Manual · Allen-Bradley
Guard I/O DeviceNet Safety Modules User Manual
Manual178 pagesPDF 5.2 MB
User manual for Allen-Bradley Guard I/O DeviceNet safety modules, including the 1791DS-IB12 and 1791DS-IB8XOB8.
Covers · 2 models
The models it covers
Summary
What is in it
Rockwell Automation's user manual for the ArmorBlock and CompactBlock Guard I/O DeviceNet safety modules (1732DS-IB8, 1732DS-IB8XOBV4, 1791DS-IB12, 1791DS-IB8XOB8, 1791DS-IB4XOW4, 1791DS-IB8XOBV4, 1791DS-IB16). It explains how the safety inputs, test outputs and safety outputs work, how to install and wire the modules with worked wiring examples, how to configure them in Logix Designer or RSNetWorx for DeviceNet, how to replace modules, and how to read the status indicators.
Its parts
- Preface
- About the Modules
- Understand the Operation of Safety Functions
- Install and Connect Your Modules
- Wiring Examples
- Configure Modules with the Logix Designer Application
- Configure Modules in RSNetWorx for DeviceNet Software
- Considerations When Replacing Guard I/O Modules
- Interpret Status Indicators
From the manual
Key facts from this manual
Each line names its page in the PDF.
This is the Rockwell Automation user manual, publication 1791DS-UM001J-EN-P, for Guard I/O DeviceNet safety modules. It covers the 1732DS-IB8, 1732DS-IB8XOBV4, 1791DS-IB12, 1791DS-IB8XOB8, 1791DS-IB4XOW4, 1791DS-IB8XOBV4 and 1791DS-IB16. It explains mounting, wiring, setting the node address, configuring the modules, replacing them, and reading their status indicators.
- Device type
- Safety I/O module using the CIP Safety protocol over a DeviceNet network p. 17
- Inputs
- 1791DS-IB12: safety input module, 12 inputs, 24VDC p. 19, 21
- Inputs and outputs
- 1791DS-IB8XOB8: 8 inputs and 8 solid state safety outputs, 24VDC p. 19, 21
- Mounting
- 35 mm (1.38 in.) wide DIN rail, vertical or horizontal p. 17
- Power supply
- External DC supply rated SELV, class 2 or limited voltage/current circuit per UL 508 p. 14
- Network connector
- DeviceNet: red V+, white CAN_H, shield, blue CAN_L, black V-; module powered from V+ and V- p. 46
- Node address
- Two rotary switches, 00 to 63 valid, default 63; 64 to 99 means set in RSNetWorx for DeviceNet p. 46
- Enclosure
- Install 1791DS modules in an enclosure rated IP54 (IEC60529) or higher p. 44
- Clearance
- 1791DS-IB12 and 1791DS-IB8XOB8: at least 50 mm (1.96 in.) above and below p. 17
- Test outputs
- For short circuit checks of safety inputs; can supply 24V to sensors or be set as standard outputs p. 18
- Indicators
- Module status (MS), network status (NS), configuration lock (LOCK), input power, and per-point I/O lights p. 21, 131, 132
- Connectors
- Removable I/O connectors with mechanical keying p. 18
- Safety level
- The manual states use in systems up to SIL 3 (IEC 61508) and Safety Category 4 (EN 954-1) p. 17
- SmartGuard D6
- D6 on the SmartGuard display: a 1791DS module change is not in the offline configuration p. 109
What this manual walks you through
- Mounting the module on DIN rail with the required spacing p. 44, 45
- Wiring the DeviceNet communication connector by wire color p. 46
- Setting the node address with the rotary switches p. 46
- Clearing the D6 message on a SmartGuard 600 controller p. 109
- Resetting a module that was owned by another safety controller p. 110, 111
- Setting the safety network number (SNN) after a reset p. 111, 112
- Reading the module, network, lock, power and I/O indicators p. 129, 130, 131, 132
- Proof testing each input and output point p. 161
Good to know
- Use the module only where the off state is the safe state. p. 14
- Test outputs are not safety outputs and must never be used as such. p. 15
- Test outputs set as Pulse Test or Power Supply turn on when input power is applied; reset removed modules to out-of-box condition. p. 43
- Set the node address switches only with the communication power off. p. 46
- Do not clean the module with thinner, benzene or acetone. p. 17
Questions this manual answers
How do I set the node address on a 1791DS-IB12?
With the communication power off, use the left rotary switch for the tens digit and the right one for the ones digit. Values 00 to 63 are valid and the default is 63. p. 46
What does a solid red MS light mean on a 1791DS-IB8XOB8?
A fatal hardware fault. Check for electrical noise and remove the source; if it persists, replace the module. p. 131
Why will a used 1791DS module not connect to my SmartGuard controller?
It was probably owned by a different safety controller. Reset the owner with Reset Safety Device in RSNetWorx for DeviceNet before it can make a new safety connection. p. 110
Does the 1791DS-IB12 need a separate power supply for its electronics?
The module's internal power comes from the DeviceNet communication power supply (V+ and V-). p. 46
What DIN rail does the 1791DS-IB12 mount on?
A 35 mm (1.38 in.) wide DIN rail, with an end plate on each end of the modules. p. 44
Contents
Chapters and sections
Each line opens the PDF at its page.
- Guard I/O DeviceNet Safety Modules User Manual, 1791DS-UM001J-EN-P1
- Summary of Changes3
- Preface9
- 1 - About the Modules13
- 2 - Understand the Operation of Safety Functions25
- 3 - Install and Connect Your Modules43
- 4 - Wiring Examples47
43 more lines, from page 55 on
- Bipolar Output Examples55
- 5 - Configure Modules with the Logix Designer Application61
- 6 - Configure Modules in RSNetWorx for DeviceNet Software81
- 7 - Considerations When Replacing Guard I/O Modules115
- 8 - Interpret Status Indicators129
- A - Get Point Status from Modules by Using Explicit Messaging137
- B - Safety Data161
- C - Configuration Reference Information165
- Index175
- Back Cover178
The whole text · 22 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 41-4
- Table of Contents5-8
- Preface9-12
- 1 - About the Modules13-24
- 2 - Understand the Operation of Safety Functions, pages 25 to 3325-33
- 2 - Understand the Operation of Safety Functions, pages 34 to 4234-42
- 3 - Install and Connect Your Modules43-46
- 4 - Wiring Examples47-60
- 5 - Configure Modules with the Logix Designer Application, pages 61 to 7061-70
- 5 - Configure Modules with the Logix Designer Application, pages 71 to 8071-80
- 6 - Configure Modules in RSNetWorx for DeviceNet Software, pages 81 to 8981-89
- 6 - Configure Modules in RSNetWorx for DeviceNet Software, pages 90 to 9890-98
- 6 - Configure Modules in RSNetWorx for DeviceNet Software, pages 99 to 10799-107
- 6 - Configure Modules in RSNetWorx for DeviceNet Software, pages 108 to 114108-114
- 7 - Considerations When Replacing Guard I/O Modules115-128
- 8 - Interpret Status Indicators129-136
- A - Get Point Status from Modules by Using Explicit Messaging, pages 137 to 144137-144
- A - Get Point Status from Modules by Using Explicit Messaging, pages 145 to 152145-152
- A - Get Point Status from Modules by Using Explicit Messaging, pages 153 to 160153-160
- B - Safety Data161-164
- C - Configuration Reference Information165-174
- Pages 175 to 178175-178