The text of a spec sheet · part 1 of 4

CompactBlock I/O for DeviceNet 1791D Technical Data, pages 1 to 9

Pages 1 to 9 of 36

The original document is the PDF (4.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1791D-OB16P and Allen-Bradley 1791D-OB16PX

Page 1

Technical Data

CompactBlock I/O for DeviceNet 1791D

The 1791D CompactBlock I/O modules contain I/O circuits, a built-in power supply, and a built-in DeviceNet™ I/O adapter. CompactBlock I/O modules are ideal for applications restricted by space limitations and applications requiring highly distributed I/O blocks close to sensors and actuators. The following CompactBlock I/O modules are available: CompactBlock I/O • 4 sinking input base module • (1791D-4B0) • • • •

8 sourcing input/ 8 sinking • output base module (1791D-8V8P) 16 sourcing input base • module (1791D-16V0) 16 sourcing output base • module (1791D-0B16P) 16 sinking output expansion module (1791D-0V16PX)

4 sinking input/ 4 sourcing output • base module (1791D-4B4P) 16 sinking input base module (1791D-16B0)

•

16 sourcing input expansion module (1791D-16V0X) 16 sourcing output expansion module (1791D-0B16PX)

• •

8 sinking input/ 8 sourcing output base module (1791D-8B8P) 16 sinking input expansion module (1791D-16B0X) 8 sourcing output base module (1791D-0B8P) 16 sinking output base module (1791D-0V16P)

Page 2

2

Overview

CompactBlock I/O for DeviceNet

Overview

CompactBlock I/O modules are compatible with PLC®, SLC™ or SoftLogix™ programmable controllers using DeviceNet scanners. All CompactBlock I/O module values are accessible through the data tables of the PLC or SLC programmable controller.

Compact Block I/O Module

Node addresses on the modules are set using rotary switches, located on the module, RSNetworx™ for DeviceNet software or a similar configuration tool. All other module parameters are set using a similiar configuration tool.

Features and Benefits Feature: 10–30V dc device power NEMA type 1+ inputs output short-circuit protection hardware watchdog function I/O block located close to sensors and actuators compact size of I/O block autobaud detection rotary node address switches selectable input filters change-of-state operation ODVA conformance tested to DeviceNet version 2.0

Publication 1791D-IN001A-EP - September 2000

Benefit: accommodates broad range of power supplies and multiple voltage levels from the network compatible with a broad range of sensors protects outputs against accidental miswiring puts outputs in a known state if the microprocessor or crystal fails lower wiring costs module requires no adapter or power supply module automatically matches system baud rate - no crashing due to incorrect baud setting reduces node commissioning time select off-to-on and on-to-off delays best suited for your application improves network throughput by reducing network bandwidth usage assures interoperability with other DeviceNet compliant devices and systems

Page 3

CompactBlock I/O for DeviceNet

Overview

Typical Configuration

3

This graphic shows how your CompactBlock I/O fits into a typical DeviceNet system. 1771-SDN scanner

1747-SDN scanner

Personal Computer with configuration software

1784-PCD PCMCIA card

SLC controller

PLC-5 controller

FLEX I/O™ Series 9000 Photoelectric Sensors

DTAM Micro or Plus

RediSTATION™ operator interface

GV3000 drive

1305 drive

1336 PLUS drive

FlexPac™ 3000 drive

SSC Bulletin 160

DeviceView™ hand-held configurator ArmorBlock™ I/O

1336 FORCE drive

EZLINK™ bearing monitor

SMC motor starter with Dialog SMP-3 overload Plus relay

1791D CompactBlock I/O DeviceLink™ I/O with limit switch

20455-M

System Compatibility

CompactBlock I/O modules are compatible with PLC, SLC or SoftLogix programmable controllers when used with DeviceNet scanners.

CompactBlock Family Module Communication

The CompactBlock modules act as a slave in a master/slave environment. Their I/O data is exchanged with the master through a polled, cyclic, or change-of-state connection. This selection is made in the DeviceNet scanner module’s configuration.

Polled When configured as a polled device, a master initiates communication by sending its polled I/O message to the CompactBlock module.

Cyclic When using cyclic operation, the master only sends data to the CompactBlock I/O module and only receives data from the module at a preconfigured time interval.

Publication 1791D-IN001A-EP - September 2000

Page 4

4

Overview

CompactBlock I/O for DeviceNet

Change-of-State When the CompactBlock I/O module is configured for change-of-state, the master only sends output data when: • the user’s control program wants to update the module’s output • the time period for communication has expired The CompactBlock module’s input is only sent to the master when: • an input changes • the time period for communication has expired With change-of-state, the master does not have to request input data from the slave, it is sent automatically when data changes. In addition, an adjustable "heartbeat" is produced periodically by the CompactBlock module to let the consuming device know that the module connection is alive and ready to communicate.

Input Filtering

Input filtering limits the effect of voltage transients caused by contact bounce and/or electrical noise. If not filtered, voltage transients could produce false data. To configure an input filter, an input signal delay is set to turn off-to-on or on-to-off for nominal amounts of time. The mode and filter time is set through RSNetworx for DeviceNet software, or a similar configuration tool.

Idle and Fault Mode Selection

When the PLC, SLC or PC-based programmable controller is in program mode, the DeviceNet scanner puts the CompactBlock module in an idle state. If the DeviceNet scanner drops off the network, the module goes to a fault state. In both idle and fault states, the module resets its outputs by default. RSNetworx for DeviceNet software or a similar configuration tool can change the default and set the module to save the last received outputs. Fault State hold last state (HLS) HLS use fault value 0

Fault Value apply 0 to output

1 apply 1 to output

Fault state can be set to HLS or use fault value. The fault value can be set to 0 or 1. The same logic applies for idle conditions.

