Page 10

10

4 Sinking Input Base Module 1791D-4B0

CompactBlock I/O for DeviceNet

The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.

General Specifications Indicators

Communication Rate Thick Cable

Flat Media

Wiring Connections Input Wiring Diagram for 1791D-4BO VDC

GND

IN 1

GND

IN 0

VDC

Not Used

VDC

GND

Not Used

Not Used

Not Used

IN 2

GND VDC

IN 3

Not Used

GND VDC

Not Used

Typical PNP 3-wire sensor +

_

Not Used

42343

Max 4

DeviceNet Power Voltage Current

11V - 25 V dc 150mA maximum

Base Module Dimensions

150mm X 48mm X 38mm 5.91in X 1.9in X 1.5in

Environmental Conditions Operating Temperature 0 to 60°C (32 to 140°F) Non-Operating Temperature -40 to 85°C (-40 to 185°F) Relative Humidity 5-95% non-condensing Operating Shock 30g Non-operating Shock 50g Vibration tested 5g @ 10-500Hz per IEC 68-2-6

Category

-

On-state Voltage

10V dc

30V dc @ 40°C 25V dc @ 60°C

UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives

Enclosure

IEC IP20

1 Use this conductor category information for planning conductor routing as

Off-state Current -

1.5mA @ 5V dc

On-state Current

2mA @ 10V dc

11mA @ 30V dc

14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2

Product Certifications Min

Off-state Voltage 5V

125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac

Specifications

Inputs per Block

125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft)

Isolation I/O to DeviceNet I/O group-to-group I/O group-to-logic

Conductors Wire Size

Sinking Inputs

Mod/Net status - red/green Logic status - green I/O status - yellow

Publication 1791D-IN001A-EN-P - September 2000 described in the system level installation manual. 2

Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.

Page 11

CompactBlock I/O for DeviceNet

4 Sinking Input/4 Sourcing Output 1791D-4B4P Base Module

11

4 Sinking Input/4 Sourcing Output Base Module 1791D-4B4P Output Simplified Schematic

Input Simplified Schematic Input

Opto Isolation

System Circuitry

Input Indication LED (Logic)

Output Indication LED (Logic)

V dc

+ +

System Circuitry

Opto Isolation

Protected Output Device

Output

24V dc _

24V dc Load

–

Gnd

GND

42500

The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data.

The module produces 1 byte for every 4 inputs. Similarly, the module consumes 1 byte for every 4 outputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module. The following table contains connection sizes for this module: Module(s)

I/O Produce Points (input bytes) 4 input / 1 4 output 4 input/ 1 20 output 20 input/ 3 4 output

1791D-4B4P

Consume (output bytes) 1

Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block.

Refer to the table below for the word/bit definitions.

Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.

Bit Produces Consumes

1791D-4B4P with expansion output 1791D-4B4P with expansion input

Word Produces

Consumes

03 I3 O3

02 I2 O2

01 I1 O1

3 1

00 I0 O0

Bit Description 00-03 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3. 00-03 Output bits - when the bit is set (1), the output is on. Bit 00 corresponds to output O0, bit 01 corresponds to output 01, bit 02 to output 02, bit 03 to output 03.

Publication 1791D-IN001A-EN-P - September 2000

Page 12

12

4 Sinking Input/4 Sourcing Output 1791D-4B4P Base Module

CompactBlock I/O for DeviceNet

The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.

General Specifications Indicators

Communication Rate Thick Cable

Wiring Connections

Flat Media

Wiring Diagram for the 1791D-4B4P Base Module VDC

IN 0 GND

IN 2

VDC IN 1

VDC

VDC

IN 3

VDC

VDC

OUT 0 GND

GND

OUT 2

OUT 1 GND

GND

Not Used

OUT 3 GND

Load

+

+

_

_

Isolation Power supply to DeviceNet I/O group-to-group I/O group-to-logic DeviceNet Power Voltage Current Auxiliary Power Voltage Current Base Module Dimensions

