For the Allen-Bradley 1791D-OB16P and Allen-Bradley 1791D-OB16PX
Page 1
Technical Data
CompactBlock I/O for DeviceNet 1791D
The 1791D CompactBlock I/O modules contain I/O circuits, a built-in power supply, and a built-in DeviceNet™ I/O adapter. CompactBlock I/O modules are ideal for applications restricted by space limitations and applications requiring highly distributed I/O blocks close to sensors and actuators. The following CompactBlock I/O modules are available: CompactBlock I/O • 4 sinking input base module • (1791D-4B0) • • • •
8 sourcing input/ 8 sinking • output base module (1791D-8V8P) 16 sourcing input base • module (1791D-16V0) 16 sourcing output base • module (1791D-0B16P) 16 sinking output expansion module (1791D-0V16PX)
4 sinking input/ 4 sourcing output • base module (1791D-4B4P) 16 sinking input base module (1791D-16B0)
•
16 sourcing input expansion module (1791D-16V0X) 16 sourcing output expansion module (1791D-0B16PX)
• •
8 sinking input/ 8 sourcing output base module (1791D-8B8P) 16 sinking input expansion module (1791D-16B0X) 8 sourcing output base module (1791D-0B8P) 16 sinking output base module (1791D-0V16P)
Page 2
2
Overview
CompactBlock I/O for DeviceNet
Overview
CompactBlock I/O modules are compatible with PLC®, SLC™ or SoftLogix™ programmable controllers using DeviceNet scanners. All CompactBlock I/O module values are accessible through the data tables of the PLC or SLC programmable controller.
Compact Block I/O Module
Node addresses on the modules are set using rotary switches, located on the module, RSNetworx™ for DeviceNet software or a similar configuration tool. All other module parameters are set using a similiar configuration tool.
Features and Benefits Feature: 10–30V dc device power NEMA type 1+ inputs output short-circuit protection hardware watchdog function I/O block located close to sensors and actuators compact size of I/O block autobaud detection rotary node address switches selectable input filters change-of-state operation ODVA conformance tested to DeviceNet version 2.0
Publication 1791D-IN001A-EP - September 2000
Benefit: accommodates broad range of power supplies and multiple voltage levels from the network compatible with a broad range of sensors protects outputs against accidental miswiring puts outputs in a known state if the microprocessor or crystal fails lower wiring costs module requires no adapter or power supply module automatically matches system baud rate - no crashing due to incorrect baud setting reduces node commissioning time select off-to-on and on-to-off delays best suited for your application improves network throughput by reducing network bandwidth usage assures interoperability with other DeviceNet compliant devices and systems
Page 3
CompactBlock I/O for DeviceNet
Overview
Typical Configuration
3
This graphic shows how your CompactBlock I/O fits into a typical DeviceNet system. 1771-SDN scanner
1747-SDN scanner
Personal Computer with configuration software
1784-PCD PCMCIA card
SLC controller
PLC-5 controller
FLEX I/O™ Series 9000 Photoelectric Sensors
DTAM Micro or Plus
RediSTATION™ operator interface
GV3000 drive
1305 drive
1336 PLUS drive
FlexPac™ 3000 drive
SSC Bulletin 160
DeviceView™ hand-held configurator ArmorBlock™ I/O
1336 FORCE drive
EZLINK™ bearing monitor
SMC motor starter with Dialog SMP-3 overload Plus relay
1791D CompactBlock I/O DeviceLink™ I/O with limit switch
20455-M
System Compatibility
CompactBlock I/O modules are compatible with PLC, SLC or SoftLogix programmable controllers when used with DeviceNet scanners.
CompactBlock Family Module Communication
The CompactBlock modules act as a slave in a master/slave environment. Their I/O data is exchanged with the master through a polled, cyclic, or change-of-state connection. This selection is made in the DeviceNet scanner module’s configuration.
Polled When configured as a polled device, a master initiates communication by sending its polled I/O message to the CompactBlock module.
Cyclic When using cyclic operation, the master only sends data to the CompactBlock I/O module and only receives data from the module at a preconfigured time interval.
Publication 1791D-IN001A-EP - September 2000
Page 4
4
Overview
CompactBlock I/O for DeviceNet
Change-of-State When the CompactBlock I/O module is configured for change-of-state, the master only sends output data when: • the user’s control program wants to update the module’s output • the time period for communication has expired The CompactBlock module’s input is only sent to the master when: • an input changes • the time period for communication has expired With change-of-state, the master does not have to request input data from the slave, it is sent automatically when data changes. In addition, an adjustable "heartbeat" is produced periodically by the CompactBlock module to let the consuming device know that the module connection is alive and ready to communicate.
Input Filtering
Input filtering limits the effect of voltage transients caused by contact bounce and/or electrical noise. If not filtered, voltage transients could produce false data. To configure an input filter, an input signal delay is set to turn off-to-on or on-to-off for nominal amounts of time. The mode and filter time is set through RSNetworx for DeviceNet software, or a similar configuration tool.
Idle and Fault Mode Selection
When the PLC, SLC or PC-based programmable controller is in program mode, the DeviceNet scanner puts the CompactBlock module in an idle state. If the DeviceNet scanner drops off the network, the module goes to a fault state. In both idle and fault states, the module resets its outputs by default. RSNetworx for DeviceNet software or a similar configuration tool can change the default and set the module to save the last received outputs. Fault State hold last state (HLS) HLS use fault value 0
Fault Value apply 0 to output
1 apply 1 to output
Fault state can be set to HLS or use fault value. The fault value can be set to 0 or 1. The same logic applies for idle conditions.