Publication 1791D-IN001A-EP - September 2000

42455

Page 5

CompactBlock I/O for DeviceNet

Status Indicators

Overview

5

Each CompactBlock I/O module has indicators to provide a diagnostic readout. Logic Status Indicator Module Status Indicator I/O Status Indicators

42499

Module/Network Status Indicators Indication:

Status:

Off

No power or auto bauding

Flashing Green/Off On line but not connected Solid Green

On line, link OK, connected

Flashing Red

Recoverable fault - (expansion module fault or module configuration error) I/O connection fault - one or more I/O connections in the timed-out state

Solid Red

Unrecoverable fault Communication failure - duplicate node address present or incorrect baud rate

Green to Red to Off At powerup only - LED test

Logic Status Indicators (base only) Indication:

Status:

Off

Logic is disabled

Solid Green

Logic is enabled

Flashing Green

Local forces are applied and local logic is enabled

I/O Status Indicators (base and expansion) Function:

LED Color:

Module Illumination:

Condition:

Outputs

Yellow

None Yellow

Output not energized Output energized

Inputs

Yellow

None Yellow

No valid input Valid input

Publication 1791D-IN001A-EP - September 2000

Page 6

6

Overview

CompactBlock I/O for DeviceNet

Power Supply Requirements

The DeviceNet network supplies power to the CompactBlock I/O base and expansion modules. Inputs and outputs are powered by an external 24V dc source which is independent of the network.

Mounting

The CompactBlock I/O base and expansion modules can be mounted directly to a panel or on a DIN rail. The following graphic shows the base and expansion modules mounting dimensions. Base Module

141 mm 5.55 in

Expansion Module 25mm 1 in

104 mm 4.09 in

41mm 1.6 in

41mm 1.6 in

Expansion covers 30358

Remember to consider the length of the expansion ribbon cable when installing a base module with an expansion. The expansion module must be close enough for the expansion cable to reach from the base module to the expansion module. Modules can be mounted vertically or horizontally. Base and expansion modules can be mounted side-by-side. The graphic below shows a base module connected to an expansion module. Base Module

Expansion Module

30360

Publication 1791D-IN001A-EP - September 2000

Page 7

CompactBlock I/O for DeviceNet

CompactBlock I/O Cables

Overview

7

The following tables lists part numbers and descriptions for CompactBlock cables

CompactBlock I/O Expansion Cables Description

Length cm(in) Part Number

DeviceNet Expansion Cable1

4 (1.6)

1791D-4CMCBL

Expansion Cable

10 (4)

1791D-10CMCBL

1 This cable is shipped with the product, catalog number is for spare cables only.

DeviceNet Cables Description Mini male to conductor (unshielded) Mini male to conductor (shielded)

Specific Module Information

Length m Part Number Part Number Application: (aluminum): (stainless steel): 1 1485-P1M5-C 1485RS-P1M5-C DeviceNet drop cable 6 1485R-P6M5-C 1485RS-P6M5-C (flat media) 1 1485R-P1M5-C 1485P-1M5-C DeviceNet drop cable 2 1485R-P2M5-C 1485RS-P2M5-C (round media) 3 1485RS-P3M5-C 1485RS-P3M5-C

The remainder of this publication contains specification sheets for each CompactBlock I/O module. Refer to the table below for information about a specific module. For information about: 4 sinking input base module (1791D-4B0) 4 sinking input/ 4 sourcing output base module (1791D-4B4P0 8 sinking input / 8 sourcing output base module (1791D-8B8P) 8 sourcinginput/ 8 sinking output base module (1791D-8V8P) 16 sinking input base module (1791D-16B0) 16 sinking input expansion module (1791D-16B0X) 16 sourcing input base module (1791D-16V0) 16 sourcing input expansion module (1791D-16V0X) 8 sourcing output base module (1791D-0B8P) 16 sourcing output base module (1791D-0B16P) 16 sourcing output expansion module (1791D-0B16PX) 16 sinking output base module (1791D-0V16P) 16 sinking output expansion module (1791D-0V16PX)

Related Publications

See page: 9 11 13 15 17 19 21 23 25 27 29 31 33

Refer to the following list of publications for more information about the CompactBlock I/O modules as well as the DeviceNet network and its products. Title: CompactBlock I/O Product Profile CompactBlock I/O Installation Instructions DeviceNet Product Overview DeviceNet Cable System Planning and Installation Manual

Publication Number: 1791D-1.4 1791D-IN001A-EN-P DN-2.5 DN-6.7.2

Publication 1791D-IN001A-EP - September 2000

Page 8

8

Overview

Notes:

Publication 1791D-IN001A-EP - September 2000

CompactBlock I/O for DeviceNet

Page 9

CompactBlock I/O for DeviceNet

4 Sinking Input Base Module 1791D-4B0

9

4 Sinking Input Base Module 1791D-4BO Simplified Schematic Input Opto Isolation

Input Indication LED (Logic)

System Circuitry

+

24V dc

_ 42501

GND

The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data. Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block. Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.

The module produces 1 byte for every 4 inputs. The following table contains the connection sizes for this module: Module

I/O Points

Produce Consume (input bytes) (output bytes)

1791D-4B0

4 input

1

0

Refer to the tables below for the word/bit definitions. Bit Produces 0

03 I3

02 I2

01 I1

00 I0

Word Bit Description Produces 0 00-03 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3.

Publication 1791D-IN001A-EN-P - September 2000