Page 145
Get Point Status from Modules by Using Explicit Messaging
1791DS-IB12 Module Definition Configuration
Appendix A
Follow this procedure to configure the 1791DS-IB12 module definition. 1. In the Module Definition dialog box, from the Input Status pull-down menu, choose Combined Status-Muting.
This creates a 2-byte assembly, as shown for the 1791DS-IB12 module.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
145
Page 146
Appendix A
Get Point Status from Modules by Using Explicit Messaging
2. Use the CombinedStatus bit to detect if one or more of the I/O points on the module have a fault. • If the CombinedStatus bit goes to a value of 0 (0=bad, 1=good), use an explicit message to determine which individual data points have faulted. Use the CombinedStatus bits to condition your msg rung as follows. • Note that you can use the second rung to read the status on mode transition and once a fault is detected, continue reading until the fault is corrected. • Place these rungs in the standard task.
This figure shows the MSG instruction parameters for reading Instance 786 from the 1791DS-IB12 module.
In this example, we created a UDT from the destination type. • You can find the UDT called Assembly786_1791DS_IB12 in an ACD file. This UDT is based on the Assembly786 for the 1791DS_IB12 module. • There are other assemblies in the EDS file that can be used, but this one is the most inclusive. • Make sure the Communication Path is set to the correct module.
146
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 147
Get Point Status from Modules by Using Explicit Messaging
Appendix A
This figure shows the 1791DS-IB12 Assembly786 UDT.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
147
Page 148
Appendix A
Get Point Status from Modules by Using Explicit Messaging
I/O Assembly and Reference Data
See the tables for I/O assembly and reference data.
1791DS-IB12, 1791DS-IB8XOB8, 1791DS-IB4XOW4 Data The bits in the tag definitions of the Logix Designer application and RSNetWorx for DeviceNet software are different than those shown in this section. This table defines the name associations for clarification with the programming software.
148
Bit Definitions
Logix Designer Application Tag Name
Safety Input 0
Pt00Data
Safety Input 11
Pt11Data
Safety Input 0 Status
Pt00InputStatus
Safety Input 11 Status
Pt11InputStatus
Safety In Status
InputStatus
Muting Lamp Status
MutingStatus
Safety Output 0
Pt00Data
Safety Output 7
Pt07Data
Standard Output 0
Test00Data
Standard Output 3
Test03Data
Safety Output 0 Status
Pt00OutputStatus
Safety Output 7 Status
Pt07OutputStatus
Safety Out Status
OutputStatus
Safety Output 0 Monitor
Pt00Monitor
Safety Output 7 Monitor
Pt07Readback
Test Output 0 Status
Pt00TestOutputStatus
Test Output 3 Status
Pt03TestOutputStatus
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 149
Get Point Status from Modules by Using Explicit Messaging
Appendix A
These tables provide reference data concerning input and output data. Table 18 - Input Data for 1791DS-IB12, 1791DS-IB8XOB8, 1791DS-IB4XOW4 Modules Instance Hex (decimal)
Module
Byte
Bit 7
203 (515)
1791DS-IB4XOW4
0
Reserved
204 (516)
1791DS-IB8XOB8
0
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
20C (524)
1791DS-IB12
0
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
1
Reserved
0
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
1
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input Status Status Status Status Status Status 1 Status 0 Status
0
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
1
Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0 Safety Input Status Status Status Status 11
2
Safety Input 11 Status
224 (548)
22C (556)
1791DS-IB12
1791DS-IB12
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
Safety Input 11
Safety Input 10 Status
Safety Input 10
Safety Input 10
Safety Input Safety Input 9 8
Safety Input Safety Input 9 8
Safety Input 9 Safety Input 8 Safety Input 7 Safety Input 7 Safety Input Safety Input Status Status Status Status 5 Status 4 Status
300 (768)
1791DS-IB12, 1791DS-IB8XOB8, 1791DS-IB4XOW4
0
Reserved
310 (784)
1791DS-IB12
0
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
1
Muting Lamp Combined Status Safety In Status
0
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
1
Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0 Safety Input Status Status Status Status 11
2
Safety Input 11 Status
3
Muting Lamp Reserved Status
0
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
1
Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0 Safety Input Status Status Status Status 11
2
Safety Input 11 Status
3
Muting Lamp Reserved Status
0
