CompactBlock I/O for DeviceNet
16 Sinking Input Expansion Module 1791D-16B0X
19
16 Sinking Input Expansion module 1791D-16B0X Simplified Schematic Input Opto Isolation
Input Indication LED (Logic)
System Circuitry
+
24V dc
_ 42501
GND
The CompactBlock expansion module I/O is exchanged with the master through a poll, changeof-state, or cyclic connection.
The following table contains the connection sizes for this module: Module(s)
Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data.
1791D-16B0X with base input module 1791D-16B0X with base output module 1791D-16B0X with combination base module
I/O Points Produce Consume (input bytes) (output bytes) 32 input 5 0 16 input/ 16 output 24 input/ 8 output
3
2
4
1
Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block.
Refer to the table below for the word/bit definitions.
Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.
Word Produces
This module produces 1 byte for every 8 inputs. When it is connected to a base module, an additional byte will be returned indicating the health of the expansion module.
Bit 07 Produces I7 Produces 1 I15
06 I6 I14
05 I5 I13
04 I4 I12
03 I3 I11
02 I2 I10
01 I1 I9
00 I0 I8
Bit Description 00-07 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3, etc. Produces 1 08-15 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I8, bit 01 corresponds to input I9, bit 02 corresponds to input I10, bit 03 corresponds to input I11, etc.
Publication 1791D-IN001A-EN-P - September 2000
Page 20
20
16 Sinking Input Expansion Module 1791D-16B0X
CompactBlock I/O for DeviceNet
The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.
General Specifications Indicators
Communication Rate Thick Cable
Flat Media
Wiring Connections Input Wiring Diagram for 1791D-16BOX Expansion Module VDC
IN 0 GND
IN 2
IN 1
IN 4
IN 3
IN 5
IN 6
VDC
IN 7
IN 8 GND
IN 9
IN 10 IN 12
IN 14 Not Used
+
41671
Expansion Power Voltage Current
5V dc 100mA
Expansion Module Dimensions
113mm X 48mm X 38mm 4.4in X 1.9in X 1.5in
Environmental Conditions Operating Temperature 0 to 60°C (32 to 140°F) Non-Operating Temperature -40 to 85°C (-40 to 185°F) Relative Humidity 5-95% non-condensing Operating Shock 30 g Non-operating Shock 50g Vibration tested 5g @ 10-500Hz per IEC 68-2-6
Specifications Max
Inputs per Block
2 groups of 8
125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac
Conductors Wire Size
Sinking Inputs
125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft)
Isolation I/O to DeviceNet I/O group-to-group I/O group-to-logic
IN 11 IN 13 IN 15
-
Mod/Net status - red/green Logic status - green I/O status - yellow
Category
14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2
Product Certifications
UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives
Enclosure
IEC IP20
Min
Off-state Voltage 5V dc
-
On-state Voltage
30V dc @ 40°C 24V dc @ 60°C
10V dc
1 Use this conductor category information for planning conductor routing as
Off-state Current
1.5mA @ 5V dc
-
2
On-state Current
11mA @ 30V dc
2mA @ 10V dc described in the system level installation manual.
Publication 1791D-IN001A-EN-P - September 2000
Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.
Page 21
CompactBlock I/O for DeviceNet
16 Sourcing Input Base Module 1791D-16V0
21
16 Sourcing Input Base Module 1791D-16V0 Simplified Schematic V dc
+
24V dc
_ Opto Isolation
Input Indication LED (Logic)
System Circuitry
Input
41886
The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection.
The following table contains the connection sizes for this module: Module(s)
Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data. Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block. Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured. The module produces 1 byte for every 8 inputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module.
I/O Points Produce Consume (input bytes) (output bytes) 16 input 2 0 32 input 5 0
1791D-16V0 1791D-16V0 with expansion input 1791D-16V0 with expansion output
16 input/ 16 output
3
2
Refer to the table below for the word/bit definitions. Bit
07
06
05
04
03
02
01
00
Produces 0 I7
I6
I5
I4
I3
I2
I1
I0
Produces 1 I15
I14
I13
I12
I11
I10
I9
I8
Word
Bit
Description
Produces 0 00-07
Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3, etc.
Produces 1 00-07
Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I8, bit 01 corresponds to input I9, bit 02 corresponds to input I10, bit 03 corresponds to input I11, etc.
Publication 1791D-IN001A-EN-P - September 2000
Page 22
22
16 Sourcing Input Base Module 1791D-16V0
CompactBlock I/O for DeviceNet
The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.
