Page 1 of CompactBlock I/O for DeviceNet 1791D Technical Data

Spec sheet · Allen-Bradley

CompactBlock I/O for DeviceNet 1791D Technical Data

Spec sheet36 pagesPDF 4.5 MB

Technical data for Allen-Bradley 1791D CompactBlock I/O for DeviceNet, including the 1791D-0B16P base and 1791D-0B16PX expansion modules.

Download the PDF4.5 MB

Covers · 2 models

The models it covers

Summary

What is in it

Allen-Bradley technical data for the 1791D CompactBlock I/O family for DeviceNet: compact blocks with I/O circuits, a built-in power supply and a built-in DeviceNet adapter. An overview covers compatibility, polled, cyclic and change-of-state communication, input filtering, idle and fault modes, indicators, power, mounting and cables. A specification sheet follows for each module, including the 16 sourcing output base module 1791D-0B16P and expansion module 1791D-0B16PX.

Its parts

  1. Overview
  2. 4 Sinking Input Base Module 1791D-4B0
  3. 4 Sinking Input/4 Sourcing Output Base Module 1791D-4B4P
  4. 8 Sinking Input/8 Sourcing Output Base Module 1791D-8B8P
  5. 8 Sourcing Input/8 Sinking Output Base Module 1791D-8V8P
  6. 16 Sinking Input Base Module 1791D-16B0
  7. 16 Sinking Input Expansion Module 1791D-16B0X
  8. 16 Sourcing Input Base Module 1791D-16V0
  9. 16 Sourcing Input Expansion Module 1791D-16V0X
  10. 8 Sourcing Output Base Module 1791D-0B8P
  11. 16 Sourcing Output Base Module 1791D-0B16P
  12. 16 Sourcing Output Expansion Module 1791D-0B16PX
  13. 16 Sinking Output Base Module 1791D-0V16P
  14. 16 Sinking Output Expansion Module 1791D-0V16PX

From the sheet

Key facts from this sheet

Each line names its page in the PDF.

Rockwell Automation technical data (publication 1791D-IN001A-EN-P, September 2000) for the thirteen 1791D CompactBlock I/O for DeviceNet modules. Its pages for the 16 sourcing output base module (printed both 1791D-0B16P and 1791D-OB16P) and its expansion module 1791D-0B16PX give wiring, power, output ratings and output bit maps. Shared pages explain communication modes, idle and fault behavior, status indicators, mounting and cables.

Read for this summary: pages 1 to 8, 27 to 30 and 36 of 36.

Outputs
16 sourcing outputs in 2 groups of 8 p. 27, 28, 29, 30
Output voltage
10 - 30V dc on-state range; 0.5V dc drop at rated current p. 28, 30
Output current
On-state 0.5A maximum; all outputs 4.0A maximum; surge 1.0A for 10ms, repeatable every 2 s; off-state leakage 1.0mA maximum p. 28, 30
Auxiliary power
10 - 30V dc, 4A maximum, from an external source independent of the network p. 6, 28, 30
Environment
0 to 60°C (32 to 140°F) operating; -40 to 85°C non-operating; 5-95% humidity non-condensing p. 28, 30
Isolation
500V ac I/O to DeviceNet, I/O group-to-group and I/O group-to-logic p. 28, 30
Enclosure and wiring
IEC IP20; wire up to 14 gauge (2mm2) stranded, insulation up to 3/64 inch p. 28, 30
DeviceNet power
1791D-OB16P: 11V - 25 V dc, 200mA maximum (with expansion) p. 28
Expansion power
1791D-OB16PX: 5V dc, 100mA p. 30
I/O data
1 byte consumed per 8 outputs; with an expansion module attached, an extra byte reports its health p. 27, 29
Connection types
Polled, change-of-state or cyclic, chosen in the DeviceNet scanner configuration p. 3, 27, 29
Idle and fault outputs
Outputs reset by default; configurable to hold last state or apply a fault value of 0 or 1 p. 4
Setup
Node address by rotary switches or RSNetworx for DeviceNet; autobaud detection of the network rate p. 2
Expansion cables
1791D-4CMCBL 4 cm (1.6 in), shipped with the product; 1791D-10CMCBL 10 cm (4 in) p. 7