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
1
Muting Lamp Combined Status Safety In Status
311 (785)
312 (786)
320 (800)
1791DS-IB12
1791DS-IB12
1791DS-IB8XOB8
Output Power Error
Safety Input 10 Status
Safety Input 10 Status
Reserved
Safety Input 11
Safety Input 10
Safety Input 10
Input Power Error
Safety Input Safety Input 9 8
Safety Input Safety Input 9 8
Safety Input 9 Safety Input 8 Safety Input 7 Safety Input 6 Safety Input Safety Input Status Status Status Status 5 Status 4 Status
Safety Input 10
Safety Input Safety Input 9 8
Safety Input 9 Safety Input 8 Safety Input 7 Safety Input 6 Safety Input Safety Input Status Status Status Status 5 Status 4 Status Test Output 3 Test Output 2 Test Output 1 Test Output 0 Status Status Status Status
Combined Safety Out Status
Reserved
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
149
Page 150
Appendix A
Get Point Status from Modules by Using Explicit Messaging
Table 18 - Input Data for 1791DS-IB12, 1791DS-IB8XOB8, 1791DS-IB4XOW4 Modules (continued) Instance Hex (decimal)
Module
Byte
Bit 7
321 (801)
1791DS-IB8XOB8
0
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
1
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input Status Status Status Status Status Status 1 Status 0 Status
2
Safety Output Safety Output Safety Output Safety Output 4 Safety Output Safety Output Safety Output Safety 7 Status 6 Status 5 Status Status 3 Status 2 Status 1 Status Output 0 Status
3
Muting Lamp Reserved Status
0
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
1
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input Status Status Status Status Status Status 1 Status 0 Status
2
Safety Output Safety Output Safety Output Safety Output 4 Safety Output Safety Output Safety Output Safety 7 Status 6 Status 5 Status Status 3 Status 2 Status 1 Status Output 0 Status
3
Safety Output Safety Output Safety Output Safety Output 4 Safety Output Safety Output Safety Output Safety 7 Readback 6 Readback 5 Readback Readback 3 Readback 2 Readback 1 Readback Output 0 Readback
4
Muting Lamp Reserved Status
0
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
1
Safety Input 7 Safety Input 6 Safety Input 5 Safety Input 4 Safety Input 3 Safety Input 2 Safety Input Safety Input Status Status Status Status Status Status 1 Status 0 Status
2
Safety Output Safety Output Safety Output Safety Output 4 Safety Output Safety Output Safety Output Safety 7 Status 6 Status 5 Status Status 3 Status 2 Status 1 Status Output 0 Status
3
Safety Output Safety Output Safety Output Safety Output 4 Safety Output Safety Output Safety Output Safety 7 Readback 6 Readback 5 Readback Readback 3 Readback 2 Readback 1 Readback Output 0 Readback
4
Muting Lamp Reserved Status
322 (802)
323 (803)
1791DS-IB8XOB8
1791DS-IB8XOB8
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Test Output 3 Test Output 2 Test Output 1 Test Output 0 Status Status Status Status
330 (816)
1791DS-IB4XOW4
0
Muting Lamp Combined Status Safety In Status
331 (817)
1791DS-IB4XOW4
0
Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0 Safety Input 3 Safety Input 2 Safety Input Safety Input Status Status Status Status 1 0
1
Muting Lamp Reserved Status
0
Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0 Safety Input 3 Safety Input 2 Safety Input Safety Input Status Status Status 1 0 Status
1
Safety Output Safety Output 2 Safety Output 1 Safety Output 0 Safety Output Safety Output Safety Output Safety 3 Readback Readback Readback Readback 3 Status 2 Status 1 Status Output 0 Status
2
Muting Lamp Reserved Status
0
Safety Input 3 Safety Input 2 Safety Input 1 Safety Input 0 Safety Input 3 Safety Input 2 Safety Input Safety Input Status Status Status Status 1 0
1
Safety Output Safety Output 2 Safety Output 1 Safety Output 0 Safety Output Safety Output Safety Output Safety 3 Readback Readback Readback Readback 3 Status 2 Status 1 Status Output 0 Status
2
Muting Lamp Reserved Status
332 (818)
333 (819)
150
1791DS-IB4XOW4
1791DS-IB4XOW4
Combined Safety Out Status
Reserved
Safety Input 3 Safety Input 2 Safety Input Safety Input 1 0
Safety Output Safety Output Safety Output Safety 3 Status 2 Status 1 Status Output 0 Status
Test Output 3 Test Output 2 Test Output 1 Test Output 0 Status Status Status Status
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 151
Get Point Status from Modules by Using Explicit Messaging
Appendix A
Table 18 - Input Data for 1791DS-IB12, 1791DS-IB8XOB8, 1791DS-IB4XOW4 Modules (continued) Instance Hex (decimal)
Module
Byte
Bit 7
340 (832)
1791DS-IB12
0
Reserved
1
Reserved
341 (833)
1791DS-IB8XOB8
342 (834)
1791DS-IB4XOW4
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Test Output 3 Test Output 2 Output Status Status Power Error
