For the Allen-Bradley 1791D-OB16P and Allen-Bradley 1791D-OB16PX

Page 19

CompactBlock I/O for DeviceNet

16 Sinking Input Expansion Module 1791D-16B0X

19

16 Sinking Input Expansion module 1791D-16B0X Simplified Schematic Input Opto Isolation

Input Indication LED (Logic)

System Circuitry

+

24V dc

_ 42501

GND

The CompactBlock expansion module I/O is exchanged with the master through a poll, changeof-state, or cyclic connection.

The following table contains the connection sizes for this module: Module(s)

Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data.

1791D-16B0X with base input module 1791D-16B0X with base output module 1791D-16B0X with combination base module

I/O Points Produce Consume (input bytes) (output bytes) 32 input 5 0 16 input/ 16 output 24 input/ 8 output

3

2

4

1

Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block.

Refer to the table below for the word/bit definitions.

Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.

Word Produces

This module produces 1 byte for every 8 inputs. When it is connected to a base module, an additional byte will be returned indicating the health of the expansion module.

Bit 07 Produces I7 Produces 1 I15

06 I6 I14

05 I5 I13

04 I4 I12

03 I3 I11

02 I2 I10

01 I1 I9

00 I0 I8

Bit Description 00-07 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3, etc. Produces 1 08-15 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I8, bit 01 corresponds to input I9, bit 02 corresponds to input I10, bit 03 corresponds to input I11, etc.

Publication 1791D-IN001A-EN-P - September 2000

Page 20

20

16 Sinking Input Expansion Module 1791D-16B0X

CompactBlock I/O for DeviceNet

The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.

General Specifications Indicators

Communication Rate Thick Cable

Flat Media

Wiring Connections Input Wiring Diagram for 1791D-16BOX Expansion Module VDC

IN 0 GND

IN 2

IN 1

IN 4

IN 3

IN 5

IN 6

VDC

IN 7

IN 8 GND

IN 9

IN 10 IN 12

IN 14 Not Used

+

41671

Expansion Power Voltage Current

5V dc 100mA

Expansion Module Dimensions

113mm X 48mm X 38mm 4.4in X 1.9in X 1.5in

Environmental Conditions Operating Temperature 0 to 60°C (32 to 140°F) Non-Operating Temperature -40 to 85°C (-40 to 185°F) Relative Humidity 5-95% non-condensing Operating Shock 30 g Non-operating Shock 50g Vibration tested 5g @ 10-500Hz per IEC 68-2-6

Specifications Max

Inputs per Block

2 groups of 8

125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac

Conductors Wire Size

Sinking Inputs

125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft)

Isolation I/O to DeviceNet I/O group-to-group I/O group-to-logic

IN 11 IN 13 IN 15

-

Mod/Net status - red/green Logic status - green I/O status - yellow

Category

14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2

Product Certifications

UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives

Enclosure

IEC IP20

Min

Off-state Voltage 5V dc

-

On-state Voltage

30V dc @ 40°C 24V dc @ 60°C

10V dc

1 Use this conductor category information for planning conductor routing as

Off-state Current

1.5mA @ 5V dc

-

2

On-state Current

11mA @ 30V dc

2mA @ 10V dc described in the system level installation manual.

Publication 1791D-IN001A-EN-P - September 2000

Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.

Page 21

CompactBlock I/O for DeviceNet

16 Sourcing Input Base Module 1791D-16V0

21

16 Sourcing Input Base Module 1791D-16V0 Simplified Schematic V dc

+

24V dc

_ Opto Isolation

Input Indication LED (Logic)

System Circuitry

Input

41886

The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection.

The following table contains the connection sizes for this module: Module(s)

Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data. Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block. Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured. The module produces 1 byte for every 8 inputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module.

I/O Points Produce Consume (input bytes) (output bytes) 16 input 2 0 32 input 5 0

1791D-16V0 1791D-16V0 with expansion input 1791D-16V0 with expansion output

16 input/ 16 output

3

2

Refer to the table below for the word/bit definitions. Bit

07

06

05

04

03

02

01

00

Produces 0 I7

I6

I5

I4

I3

I2

I1

I0

Produces 1 I15

I14

I13

I12

I11

I10

I9

I8

Word

Bit

Description

Produces 0 00-07

Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3, etc.

Produces 1 00-07

Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I8, bit 01 corresponds to input I9, bit 02 corresponds to input I10, bit 03 corresponds to input I11, etc.

Publication 1791D-IN001A-EN-P - September 2000

Page 22

22

16 Sourcing Input Base Module 1791D-16V0

CompactBlock I/O for DeviceNet

The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.

