Page 10
10
4 Sinking Input Base Module 1791D-4B0
CompactBlock I/O for DeviceNet
The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.
General Specifications Indicators
Communication Rate Thick Cable
Flat Media
Wiring Connections Input Wiring Diagram for 1791D-4BO VDC
GND
IN 1
GND
IN 0
VDC
Not Used
VDC
GND
Not Used
Not Used
Not Used
IN 2
GND VDC
IN 3
Not Used
GND VDC
Not Used
Typical PNP 3-wire sensor +
_
Not Used
42343
Max 4
DeviceNet Power Voltage Current
11V - 25 V dc 150mA maximum
Base Module Dimensions
150mm X 48mm X 38mm 5.91in X 1.9in X 1.5in
Environmental Conditions Operating Temperature 0 to 60°C (32 to 140°F) Non-Operating Temperature -40 to 85°C (-40 to 185°F) Relative Humidity 5-95% non-condensing Operating Shock 30g Non-operating Shock 50g Vibration tested 5g @ 10-500Hz per IEC 68-2-6
Category
-
On-state Voltage
10V dc
30V dc @ 40°C 25V dc @ 60°C
UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives
Enclosure
IEC IP20
1 Use this conductor category information for planning conductor routing as
Off-state Current -
1.5mA @ 5V dc
On-state Current
2mA @ 10V dc
11mA @ 30V dc
14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2
Product Certifications Min
Off-state Voltage 5V
125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac
Specifications
Inputs per Block
125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft)
Isolation I/O to DeviceNet I/O group-to-group I/O group-to-logic
Conductors Wire Size
Sinking Inputs
Mod/Net status - red/green Logic status - green I/O status - yellow
Publication 1791D-IN001A-EN-P - September 2000 described in the system level installation manual. 2
Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.
Page 11
CompactBlock I/O for DeviceNet
4 Sinking Input/4 Sourcing Output 1791D-4B4P Base Module
11
4 Sinking Input/4 Sourcing Output Base Module 1791D-4B4P Output Simplified Schematic
Input Simplified Schematic Input
Opto Isolation
System Circuitry
Input Indication LED (Logic)
Output Indication LED (Logic)
V dc
+ +
System Circuitry
Opto Isolation
Protected Output Device
Output
24V dc _
24V dc Load
–
Gnd
GND
42500
The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data.
The module produces 1 byte for every 4 inputs. Similarly, the module consumes 1 byte for every 4 outputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module. The following table contains connection sizes for this module: Module(s)
I/O Produce Points (input bytes) 4 input / 1 4 output 4 input/ 1 20 output 20 input/ 3 4 output
1791D-4B4P
Consume (output bytes) 1
Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block.
Refer to the table below for the word/bit definitions.
Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.
Bit Produces Consumes
1791D-4B4P with expansion output 1791D-4B4P with expansion input
Word Produces
Consumes
03 I3 O3
02 I2 O2
01 I1 O1
3 1
00 I0 O0
Bit Description 00-03 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3. 00-03 Output bits - when the bit is set (1), the output is on. Bit 00 corresponds to output O0, bit 01 corresponds to output 01, bit 02 to output 02, bit 03 to output 03.
Publication 1791D-IN001A-EN-P - September 2000
Page 12
12
4 Sinking Input/4 Sourcing Output 1791D-4B4P Base Module
CompactBlock I/O for DeviceNet
The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.
General Specifications Indicators
Communication Rate Thick Cable
Wiring Connections
Flat Media
Wiring Diagram for the 1791D-4B4P Base Module VDC
IN 0 GND
IN 2
VDC IN 1
VDC
VDC
IN 3
VDC
VDC
OUT 0 GND
GND
OUT 2
OUT 1 GND
GND
Not Used
OUT 3 GND
Load
+
+
_
_
Isolation Power supply to DeviceNet I/O group-to-group I/O group-to-logic DeviceNet Power Voltage Current Auxiliary Power Voltage Current Base Module Dimensions
42344
Specifications Sinking Inputs Inputs per block Off-state Voltage Current On-state Voltage Current Sourcing Outputs Outputs per block On-state Voltage Range On-state Voltage Drop On-state Current Off-state Leakage Module Current (all outputs) Surge Current - for 10 mS repeatable every 2 S
Max 4
Min
5V dc -
1.5mA @ 5Vdc
30V dc @ 40oC 25V dc @ 60oC 11mA @ 30V dc
10V dc
Environmental Conditions Operating Temperature Non-Operating Temperature Relative Humidity Operating Shock Non-operating Shock Vibration Conductors Wire Size Category Product Certifications (where product or packaging is marked)
2mA @ 10V dc Enclosure
4 10–30V dc 0.5V dc @ rated current 0.5 A 1.0mA 4.0 A 1.0 A -
Publication 1791D-IN001A-EN-P - September 2000
1
Mod/Net status - red/green Logic status - green I/O status - yellow 125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft) 125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac 11–30V dc 200mA maximum (with expansion) 10–30V dc 4A maximum 150mm X 48mm X 38mm 5.91in X 1.9in X 1.5in 0 to 60°C (32 to 140°F) -40 to 85°C (-40 to 185°F) 5-95% non-condensing 30g 50g tested 5g @ 10-500Hz per IEC 68-2-6 14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2 UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives IEC IP20
Use this conductor category information for planning conductor routing as described in the system level installation manual.
