. • If the offline configuration of the device does not match the actual (online) configuration of the device, change the offline configuration to match the online configuration.

90

Controller has set the scanner to the disabled mode.

If desired, turn enable the scanner by locating the O.CommandRegister.DisableNetwork bit of the command register and turn if off.

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 23

ControlNet-to-DeviceNet Linking Device 23

DeviceNet Status Codes Status Code

Description of Status

Recommended Action

91

Bus-off condition likely due to cable or signal errors.

• Cycle power to the device. • Verify that all devices are set to the same baud rate. • Check DeviceNet cabling to make sure no short circuits exist between CAN (blue and white) wires and power or shield (black, red, and shield) wires. • Check the media system for the following noise sources: – Device located near high-volt power cable. – Incorrect or no termination resistor used. – Improper grounding. – Device on network producing noise or incorrect data for the network.

92

DeviceNet cable not supplying power to the device’s communication port.

• Verify the network’s 24V dc power supply is operating properly. • Verify good cable condition. • Check cable connections to the device.

95

A device’s firmware is being updated or a configuration is being downloaded.

None. Do not disconnect the device while the update is in process as existing data in device memory will be lost.

96

Communication port is in test mode.

None.

97

The controller has placed the scanner in halt mode.

If the O.CommandRegister.HaltScanner bit is on, turn it off then cycle scanner power.

98

General firmware error.

Replace device.

99

System Failure.

Replace device.

Rockwell Automation Publication 1788-IN052E-EN-P - December 2014

Page 24

24 ControlNet-to-DeviceNet Linking Device

View and Interpret Controller Status Tags Use the following procedure to troubleshoot the DeviceNet network using the controller status tags in RSLogix5000 software. 1. Use RSLogix5000 software to verify that the controller is in run mode and that the program is online with the controller. 2. In the program’s organization tree, double-click Controller Tags. Double-click to open

3. Determine which tags you need to view using the following procedure. a. Determine the first part of the tag title specific to your device using the table below. If Your DeviceNet Module Is

Then the Tag Title Begins With

Example

Local 1756-DNB module

Local:slot number

Local:3:

Remote 1756-DNB module

Name of the module:slot number in remote chassis

1756-DNB:3

CompactLogix 1769-SDN module

Local:slot number

Local:4

SoftLogix5800 1784-PCIDS module

Local:slot number

Local:0

DriveLogix/FlexLogix 1788-DNBO

Name of module entered in the module Properties dialog.

My_Flex_Bridge

Linking Device, 1788-EN2DN or 1788-CN2DN

Name of the module entered in the module Properties dialog.

As_You_Name_ b. Decide which tag type you need to view using the following table as a reference. If You Are Troubleshooting

Then Check Tag Type

Indicated By

A problem specific to the DeviceNet scanner or the DeviceNet network.

Status Register

StatusRegister

The DeviceNet scanner and the DeviceNet network status.

Command Register

CommandRegister

A problem corresponding to a specific device on the DeviceNet network.

Status Tag

S

4. Scroll through the list of tags to locate the specific tag you need.