General Specifications Indicators

Communication Rate Thick Cable

Flat Media

Wiring Connections Input Wiring Diagram for 1791D-16VO VDC

IN 0

GND

IN 2

IN 1

IN 4

IN 3

IN 6

IN 5

VDC IN 8 IN 7

GND

IN 10 IN 9

IN 12

IN 11

IN 14

IN 13

Not Used

IN 15

+ 41670

DeviceNet Power Voltage Current

11 - 25 V dc 200mA maximum (with expansion)

Base Module Dimensions

150mm X 48mm X 38mm 5.91in X 1.9in X 1.5in

Environmental Conditions Operating Temperature 0 to 60°C (32 to 140°F) Non-Operating Temperature -40 to 85°C (-40 to 185°F) Relative Humidity 5-95% non-condensing Operating Shock 30g Non-operating Shock 50g Vibration tested 5g @ 10-500Hz per IEC 68-2-6

Category

Inputs per Block

2 groups of 8

Off-state Voltage

5V dc

-

On-state Voltage

30V dc @ 40°C 25V dc @ 60°C

10V dc

1.5mA @ 5V dc

-

Off-state Current On-state Current

11mA @ 30V dc

125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac

Specifications Max

125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft)

Isolation I/O to DeviceNet I/O group-to-group I/O group-to-logic

Conductors Wire Size

Sourcing Inputs

Mod/Net status - red/green Logic status - green I/O status - yellow

14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2

Product Certifications

UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives

Enclosure

IEC IP20

Min

1 Use this conductor category information for planning conductor routing as

2mA @ 10V dc

Publication 1791D-IN001A-EN-P - September 2000 described in the system level installation manual. 2

Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.

Page 23

CompactBlock I/O for DeviceNet

16 Sourcing Input Expansion Module 1791D-16V0X 23

16 Sourcing Input Expansion Module 1791D-16V0X Simplified Schematic V dc

+

24V dc

_

Input

Opto Isolation

Input Indication LED (Logic)

System Circuitry

41886

The CompactBlock expansion module I/O is exchanged with the master through a poll, changeof-state, or cyclic connection.

The following table contains the connection sizes for this module: Module(s)

Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data. Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block. Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured. This module produces 1 byte for every 8 inputs. When it is connected to a base module, an additional byte will be returned indicating the health of the expansion module.

1791D-16B0X with base input module 1791D-16B0X with base output module 1791D-16B0X with combination base module

I/O Points Produce Consume (input bytes) (output bytes) 32 input 5 0 16 input/ 3 16 output 24 input/ 8 4 output

2 1

Refer to the table below for the word/bit definitions. Bit 07 Produces I7 Produces 1 I15

06 I6 I14

Word Produces

Description Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3, ect. Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I8, bit 01 corresponds to input I9, bit 02 corresponds to input I10, bit 03 corresponds to input I11, etc.

Bit 00-07

Produces 1 08-15

05 I5 I13

04 I4 I12

03 I3 I11

02 I2 I10

01 I1 I9

00 I0 I8

Publication 1791D-IN001A-EN-P - September 2000

Page 24

24

16 Sourcing Input Expansion Module 1791D-16V0X

CompactBlock I/O for DeviceNet

The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.

General Specifications Indicators

Communication Rate Thick Cable

Flat Media

Wiring Connections Input Wiring Diagram for 1791D-16VOX Expansion Module VDC GND

IN 0

IN 4

IN 2

IN 1

IN 3

IN 5

IN 6

VDC

IN 7

IN 8

GND

IN 10 IN 12

IN 9

IN 11

IN 14

IN 13

Not Used

41670

Expansion Power Voltage Current

5V dc 100mA

Expansion Module Dimensions

113mm X 48mm X 38mm 4.4in X 1.9in X 1.5in

Environmental Conditions Operating Temperature 0 to 60°C (32 to 140°F) Non-Operating Temperature -40 to 85°C (-40 to 185°F) Relative Humidity 5-95% non-condensing Operating Shock 30 g Non-operating Shock 50g Vibration tested 5g @ 10-500Hz per IEC 68-2-6

Specifications

Inputs per Block

Category

UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives

Enclosure

IEC IP20

Min -

On-state Voltage 30V dc @ 40°C 24V dc @ 60°C

10V dc

Off-state Current 1.5mA @ 5V dc

-

On-state Current

2mA @ 10V dc

11mA @ 30V dc

Publication 1791D-IN001A-EN-P - September 2000

14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2

Product Certifications 2 groups of 8

Off-state Voltage 5V dc

125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac

Conductors Wire Size

Sourcing Inputs Max

125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft)

Isolation I/O to DeviceNet I/O group-to-group I/O group-to-logic

IN 15

+

Mod/Net status - red/green Logic status - green I/O status - yellow

1 Use this conductor category information for planning conductor routing as described in the system level installation manual. 2

Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.