2 Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.
Page 13
CompactBlock I/O for DeviceNet
8 Sinking Input/8 Sourcing Output 1791D-8B8P Base Module
13
8 Sinking Input/8 Sourcing Output Base Module 1791D-8B8P Output Simplified Schematic
Input Simplified Schematic V dc
Opto Isolation
System Circuitry
Input Indication LED (Logic)
Output Indication LED (Logic)
V dc
+ +
System Circuitry
Opto Isolation
Protected Output Device
Output
24V dc _
24V dc Load
–
Gnd
Input
42500
The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data.
The module produces 1 byte for every 8 inputs. Similarly, the module consumes 1 byte for every 8 outputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module. The following table contains connection sizes for this module: Module(s) 1791D-8B8P
I/O Produce Points (input bytes) 8 input / 1 8 output 8 input/ 2 24 output 24 input/ 4 8 output
Consume (output bytes) 1
Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block.
Refer to the table below for the word/bit definitions.
Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.
Bit Produces Consumes
1791D-8B8P with expansion output 1791D-8B8P with expansion input
07 I7 O7
06 I6 O6
05 I5 O5
04 I4 O4
03 I3 O3
3 1
02 I2 O2
01 I1 O1
00 I0 O0
Word Bit Description Produces 00-07 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3, etc. Consumes 00-07 Output bits - when the bit is set (1), the output is on. Bit 00 corresponds to output O0, bit 01 corresponds to output 01, bit 02 to output 02, bit 03 to output 03, etc.
Publication 1791D-IN001A-EN-P - September 2000
Page 14
14
8 Sinking Input/8 Sourcing Output 1791D-8B8P Base Module
CompactBlock I/O for DeviceNet
The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.
General Specifications Indicators
Communication Rate Thick Cable
Wiring Connections
Flat Media
Wiring Diagram for the 1791D-8B8P Base Module VDC
IN 0 GND
IN 2 IN 1
IN 4
IN 3
IN 6
IN 5
-
IN 7
VDC
OUT 0 OUT 2 OUT 4 OUT 6 Not Used
GND
OUT 1 OUT 3 OUT 5 OUT 7
+ Load
+
-
41672
Specifications Sinking Inputs Inputs per block Off-state Voltage On-state Voltage Off-state Current On-state Current Sourcing Outputs On-state Voltage Range On-state Voltage Drop On-state Current Off-state Leakage Module Current (all outputs) Surge Current - for 10ms, repeatable every 2 s
Isolation Power supply to DeviceNet I/O group-to-group I/O group-to-logic DeviceNet Power Voltage Current Auxiliary Power Voltage Current Base Module Dimensions
Max 1 group of 8 5V 30V dc @ 40°C 25V dc @ 60°C 11mA @ 30V dc
Min 10V dc 1.5mA @ 5V dc 2mA @ 10V dc
10 - 30V dc 0.5V dc @ rated current 0.5A maximum 1.0mA maximum 4.0A maximum 1.0A maximum
Publication 1791D-IN001A-EN-P - September 2000
Environmental Conditions Operating Temperature Non-Operating Temperature Relative Humidity Operating Shock Non-operating Shock Vibration Conductors Wire Size Category Product Certifications (where product or packaging is marked)
Enclosure 1
Mod/Net status - red/green Logic status - green I/O status - yellow 125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft) 125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac 11V dc minimum 200mA maximum (with expansion) 10V dc minimum 4A maximum 150mm X 48mm X 38mm 5.91in X 1.9in X 1.5in 0 to 60°C (32 to 140°F) -40 to 85°C (-40 to 185°F) 5-95% non-condensing 30g 50g tested 5g @ 10-500Hz per IEC 68-2-6 14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2 UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives IEC IP20
Use this conductor category information for planning conductor routing as described in the system level installation manual.