General Specifications Indicators
Communication Rate Thick Cable
Flat Media
Wiring Connections Input Wiring Diagram for 1791D-16VO VDC
IN 0
GND
IN 2
IN 1
IN 4
IN 3
IN 6
IN 5
VDC IN 8 IN 7
GND
IN 10 IN 9
IN 12
IN 11
IN 14
IN 13
Not Used
IN 15
+ 41670
DeviceNet Power Voltage Current
11 - 25 V dc 200mA maximum (with expansion)
Base Module Dimensions
150mm X 48mm X 38mm 5.91in X 1.9in X 1.5in
Environmental Conditions Operating Temperature 0 to 60°C (32 to 140°F) Non-Operating Temperature -40 to 85°C (-40 to 185°F) Relative Humidity 5-95% non-condensing Operating Shock 30g Non-operating Shock 50g Vibration tested 5g @ 10-500Hz per IEC 68-2-6
Category
Inputs per Block
2 groups of 8
Off-state Voltage
5V dc
-
On-state Voltage
30V dc @ 40°C 25V dc @ 60°C
10V dc
1.5mA @ 5V dc
-
Off-state Current On-state Current
11mA @ 30V dc
125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac
Specifications Max
125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft)
Isolation I/O to DeviceNet I/O group-to-group I/O group-to-logic
Conductors Wire Size
Sourcing Inputs
Mod/Net status - red/green Logic status - green I/O status - yellow
14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2
Product Certifications
UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives
Enclosure
IEC IP20
Min
1 Use this conductor category information for planning conductor routing as
2mA @ 10V dc
Publication 1791D-IN001A-EN-P - September 2000 described in the system level installation manual. 2
Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.
Page 23
CompactBlock I/O for DeviceNet
16 Sourcing Input Expansion Module 1791D-16V0X 23
16 Sourcing Input Expansion Module 1791D-16V0X Simplified Schematic V dc
+
24V dc
_
Input
Opto Isolation
Input Indication LED (Logic)
System Circuitry
41886
The CompactBlock expansion module I/O is exchanged with the master through a poll, changeof-state, or cyclic connection.
The following table contains the connection sizes for this module: Module(s)
Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data. Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block. Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured. This module produces 1 byte for every 8 inputs. When it is connected to a base module, an additional byte will be returned indicating the health of the expansion module.
1791D-16B0X with base input module 1791D-16B0X with base output module 1791D-16B0X with combination base module
I/O Points Produce Consume (input bytes) (output bytes) 32 input 5 0 16 input/ 3 16 output 24 input/ 8 4 output
2 1
Refer to the table below for the word/bit definitions. Bit 07 Produces I7 Produces 1 I15
06 I6 I14
Word Produces
Description Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3, ect. Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I8, bit 01 corresponds to input I9, bit 02 corresponds to input I10, bit 03 corresponds to input I11, etc.
Bit 00-07
Produces 1 08-15
05 I5 I13
04 I4 I12
03 I3 I11
02 I2 I10
01 I1 I9
00 I0 I8
Publication 1791D-IN001A-EN-P - September 2000
Page 24
24
16 Sourcing Input Expansion Module 1791D-16V0X
CompactBlock I/O for DeviceNet
The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.
General Specifications Indicators
Communication Rate Thick Cable
Flat Media
Wiring Connections Input Wiring Diagram for 1791D-16VOX Expansion Module VDC GND
IN 0
IN 4
IN 2
IN 1
IN 3
IN 5
IN 6
VDC
IN 7
IN 8
GND
IN 10 IN 12
IN 9
IN 11
IN 14
IN 13
Not Used
41670
Expansion Power Voltage Current
5V dc 100mA
Expansion Module Dimensions
113mm X 48mm X 38mm 4.4in X 1.9in X 1.5in
Environmental Conditions Operating Temperature 0 to 60°C (32 to 140°F) Non-Operating Temperature -40 to 85°C (-40 to 185°F) Relative Humidity 5-95% non-condensing Operating Shock 30 g Non-operating Shock 50g Vibration tested 5g @ 10-500Hz per IEC 68-2-6
Specifications
Inputs per Block
Category
UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives
Enclosure
IEC IP20
Min -
On-state Voltage 30V dc @ 40°C 24V dc @ 60°C
10V dc
Off-state Current 1.5mA @ 5V dc
-
On-state Current
2mA @ 10V dc
11mA @ 30V dc
Publication 1791D-IN001A-EN-P - September 2000
14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2
Product Certifications 2 groups of 8
Off-state Voltage 5V dc
125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac
Conductors Wire Size
Sourcing Inputs Max
125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft)
Isolation I/O to DeviceNet I/O group-to-group I/O group-to-logic
IN 15
+
Mod/Net status - red/green Logic status - green I/O status - yellow
1 Use this conductor category information for planning conductor routing as described in the system level installation manual. 2
Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.
