Guard I/O DeviceNet Safety Modules User Manual: 3 - Install and Connect Your Modules

Pages 43 to 46 of 178, from Guard I/O DeviceNet Safety Modules User Manual

The original document is the PDF (5.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12

Page 43

Chapter

3

Install and Connect Your Modules

Considerations for Module Installation

Topic

Page

Considerations for Module Installation

43

Install the Module

44

Connect I/O Power and I/O Cables

45

Connect Communication Connectors

46

Set the Node Address

46

The communication baud rate of the entire network is determined by the communication baud rate of the master unit. The communication baud rate does not need to be set for each module. ATTENTION: You can configure Test Outputs to be used as standard outputs. You can connect actuators to Test Output points that are expecting a Standard configuration. ATTENTION: Test Output points configured as Pulse Test or Power Supply become active whenever you apply input power to the module. These configured functions are independent of the I/O connections to the module.

ATTENTION: If a module with Test Outputs configured as Pulse Test or Power Supply is incorrectly installed in an application where actuators are connected to these Test Output points, the actuators will be activated when network power and input power are applied. ATTENTION: To prevent this possibility, use the following procedures: • When installing a module, be sure that the module is correctly configured for the application or in the out-of-box condition before applying input power. • When replacing a module, be sure that the module is correctly configured for the application or in the out-of-box condition before applying input power. • Reset modules to their out-of-box condition when removing them from an application. • Be sure that all modules in replacement stock are in their out-of-box condition.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

43

Page 44

Chapter 3

Install and Connect Your Modules

Install the Module Follow these instructions when installing a module: • Use the module in an environment that is within the general specifications. • Use the 1791DS modules in an enclosure rated IP54 (IEC60529) or higher. • Use DIN rail that is 35 mm (1.38 in.) wide to mount the 1791DS module in the control panel. • Always use an end plate on each end of the 1791DS modules to secure properly. • Place other heat sources an appropriate distance away from the module to maintain ambient temperatures around the module below specified maximums.

IMPORTANT

See the figures for required spacing for module installation. You can install modules horizontally or vertically.

IMPORTANT

Figure 21 - Module Installation (1791DS-IB12, 1791DS-IB8XOB8, and 1791DS-IB4XOW4 modules) 35 (1.38)

Dimensions are in mm (in.). End Plate

50 (1.96) Min

End Plate

44

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Wiring Duct

Wiring Duct

50 (1.96) Min

Page 45

Install and Connect Your Modules

Chapter 3

Figure 22 - Module Installation 35 (1.38) DIN Rail

Dimensions are in mm (in.).

Wiring Duct

15 (0.6) Min

15 (0.6) Min

Wiring Duct

Any Object

15 (0.6) Min

15 (0.6) Min

Any Object

End Plate

1732DS-IB8XOBV4 module is shown. 1732DS-IB8 modules have identical dimensions.

Connect I/O Power and I/O Cables

1791DS-IB8XOBV4 module is shown. 1791DS-IB16 modules have identical dimensions.

44225

See module installation instructions for wire type and wire size specifications. IMPORTANT

• Note that I/O connectors are detachable. • Tighten the screws on the I/O connector to the specified torque setting as shown in the installation instructions. • Since the I/O connector has a structure that helps prevent incorrect wiring, make connections at the specified locations corresponding to the terminal numbers. • When present, do not remove debris shield from the module before wiring. • When present, always remove the debris shield after completing wiring to be sure of proper heat dispersion.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

45

Page 46

Chapter 3

Install and Connect Your Modules

Connect Communication Connectors

Colored stickers on the communication connector match the colors of the wires to be inserted. Check that the colors of the wires match when wiring the connectors. The colors are as follows. Color

Signal

Red

Power cable positive side (V+)

White

High side of communication data (CAN_H)

-

Shield

Blue

Low side of communication data (CAN_L)

Black

Power cable negative side (V-)

When connecting a communication connector with the module, tighten the screws on the communication connector to the specified torque setting as shown in the installation instructions.

IMPORTANT

The internal power for the module is supplied from the communication power supply (V+, V-).

Set the Node Address

To set the node address, follow this procedure. The node-address setting rotary switches must be set while the communication power supply is turned off.

IMPORTANT

Figure 23 - Sample Node Address Digits 0

|

4

8

0

|

2 |

|

2 |

8 6

|

|

|

|

6

|

4

X10

X1

Tens Digit

Ones Digit

1. Set the node address by using the two rotary switches on the front panel of the module, noting that the default setting is 63 and a value between 00…63 is valid for proper use. 2. Use the left rotary switch to set the tens digit of node address (decimal). 3. Use the right rotary switch to set the ones digit. If the node address switches are set from 64…99, the node address needs to be set from RSNetWorx for DeviceNet software.

46

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013