2 Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.
Page 15
CompactBlock I/O for DeviceNet
8 Sourcing Input/8 Sinking Output 1791D-8V8P Base Module
15
8 Sourcing Input/8 Sinking Output Base Module 1791D-8V8P Output Simplified Schematic
Input Simplified Schematic V dc
Opto Isolation
System Circuitry
Input Indication LED (Logic)
Output Indication LED (Logic)
V dc +
+
System Circuitry
Opto Isolation
Protected Output Device
Output
24V dc _
24V dc Load
–
Gnd
Input
42500
The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data.
The module produces 1 byte for every 8 inputs. Similarly, the module consumes 1 byte for every 8 outputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module. The following table contains connection sizes for this module: Module(s) 1791D-8V8P
I/O Produce Points (input bytes) 8 input / 1 8 output 8 input/ 2 24 output 24 input/ 4 8 output
Consume (output bytes) 1
Change of state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block.
Refer to the table below for the word/bit definitions.
Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.
Bit Produces Consumes
07 I7 O7
Word Produces
Bit Description 00-07 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3, etc. 00-07 Output bits - when the bit is set (1), the output is on. Bit 00 corresponds to output O0, bit 01 corresponds to output 01, bit 02 to output 02, bit 03 to output 03, etc.
1791D-8V8P with expansion output 1791D-8V8P with expansion input
Consumes
06 I6 O6
05 I5 O5
04 I4 O4
03 I3 O3
3 1
02 I2 O2
01 I1 O1
00 I0 O0
Publication 1791D-IN001A-EN-P - September 2000
Page 16
16
8 Sourcing Input/8 Sinking Output 1791D-8V8P Base Module
CompactBlock I/O for DeviceNet
The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.
General Specifications Indicators
Communication Rate Thick Cable
Wiring Connections
Flat Media
Wiring Diagram for the 1791D-8V8P Base Module VDC
IN 0
GND
IN 1
IN 2 IN 3
IN 4 IN 5
VDC OUT 0 OUT 2 OUT 4 OUT 6 Not
IN 6
Used
IN 7
GND OUT 1 OUT 3 OUT 5 OUT 7
+
_
_
Load
+
Isolation Power supply to DeviceNet I/O group-to-group I/O group-to-logic DeviceNet Power Voltage Current Auxiliary Power Voltage Current Base Module Dimensions
42346
Specifications Sinking Inputs Inputs per block Off-state Voltage Current On-state Voltage Current Sourcing Outputs Outputs per block On-state Voltage Range On-state Voltage Drop On-state Current Off-state Leakage Module Current (all outputs) Surge Current - for 10 mS repeatable every 2 S
Max 8
Min
5V dc -
1.5mA @ 5Vdc
30V dc @ 40oC 25V dc @ 60oC 11mA @ 30V dc
10V dc
Environmental Conditions Operating Temperature Non-Operating Temperature Relative Humidity Operating Shock Non-operating Shock Vibration Conductors Wire Size Category Product Certifications (where product or packaging is marked)
2mA @ 10V dc Enclosure
8 10–30V dc 0.5V dc @ rated current 0.5 A 1.0mA 4.0 A 1.0 A -
Publication 1791D-IN001A-EN-P - September 2000
1
Mod/Net status - red/green Logic status - green I/O status - yellow 125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft) 125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac 11–30V dc 200mA maximum (with expansion) 10–30V dc 4A maximum 150mm X 48mm X 38mm 5.91in X 1.9in X 1.5in 0 to 60°C (32 to 140°F) -40 to 85°C (-40 to 185°F) 5-95% non-condensing 30g 50g tested 5g @ 10-500Hz per IEC 68-2-6 14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2 UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives IEC IP20
Use this conductor category information for planning conductor routing as described in the system level installation manual.
2 Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.