Page 25
CompactBlock I/O for DeviceNet
8 Sourcing Output Base Module 1791D-0B8P
25
8 Sourcing Output Base Module 1791D-0B8P Simplified Schematic
Output Indication LED (Logic)
V dc
+ System Circuitry
Opto Isolation
Protected Output Device
Output 24V dc
Load
–
42502
Gnd
The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data. Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block. Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.
The following table contains connection sizes for this module: Module
I/O Points
1791D-0B8P 1791D-0B8P with expansion output 1791D-0B8P with expansion input
8 outputs 24 outputs 8 output/ 16 inputs
Produce (input bytes) 0 1
Consume (output bytes) 1 3
3
1
Refer to the tables below for the word/bit definitions. Bit 07 Consumes 0 O7
06 O6
05 O5
04 O4
03 O3
02 O2
01 O1
00 O0
Word Bit Consumes 0 00-07
Description Output bits - when the bit is set (1), the output will be turned on. Bit 00 corresponds to output O0, bit 01 corresponds to output 01, bit 02 to output 02, bit 03 to output 03, etc.
The module consumes 1 byte for every 8 outputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module.
Publication 1791D-IN001A-EN-P - September 2000
Page 26
26
8 Sourcing Output Base Module 1791D-0B8P
CompactBlock I/O for DeviceNet
The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.
General Specifications Indicators
Communication Rate Thick Cable
Mod/Net status - red/green Logic status - green I/O status - yellow 125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft)
Flat Media 125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft)
Wiring Connections Output Wiring Diagram for 1791D-OB8P VDC
OUT 0 GND OUT 2 GND
VDC
GND
GND OUT 1 GND OUT 3 GND
+
OUT 4 GND OUT 6 OUT 5 GND
GND
Not Used
OUT 7 GND
Load
Isolation I/O to DeviceNet I/O group-to-group I/O group-to-logic
500V ac 500V ac 500V ac
DeviceNet Power Voltage Current
11V - 25 V dc 200mA maximum (with expansion)
Auxiliary Power Voltage Current
10 - 30V dc 4A maximum
Base Module Dimensions
150mm X 48mm X 38mm 5.91 in X 1.9 in X 1.5 in
42345
_
Environmental Conditions Operating Temperature 0 to 60°C (32 to 140°F) Non-Operating Temperature -40 to 85°C (-40 to 185°F) Relative Humidity 5-95% non-condensing Operating Shock 30g Non-operating Shock 50g Vibration tested 5g @ 10-500Hz per IEC 68-2-6
Specifications
Conductors Wire Size
Sourcing Outputs Outputs per Block
8
On-state Voltage Range
10 - 30V dc
On-state Voltage Drop
0.5V dc @ rated current
On-state Current
0.5A maximum
Off-state Leakage
1.0mA maximum
Module Current (all outputs)
4.0A maximum
Surge Current - for 10ms, repeatable every 2 s
1.0A maximum
Category Product Certifications
UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives
Enclosure
IEC IP20
1
Use this conductor category information for planning conductor routing as described in the system level installation manual.
2 Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.
Publication 1791D-IN001A-EN-P - September 2000
14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2
Page 27
CompactBlock I/O for DeviceNet
16 Sourcing Output Base Module 1791D-0B16P
27
16 Sourcing Output Base Module 1791D-0B16P Simplified Schematic
Output Indication LED (Logic)
V dc
+ System Circuitry
Opto Isolation
Protected Output Device
Output 24V dc
Load
–
42502
Gnd
The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data. Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block. Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured. The module consumes 1 byte for every 8 outputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module.
The following table contains connection sizes for this module: Module
I/O Points
1791D-0B16P 1791D-0B16P with expansion output 1791D-0B16P with expansion input
16 outputs 32 outputs
Produce (input bytes) 0 1
16 output/ 16 3 inputs
Consume (output bytes) 2 4 2
Refer to the tables below for the word/bit definitions. Bit 07 Consumes 0 O7 Consumes 1 O15
06 O6 O14
Word Bit Consumes 0 00-07
Description Output bits - when the bit is set (1), the output will be turned on. Bit 00 corresponds to output O0, bit 01 corresponds to output 01, bit 02 to output 02, bit 03 to output 03, etc. Output bits - when the bit is set (1), the output will be turned on. Bit 00 corresponds to output O8, bit 01 corresponds to output O9, bit 02 to output O10, bit 03 to output O11, etc.
Consumes 1 08-15
05 O5 O13
04 O4 O12
03 O3 O11
02 O2 O10
01 O1 O9
00 O0 O8