42344

Specifications Sinking Inputs Inputs per block Off-state Voltage Current On-state Voltage Current Sourcing Outputs Outputs per block On-state Voltage Range On-state Voltage Drop On-state Current Off-state Leakage Module Current (all outputs) Surge Current - for 10 mS repeatable every 2 S

Max 4

Min

5V dc -

1.5mA @ 5Vdc

30V dc @ 40oC 25V dc @ 60oC 11mA @ 30V dc

10V dc

Environmental Conditions Operating Temperature Non-Operating Temperature Relative Humidity Operating Shock Non-operating Shock Vibration Conductors Wire Size Category Product Certifications (where product or packaging is marked)

2mA @ 10V dc Enclosure

4 10–30V dc 0.5V dc @ rated current 0.5 A 1.0mA 4.0 A 1.0 A -

Publication 1791D-IN001A-EN-P - September 2000

1

Mod/Net status - red/green Logic status - green I/O status - yellow 125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft) 125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac 11–30V dc 200mA maximum (with expansion) 10–30V dc 4A maximum 150mm X 48mm X 38mm 5.91in X 1.9in X 1.5in 0 to 60°C (32 to 140°F) -40 to 85°C (-40 to 185°F) 5-95% non-condensing 30g 50g tested 5g @ 10-500Hz per IEC 68-2-6 14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2 UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives IEC IP20

Use this conductor category information for planning conductor routing as described in the system level installation manual.

2 Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.

Page 13

CompactBlock I/O for DeviceNet

8 Sinking Input/8 Sourcing Output 1791D-8B8P Base Module

13

8 Sinking Input/8 Sourcing Output Base Module 1791D-8B8P Output Simplified Schematic

Input Simplified Schematic V dc

Opto Isolation

System Circuitry

Input Indication LED (Logic)

Output Indication LED (Logic)

V dc

+ +

System Circuitry

Opto Isolation

Protected Output Device

Output

24V dc _

24V dc Load

–

Gnd

Input

42500

The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data.

The module produces 1 byte for every 8 inputs. Similarly, the module consumes 1 byte for every 8 outputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module. The following table contains connection sizes for this module: Module(s) 1791D-8B8P

I/O Produce Points (input bytes) 8 input / 1 8 output 8 input/ 2 24 output 24 input/ 4 8 output

Consume (output bytes) 1

Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block.

Refer to the table below for the word/bit definitions.

Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.

Bit Produces Consumes

1791D-8B8P with expansion output 1791D-8B8P with expansion input

07 I7 O7

06 I6 O6

05 I5 O5

04 I4 O4

03 I3 O3

3 1

02 I2 O2

01 I1 O1

00 I0 O0

Word Bit Description Produces 00-07 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3, etc. Consumes 00-07 Output bits - when the bit is set (1), the output is on. Bit 00 corresponds to output O0, bit 01 corresponds to output 01, bit 02 to output 02, bit 03 to output 03, etc.

Publication 1791D-IN001A-EN-P - September 2000

Page 14

14

8 Sinking Input/8 Sourcing Output 1791D-8B8P Base Module

CompactBlock I/O for DeviceNet

The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.

General Specifications Indicators

Communication Rate Thick Cable

Wiring Connections

Flat Media

Wiring Diagram for the 1791D-8B8P Base Module VDC

IN 0 GND

IN 2 IN 1

IN 4

IN 3

IN 6

IN 5

-

IN 7

VDC

OUT 0 OUT 2 OUT 4 OUT 6 Not Used

GND

OUT 1 OUT 3 OUT 5 OUT 7

+ Load

+

-

41672

Specifications Sinking Inputs Inputs per block Off-state Voltage On-state Voltage Off-state Current On-state Current Sourcing Outputs On-state Voltage Range On-state Voltage Drop On-state Current Off-state Leakage Module Current (all outputs) Surge Current - for 10ms, repeatable every 2 s

Isolation Power supply to DeviceNet I/O group-to-group I/O group-to-logic DeviceNet Power Voltage Current Auxiliary Power Voltage Current Base Module Dimensions