Input Power Error
0
Reserved
1
Safety Output Safety Output 6 Safety Output 5 Safety Output 4 Safety Output Safety Output Output 7 Readback Readback Readback Readback 3 Readback 2 Readback Power Error
Input Power Error
2
Reserved
0
Reserved
1
Test Output 3 Test Output 2 Status Status
Test Output 3 Test Output 2 Test Output 1 Test Output 0 Status Status Status Status Test Output 1 Status
Test Output 0 Status
Safety Output Safety Output Safety Output Safety 3 Readback 2 Readback 1 Readback Output 0 Readback
Table 19 - Output Data for 1791DS-IB12, 1791DS-IB8XOB8, 1791DS-IB4XOW4 Modules Instance Hex Module (decimal)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Standard Output 2
Standard Output 1
Standard Output 0
21 (33)
1791DS-IB12, 1791DS- 0 IB8XOB8, 1791DSIB4XOW4
Reserved
Standard Output 3
233 (563)
1791DS-IB4XOW4
0
Reserved
Safety Output Safety Output Safety Output Safety 3 2 1 Output 0
234 (564)
1791DS-IB8XOB8
0
Safety Output 7
Safety Output Safety 6 Output 5
Safety Output Safety 4 Output 3
Safety Output Safety 2 Output 1
Safety Output 0
350 (848)
1791DS-IB4XOW4
0
Standard Output 3
Standard Output 2
Standard Output 0
Safety Output 3
Safety Output Safety 2 Output 1
Safety Output 0
351 (849)
1791DS-IB8XOB8
0
Safety Output 7
Safety Output Safety 6 Output 5
Safety Output Safety 4 Output 3
Safety Output Safety 2 Output 1
Safety Output 0
1
Reserved
Standard Output 2
Standard Output 0
Standard Output 1
Standard Output 3
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Standard Output 1
151
Page 152
Appendix A
Get Point Status from Modules by Using Explicit Messaging
1732DS-IB8, 1732DS-IB8XOBV4, 1791DS-IB8XOBV4, and 1791DS-IB16 Data The bits in the tag definitions of the Logix Designer application and RSNetWorx software are different than those shown in this section. This table defines the name associations for clarification with the programming software. Bit Definitions
Logix Designer Application Tag Name
Safety Input 0…7
Module Name:I.Pt00Data - Pt15Data
Safety Input 0…7 Status
Module Name:I.Pt00InputStatus - Pt15InputStatus
Combined Safety In Status
Module Name:I.InputStatus
Muting Lamp Status
Module Name:I.MutingStatus
Safety Output 0…7
Module Name:O.Pt00Data - Pt07Data
Safety Output 0…7 Status
Module Name:I.Pt00OutputStatus - Pt07OutputStatus
Combined Safety Out Status
Module Name:I.OutputStatus
Safety Output 0…7 Readback
Module Name:I.Pt00Readback - Pt07Readback
Test Output 0…7 Data
Module Name:I.Test00Data - Test07Data
Test Output 0…7 Status
Module Name:I.Pt00TestOutputStatus - Pt07TestOutputStatus
These tables provide reference data concerning input and output data. Table 20 - Input Data for 1732DS-IB8, 1732DS-IB8XOBV4, 1791DS-IB8XOBV4, 1791DS-IB16 Modules Instance Hex Module (decimal)
Byte
Bit 7
204 (516)
0
Safety Input Safety Input 6 Safety Input Safety Input 4 Safety Input Safety Input 2 Safety Input 1 7 5 3
Safety Input 0
0
Safety Input Safety Input 6 Safety Input Safety Input 4 Safety Input Safety Input 2 Safety Input 1 7 5 3
Safety Input 0
1
Safety Input Safety Input 6 Safety Input Safety Input 4 Safety Input Safety Input 2 Safety Input 1 7 Status Status 5 Status Status 3 Status Status Status
Safety Input 0 Status
0
Safety Input Safety Input 6 Safety Input Safety Input 4 Safety Input Safety Input 2 Safety Input 1 7 5 3
Safety Input 0
Safety Input Safety Input 15 14
Safety Input 9
Safety Input 8
0
Safety Input Safety Input 6 Safety Input Safety Input 4 Safety Input Safety Input 2 Safety Input 1 7 5 3
Safety Input 0
1
Safety Input Safety Input 15 14
Safety Input 9
Safety Input 8
2
Safety Input Safety Input 6 Safety Input Safety Input 4 Safety Input Safety Input 2 Safety Input 1 7 Status Status 5 Status Status 3 Status Status Status
Safety Input 0 Status
3
Safety Input Safety Input 15 Status 14 Status
224 (548)
205 (517)
225 (549)
1732DS-IB8, 1732DS-IB8XOBV4, 1791DS-IB8XOBV4
1791DS-IB16
1791DS-IB16
Bit 6
Bit 5
Bit 4
Safety Input Safety Input 13 12
Safety Input Safety Input 13 12
Safety Input Safety Input 13 Status 12 Status
Bit 3
Bit 2
Safety Input Safety Input 11 10
Safety Input Safety Input 11 10
Safety Input Safety Input 10 Status 11 Status
Bit 1
Safety Input 9 Status
Bit 0
Safety Input 8 Status
300 (768)
1732DS-IB8, 1791DS-IB16
0
Reserved
301 (769)
1732DS-IB8, 1732DS-IB8XOBV4, 1791DS-IB8XOBV4
0
Reserved
Output Power Error
Input Power Error
314 (788)
1732DS-IB8
0
Safety Input Safety Input 6 Safety Input Safety Input 4 Safety Input Safety Input 2 Safety Input 1 7 5 3
Safety Input 0
1
Reserved
152
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Input Power Error
Muting Lamp 7 Muting Lamp 3 Status Status