Page 25

CompactBlock I/O for DeviceNet

8 Sourcing Output Base Module 1791D-0B8P

25

8 Sourcing Output Base Module 1791D-0B8P Simplified Schematic

Output Indication LED (Logic)

V dc

+ System Circuitry

Opto Isolation

Protected Output Device

Output 24V dc

Load

–

42502

Gnd

The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data. Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block. Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.

The following table contains connection sizes for this module: Module

I/O Points

1791D-0B8P 1791D-0B8P with expansion output 1791D-0B8P with expansion input

8 outputs 24 outputs 8 output/ 16 inputs

Produce (input bytes) 0 1

Consume (output bytes) 1 3

3

1

Refer to the tables below for the word/bit definitions. Bit 07 Consumes 0 O7

06 O6

05 O5

04 O4

03 O3

02 O2

01 O1

00 O0

Word Bit Consumes 0 00-07

Description Output bits - when the bit is set (1), the output will be turned on. Bit 00 corresponds to output O0, bit 01 corresponds to output 01, bit 02 to output 02, bit 03 to output 03, etc.

The module consumes 1 byte for every 8 outputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module.

Publication 1791D-IN001A-EN-P - September 2000

Page 26

26

8 Sourcing Output Base Module 1791D-0B8P

CompactBlock I/O for DeviceNet

The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.

General Specifications Indicators

Communication Rate Thick Cable

Mod/Net status - red/green Logic status - green I/O status - yellow 125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft)

Flat Media 125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft)

Wiring Connections Output Wiring Diagram for 1791D-OB8P VDC

OUT 0 GND OUT 2 GND

VDC

GND

GND OUT 1 GND OUT 3 GND

+

OUT 4 GND OUT 6 OUT 5 GND

GND

Not Used

OUT 7 GND

Load

Isolation I/O to DeviceNet I/O group-to-group I/O group-to-logic

500V ac 500V ac 500V ac

DeviceNet Power Voltage Current

11V - 25 V dc 200mA maximum (with expansion)

Auxiliary Power Voltage Current

10 - 30V dc 4A maximum

Base Module Dimensions

150mm X 48mm X 38mm 5.91 in X 1.9 in X 1.5 in

42345

_

Environmental Conditions Operating Temperature 0 to 60°C (32 to 140°F) Non-Operating Temperature -40 to 85°C (-40 to 185°F) Relative Humidity 5-95% non-condensing Operating Shock 30g Non-operating Shock 50g Vibration tested 5g @ 10-500Hz per IEC 68-2-6

Specifications

Conductors Wire Size

Sourcing Outputs Outputs per Block

8

On-state Voltage Range

10 - 30V dc

On-state Voltage Drop

0.5V dc @ rated current

On-state Current

0.5A maximum

Off-state Leakage

1.0mA maximum

Module Current (all outputs)

4.0A maximum

Surge Current - for 10ms, repeatable every 2 s

1.0A maximum

Category Product Certifications

UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives

Enclosure

IEC IP20

1

Use this conductor category information for planning conductor routing as described in the system level installation manual.

2 Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1791D-IN001A-EN-P - September 2000

14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2

Page 27

CompactBlock I/O for DeviceNet

16 Sourcing Output Base Module 1791D-0B16P

27

16 Sourcing Output Base Module 1791D-0B16P Simplified Schematic

Output Indication LED (Logic)

V dc

+ System Circuitry

Opto Isolation

Protected Output Device

Output 24V dc

Load

–

42502

Gnd

The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data. Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block. Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured. The module consumes 1 byte for every 8 outputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module.

The following table contains connection sizes for this module: Module

I/O Points

1791D-0B16P 1791D-0B16P with expansion output 1791D-0B16P with expansion input

16 outputs 32 outputs

Produce (input bytes) 0 1

16 output/ 16 3 inputs

Consume (output bytes) 2 4 2

Refer to the tables below for the word/bit definitions. Bit 07 Consumes 0 O7 Consumes 1 O15

06 O6 O14

Word Bit Consumes 0 00-07

Description Output bits - when the bit is set (1), the output will be turned on. Bit 00 corresponds to output O0, bit 01 corresponds to output 01, bit 02 to output 02, bit 03 to output 03, etc. Output bits - when the bit is set (1), the output will be turned on. Bit 00 corresponds to output O8, bit 01 corresponds to output O9, bit 02 to output O10, bit 03 to output O11, etc.

Consumes 1 08-15

05 O5 O13

04 O4 O12

03 O3 O11

02 O2 O10

01 O1 O9

00 O0 O8

Publication 1791D-IN001A-EN-P - September 2000