Publication 1791D-IN001A-EP - September 2000
42455
Page 5
CompactBlock I/O for DeviceNet
Status Indicators
Overview
5
Each CompactBlock I/O module has indicators to provide a diagnostic readout. Logic Status Indicator Module Status Indicator I/O Status Indicators
42499
Module/Network Status Indicators Indication:
Status:
Off
No power or auto bauding
Flashing Green/Off On line but not connected Solid Green
On line, link OK, connected
Flashing Red
Recoverable fault - (expansion module fault or module configuration error) I/O connection fault - one or more I/O connections in the timed-out state
Solid Red
Unrecoverable fault Communication failure - duplicate node address present or incorrect baud rate
Green to Red to Off At powerup only - LED test
Logic Status Indicators (base only) Indication:
Status:
Off
Logic is disabled
Solid Green
Logic is enabled
Flashing Green
Local forces are applied and local logic is enabled
I/O Status Indicators (base and expansion) Function:
LED Color:
Module Illumination:
Condition:
Outputs
Yellow
None Yellow
Output not energized Output energized
Inputs
Yellow
None Yellow
No valid input Valid input
Publication 1791D-IN001A-EP - September 2000
Page 6
6
Overview
CompactBlock I/O for DeviceNet
Power Supply Requirements
The DeviceNet network supplies power to the CompactBlock I/O base and expansion modules. Inputs and outputs are powered by an external 24V dc source which is independent of the network.
Mounting
The CompactBlock I/O base and expansion modules can be mounted directly to a panel or on a DIN rail. The following graphic shows the base and expansion modules mounting dimensions. Base Module
141 mm 5.55 in
Expansion Module 25mm 1 in
104 mm 4.09 in
41mm 1.6 in
41mm 1.6 in
Expansion covers 30358
Remember to consider the length of the expansion ribbon cable when installing a base module with an expansion. The expansion module must be close enough for the expansion cable to reach from the base module to the expansion module. Modules can be mounted vertically or horizontally. Base and expansion modules can be mounted side-by-side. The graphic below shows a base module connected to an expansion module. Base Module
Expansion Module
30360
Publication 1791D-IN001A-EP - September 2000
Page 7
CompactBlock I/O for DeviceNet
CompactBlock I/O Cables
Overview
7
The following tables lists part numbers and descriptions for CompactBlock cables
CompactBlock I/O Expansion Cables Description
Length cm(in) Part Number
DeviceNet Expansion Cable1
4 (1.6)
1791D-4CMCBL
Expansion Cable
10 (4)
1791D-10CMCBL
1 This cable is shipped with the product, catalog number is for spare cables only.
DeviceNet Cables Description Mini male to conductor (unshielded) Mini male to conductor (shielded)
Specific Module Information
Length m Part Number Part Number Application: (aluminum): (stainless steel): 1 1485-P1M5-C 1485RS-P1M5-C DeviceNet drop cable 6 1485R-P6M5-C 1485RS-P6M5-C (flat media) 1 1485R-P1M5-C 1485P-1M5-C DeviceNet drop cable 2 1485R-P2M5-C 1485RS-P2M5-C (round media) 3 1485RS-P3M5-C 1485RS-P3M5-C
The remainder of this publication contains specification sheets for each CompactBlock I/O module. Refer to the table below for information about a specific module. For information about: 4 sinking input base module (1791D-4B0) 4 sinking input/ 4 sourcing output base module (1791D-4B4P0 8 sinking input / 8 sourcing output base module (1791D-8B8P) 8 sourcinginput/ 8 sinking output base module (1791D-8V8P) 16 sinking input base module (1791D-16B0) 16 sinking input expansion module (1791D-16B0X) 16 sourcing input base module (1791D-16V0) 16 sourcing input expansion module (1791D-16V0X) 8 sourcing output base module (1791D-0B8P) 16 sourcing output base module (1791D-0B16P) 16 sourcing output expansion module (1791D-0B16PX) 16 sinking output base module (1791D-0V16P) 16 sinking output expansion module (1791D-0V16PX)
Related Publications
See page: 9 11 13 15 17 19 21 23 25 27 29 31 33
Refer to the following list of publications for more information about the CompactBlock I/O modules as well as the DeviceNet network and its products. Title: CompactBlock I/O Product Profile CompactBlock I/O Installation Instructions DeviceNet Product Overview DeviceNet Cable System Planning and Installation Manual
Publication Number: 1791D-1.4 1791D-IN001A-EN-P DN-2.5 DN-6.7.2
Publication 1791D-IN001A-EP - September 2000
Page 8
8
Overview
Notes:
Publication 1791D-IN001A-EP - September 2000
CompactBlock I/O for DeviceNet
Page 9
CompactBlock I/O for DeviceNet
4 Sinking Input Base Module 1791D-4B0
9
4 Sinking Input Base Module 1791D-4BO Simplified Schematic Input Opto Isolation
Input Indication LED (Logic)
System Circuitry
+
24V dc
_ 42501
GND
The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data. Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block. Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.
The module produces 1 byte for every 4 inputs. The following table contains the connection sizes for this module: Module
I/O Points
Produce Consume (input bytes) (output bytes)
1791D-4B0
4 input
1
0
Refer to the tables below for the word/bit definitions. Bit Produces 0
03 I3
02 I2
01 I1
00 I0
Word Bit Description Produces 0 00-03 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3.
Publication 1791D-IN001A-EN-P - September 2000