Max 1 group of 8 5V 30V dc @ 40°C 25V dc @ 60°C 11mA @ 30V dc

Min 10V dc 1.5mA @ 5V dc 2mA @ 10V dc

10 - 30V dc 0.5V dc @ rated current 0.5A maximum 1.0mA maximum 4.0A maximum 1.0A maximum

Publication 1791D-IN001A-EN-P - September 2000

Environmental Conditions Operating Temperature Non-Operating Temperature Relative Humidity Operating Shock Non-operating Shock Vibration Conductors Wire Size Category Product Certifications (where product or packaging is marked)

Enclosure 1

Mod/Net status - red/green Logic status - green I/O status - yellow 125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft) 125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac 11V dc minimum 200mA maximum (with expansion) 10V dc minimum 4A maximum 150mm X 48mm X 38mm 5.91in X 1.9in X 1.5in 0 to 60°C (32 to 140°F) -40 to 85°C (-40 to 185°F) 5-95% non-condensing 30g 50g tested 5g @ 10-500Hz per IEC 68-2-6 14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2 UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives IEC IP20

Use this conductor category information for planning conductor routing as described in the system level installation manual.

2 Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.

Page 15

CompactBlock I/O for DeviceNet

8 Sourcing Input/8 Sinking Output 1791D-8V8P Base Module

15

8 Sourcing Input/8 Sinking Output Base Module 1791D-8V8P Output Simplified Schematic

Input Simplified Schematic V dc

Opto Isolation

System Circuitry

Input Indication LED (Logic)

Output Indication LED (Logic)

V dc +

+

System Circuitry

Opto Isolation

Protected Output Device

Output

24V dc _

24V dc Load

–

Gnd

Input

42500

The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data.

The module produces 1 byte for every 8 inputs. Similarly, the module consumes 1 byte for every 8 outputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module. The following table contains connection sizes for this module: Module(s) 1791D-8V8P

I/O Produce Points (input bytes) 8 input / 1 8 output 8 input/ 2 24 output 24 input/ 4 8 output

Consume (output bytes) 1

Change of state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block.

Refer to the table below for the word/bit definitions.

Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.

Bit Produces Consumes

07 I7 O7

Word Produces

Bit Description 00-07 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3, etc. 00-07 Output bits - when the bit is set (1), the output is on. Bit 00 corresponds to output O0, bit 01 corresponds to output 01, bit 02 to output 02, bit 03 to output 03, etc.

1791D-8V8P with expansion output 1791D-8V8P with expansion input

Consumes

06 I6 O6

05 I5 O5

04 I4 O4

03 I3 O3

3 1

02 I2 O2

01 I1 O1

00 I0 O0

Publication 1791D-IN001A-EN-P - September 2000

Page 16

16

8 Sourcing Input/8 Sinking Output 1791D-8V8P Base Module

CompactBlock I/O for DeviceNet

The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.

General Specifications Indicators

Communication Rate Thick Cable

Wiring Connections

Flat Media

Wiring Diagram for the 1791D-8V8P Base Module VDC

IN 0

GND

IN 1

IN 2 IN 3

IN 4 IN 5

VDC OUT 0 OUT 2 OUT 4 OUT 6 Not

IN 6

Used

IN 7

GND OUT 1 OUT 3 OUT 5 OUT 7

+

_

_

Load

+

Isolation Power supply to DeviceNet I/O group-to-group I/O group-to-logic DeviceNet Power Voltage Current Auxiliary Power Voltage Current Base Module Dimensions

42346

Specifications Sinking Inputs Inputs per block Off-state Voltage Current On-state Voltage Current Sourcing Outputs Outputs per block On-state Voltage Range On-state Voltage Drop On-state Current Off-state Leakage Module Current (all outputs) Surge Current - for 10 mS repeatable every 2 S