Page 17
CompactBlock I/O for DeviceNet
16 Sinking Input Base Module1791D-16B0
17
16 Sinking Input Base Module 1791D-16BO Simplified Schematic Input Opto Isolation
Input Indication LED (Logic)
System Circuitry
+
24V dc
_ 42501
GND
The CompactBlock base module I/O is exchanged with the master through a poll, change-of-state, or cyclic connection. Polled - a master initiates communication by sending its polled I/O message to the CompactBlock module. The module consumes the message, updates any outputs, and produces a response. If any inputs are present, the response will contain the input data.
The following table contains the connection sizes for this module: Module
I/O Points
Produce Consume (input bytes) (output bytes)
1791D-16B0
16 input
2
0
1791D-16B0 with expansion input
32 input
5
0
1791D-16B0 with expansion output
16 input/ 16 output
3
2
Change-of-state - productions occur when an input changes. If no input change occurs within the expected packet rate, a heartbeat production occurs. This heartbeat production tells the scanner module that the CompactBlock I/O module is alive and ready to communicate. Consumption occurs when data changes and the master produces new output data to the I/O block.
Refer to the tables below for the word/bit definitions.
Cyclic - allows configuration of the block as an I/O client. The block will produce and consume its I/O cyclically at the rate configured.
Word Bit Description Produces 0 00-07 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I0, bit 01 corresponds to input I1, bit 02 corresponds to input I2, bit 03 corresponds to input I3, etc. Produces 1 08-15 Input Status bits - when the bit is set (1), the input is on. Bit 00 corresponds to input I8, bit 01 corresponds to input I9, bit 02 corresponds to input I10, bit 03 corresponds to input I11, etc.
The module produces 1 byte for every 8 inputs. When an expansion module is connected, an additional byte will be returned indicating the health of the expansion module.
Bit 07 Produces 0 I7 Produces 1 I15
06 I6 I14
05 I5 I13
04 I4 I12
03 I3 I11
02 I2 I10
01 I1 I9
00 I0 I8
Publication 1791D-IN001A-EN-P - September 2000
Page 18
18
16 Sinking Input Base Module1791D-16B0
CompactBlock I/O for DeviceNet
The DeviceNet Network uses advanced network technology, producer/consumer communication, to increase network functionality and throughput. Visit our Web site at http://www.ab.com/networks for producer/consumer technology information and updates.
General Specifications Indicators
Communication Rate Thick Cable
Flat Media
Wiring Connections Input Wiring Diagram for 1791D-16BO VDC
IN 0 GND
IN 2
IN 1
IN 4
IN 3
IN 5
IN 6
VDC
IN 7
IN 8 GND
IN 10 IN 12
IN 9
IN 14 Not Used
IN 11 IN 13 IN 15
+ 41671
Max
Inputs per Block
2 groups of 8
Min
Off-state Voltage 5V
-
On-state Voltage
10V dc
30V dc @ 40°C 25V dc @ 60°C
Off-state Current -
1.5mA @ 5V dc
On-state Current
2mA @ 10V dc
11mA @ 30V dc
Publication 1791D-IN001A-EN-P - September 2000
125Kbps @ 420m (1230ft) 250Kbps @ 200m (490ft) 500Kbps @ 75m (245ft) 500V ac 500V ac 500V ac
DeviceNet Power Voltage Current
11V - 25 V dc 200mA maximum (with expansion)
Base Module Dimensions
150mm X 48mm X 38mm 5.91in X 1.9in X 1.5in
Environmental Conditions Operating Temperature 0 to 60°C (32 to 140°F) Non-Operating Temperature -40 to 85°C (-40 to 185°F) Relative Humidity 5-95% non-condensing Operating Shock 30g Non-operating Shock 50g Vibration tested 5g @ 10-500Hz per IEC 68-2-6
Category Sinking Inputs
125Kbps @ 500m (1600ft) 250Kbps @ 200m (600ft) 500Kbps @ 100m (330ft)
Isolation I/O to DeviceNet I/O group-to-group I/O group-to-logic
Conductors Wire Size
Specifications
Mod/Net status - red/green Logic status - green I/O status - yellow
14 gauge (2mm2) stranded maximum 3/64 inch insulation maximum 21, 2
Product Certifications
UL, UL Hazardous Class I, Div 2, Groups A, B, C, D. C-UL, C-UL Hazardous Class I, Div 2, Groups A, B, C, D. CE marked for all applicable directives
Enclosure
IEC IP20
1 Use this conductor category information for planning conductor routing as described in the system level installation manual. 2
Refer to, Programmable Controller Wiring and Grounding Guidelines, publication 1770-4.1.