What this sheet walks you through

  • How CompactBlock modules exchange data: polled, cyclic and change-of-state p. 3, 4
  • Setting input filters p. 4
  • Choosing idle and fault output behavior p. 4
  • Reading the module/network, logic and I/O status indicators p. 5
  • Powering and mounting base and expansion modules on a panel or DIN rail p. 6
  • Ordering expansion and DeviceNet cables p. 7
  • Wiring and specifications of the 1791D-0B16P base module p. 27, 28
  • Wiring and specifications of the 1791D-0B16PX expansion module p. 29, 30
  • Mapping output bits in the DeviceNet data to outputs p. 27, 29

Good to know

  • The expansion module must sit close enough for the expansion ribbon cable to reach it from the base module. p. 6
  • The 4 cm expansion cable ships with the product; its part number is for spare cables only. p. 7
  • If the DeviceNet scanner drops off the network, the module goes to its fault state. p. 4

Questions this sheet answers

What is the output current rating of the 1791D-OB16P?

On-state current is 0.5A maximum, and module current for all outputs together is 4.0A maximum. p. 28

What power does the 1791D-OB16P need?

DeviceNet power of 11V - 25 V dc at 200mA maximum (with expansion), plus 10 - 30V dc auxiliary power, 4A maximum, for the outputs. p. 28

What cable connects a CompactBlock expansion module to its base module?

An expansion ribbon cable: the 4 cm 1791D-4CMCBL ships with the product, and a 10 cm 1791D-10CMCBL is listed. p. 6, 7

What happens to CompactBlock outputs when the PLC goes to program mode?

The scanner puts the module in idle, and by default it resets its outputs; it can instead hold the last state or apply a set value. p. 4

What does a solid red module/network status LED mean on a CompactBlock module?

An unrecoverable fault, or a communication failure from a duplicate node address or an incorrect baud rate. p. 5

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. CompactBlock I/O for DeviceNet1
  2. Overview2
  3. Typical Configuration3
  4. System Compatibility3
  5. CompactBlock Family Module Communication3
  6. Input Filtering4
  7. Idle and Fault Mode Selection4
  8. Status Indicators5
  9. Power Supply Requirements6
  10. Mounting6
  11. CompactBlock I/O Cables7
  12. Specific Module Information7
  13. Related Publications7
  14. 4 Sinking Input Base Module 1791D-4BO9
  15. 4 Sinking Input/4 Sourcing Output Base Module 1791D-4B4P11
  16. 8 Sinking Input/8 Sourcing Output Base Module 1791D-8B8P13
  17. 8 Sourcing Input/8 Sinking Output Base Module 1791D-8V8P15
  18. 16 Sinking Input Base Module 1791D-16BO17
  19. 16 Sinking Input Expansion module 1791D-16B0X19
  20. 16 Sourcing Input Base Module 1791D-16V021
  21. 16 Sourcing Input Expansion Module 1791D-16V0X23
  22. 8 Sourcing Output Base Module 1791D-0B8P25
  23. 16 Sourcing Output Base Module 1791D-0B16P27
  24. 16 Sourcing Output Expansion Module 1791D-0B16PX29
  25. 16 Sourcing Output Base Module 1791D-0V16P31
  26. 16 Sourcing Output Expansion Module 1791D-0V16PX33
  27. Back Cover36

From the PDF’s own bookmarks.

The whole text · 4 parts

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 91-9
  2. Pages 10 to 1810-18
  3. Pages 19 to 2719-27
  4. Pages 28 to 3628-36

The file

Revision and size

Part no.1791D-IN001A-EP
RevisionSeptember 2000
PublisherRockwell Automation
Pages36
PDF4.5 MB
TextText from the PDF itself.
1791D-IN001A-EP

The first pages · 4 of 36

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 36
Page 2
Page 2of 36
Page 3
Page 3of 36
Page 4
Page 4of 36