Max 8

Min

5V dc -

1.5mA @ 5Vdc

30V dc @ 40oC 25V dc @ 60oC 11mA @ 30V dc

10V dc

Environmental Conditions Operating Temperature Non-Operating Temperature Relative Humidity Operating Shock Non-operating Shock Vibration Conductors Wire Size Category Product Certifications (where product or packaging is marked)

2mA @ 10V dc Enclosure

8 10–30V dc 0.5V dc @ rated current 0.5 A 1.0mA 4.0 A 1.0 A -

Publication 1791D-IN001A-EN-P - September 2000

1

Mod/Net status - red/green Logic status - green I/O status - yellow 125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft) 125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac 11–30V dc 200mA maximum (with expansion) 10–30V dc 4A maximum 150mm X 48mm X 38mm 5.91in X 1.9in X 1.5in 0 to 60°C (32 to 140°F) -40 to 85°C (-40 to 185°F) 5-95% non-condensing 30g 50g tested 5g @ 10-500Hz per IEC 68-2-6 14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2 UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives IEC IP20

Use this conductor category information for planning conductor routing as described in the system level installation manual.

2 Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.

Page 17

CompactBlock I/O for DeviceNet

16 Sinking Input Base Module1791D-16B0

17

16 Sinking Input Base Module 1791D-16BO Simplified Schematic Input Opto Isolation

Input Indication LED (Logic)

System Circuitry

+

24V dc

_ 42501

GND

The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data.

The following table contains the connection sizes for this module: Module

I/O Points

Produce Consume (input bytes) (output bytes)

1791D-16B0

16 input

2

0

1791D-16B0 with expansion input

32 input

5

0

1791D-16B0 with expansion output

16 input/ 16 output

3

2

Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block.

Refer to the tables below for the word/bit definitions.

Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.

Word Bit Description Produces 0 00-07 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3, etc. Produces 1 08-15 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I8, bit 01 corresponds to input I9, bit 02 corresponds to input I10, bit 03 corresponds to input I11, etc.

The module produces 1 byte for every 8 inputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module.

Bit 07 Produces 0 I7 Produces 1 I15

06 I6 I14

05 I5 I13

04 I4 I12

03 I3 I11

02 I2 I10

01 I1 I9

00 I0 I8

Publication 1791D-IN001A-EN-P - September 2000

Page 18

18

16 Sinking Input Base Module1791D-16B0

CompactBlock I/O for DeviceNet

The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.

General Specifications Indicators

Communication Rate Thick Cable

Flat Media

Wiring Connections Input Wiring Diagram for 1791D-16BO VDC

IN 0 GND

IN 2

IN 1

IN 4

IN 3

IN 5

IN 6

VDC

IN 7

IN 8 GND

IN 10 IN 12

IN 9

IN 14 Not Used

IN 11 IN 13 IN 15

+ 41671

Max

Inputs per Block

2 groups of 8

Min

Off-state Voltage 5V

-

On-state Voltage

10V dc

30V dc @ 40°C 25V dc @ 60°C

Off-state Current -

1.5mA @ 5V dc

On-state Current

2mA @ 10V dc

11mA @ 30V dc

Publication 1791D-IN001A-EN-P - September 2000

125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac

DeviceNet Power Voltage Current

11V - 25 V dc 200mA maximum (with expansion)

Base Module Dimensions

150mm X 48mm X 38mm 5.91in X 1.9in X 1.5in

Environmental Conditions Operating Temperature 0 to 60°C (32 to 140°F) Non-Operating Temperature -40 to 85°C (-40 to 185°F) Relative Humidity 5-95% non-condensing Operating Shock 30g Non-operating Shock 50g Vibration tested 5g @ 10-500Hz per IEC 68-2-6

Category Sinking Inputs

125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft)

Isolation I/O to DeviceNet I/O group-to-group I/O group-to-logic

Conductors Wire Size

Specifications

Mod/Net status - red/green Logic status - green I/O status - yellow

14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2

Product Certifications

UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives

Enclosure

IEC IP20

1 Use this conductor category information for planning conductor routing as described in the system level installation manual. 2

Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.