Guard I/O DeviceNet Safety Modules User Manual: 3 - Install and Connect Your Modules
Pages 43 to 46 of 178, from Guard I/O DeviceNet Safety Modules User Manual
The original document is the PDF (5.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12
Page 43
Chapter
3
Install and Connect Your Modules
Considerations for Module Installation
Topic
Page
Considerations for Module Installation
43
Install the Module
44
Connect I/O Power and I/O Cables
45
Connect Communication Connectors
46
Set the Node Address
46
The communication baud rate of the entire network is determined by the communication baud rate of the master unit. The communication baud rate does not need to be set for each module. ATTENTION: You can configure Test Outputs to be used as standard outputs. You can connect actuators to Test Output points that are expecting a Standard configuration. ATTENTION: Test Output points configured as Pulse Test or Power Supply become active whenever you apply input power to the module. These configured functions are independent of the I/O connections to the module.
ATTENTION: If a module with Test Outputs configured as Pulse Test or Power Supply is incorrectly installed in an application where actuators are connected to these Test Output points, the actuators will be activated when network power and input power are applied. ATTENTION: To prevent this possibility, use the following procedures: • When installing a module, be sure that the module is correctly configured for the application or in the out-of-box condition before applying input power. • When replacing a module, be sure that the module is correctly configured for the application or in the out-of-box condition before applying input power. • Reset modules to their out-of-box condition when removing them from an application. • Be sure that all modules in replacement stock are in their out-of-box condition.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
43
Page 44
Chapter 3
Install and Connect Your Modules
Install the Module Follow these instructions when installing a module: • Use the module in an environment that is within the general specifications. • Use the 1791DS modules in an enclosure rated IP54 (IEC60529) or higher. • Use DIN rail that is 35 mm (1.38 in.) wide to mount the 1791DS module in the control panel. • Always use an end plate on each end of the 1791DS modules to secure properly. • Place other heat sources an appropriate distance away from the module to maintain ambient temperatures around the module below specified maximums.
IMPORTANT
See the figures for required spacing for module installation. You can install modules horizontally or vertically.
IMPORTANT
Figure 21 - Module Installation (1791DS-IB12, 1791DS-IB8XOB8, and 1791DS-IB4XOW4 modules) 35 (1.38)
Dimensions are in mm (in.). End Plate
50 (1.96) Min
End Plate
44
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Wiring Duct
Wiring Duct
50 (1.96) Min
Page 45
Install and Connect Your Modules
Chapter 3
Figure 22 - Module Installation 35 (1.38) DIN Rail
Dimensions are in mm (in.).
Wiring Duct
15 (0.6) Min
15 (0.6) Min
Wiring Duct
Any Object
15 (0.6) Min
15 (0.6) Min
Any Object
End Plate
1732DS-IB8XOBV4 module is shown. 1732DS-IB8 modules have identical dimensions.
Connect I/O Power and I/O Cables
1791DS-IB8XOBV4 module is shown. 1791DS-IB16 modules have identical dimensions.
44225
See module installation instructions for wire type and wire size specifications. IMPORTANT
• Note that I/O connectors are detachable. • Tighten the screws on the I/O connector to the specified torque setting as shown in the installation instructions. • Since the I/O connector has a structure that helps prevent incorrect wiring, make connections at the specified locations corresponding to the terminal numbers. • When present, do not remove debris shield from the module before wiring. • When present, always remove the debris shield after completing wiring to be sure of proper heat dispersion.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
45
Page 46
Chapter 3
Install and Connect Your Modules
Connect Communication Connectors
Colored stickers on the communication connector match the colors of the wires to be inserted. Check that the colors of the wires match when wiring the connectors. The colors are as follows. Color
Signal
Red
Power cable positive side (V+)
White
High side of communication data (CAN_H)
-
Shield
Blue
Low side of communication data (CAN_L)
Black
Power cable negative side (V-)
When connecting a communication connector with the module, tighten the screws on the communication connector to the specified torque setting as shown in the installation instructions.
IMPORTANT
The internal power for the module is supplied from the communication power supply (V+, V-).
Set the Node Address
To set the node address, follow this procedure. The node-address setting rotary switches must be set while the communication power supply is turned off.
IMPORTANT
Figure 23 - Sample Node Address Digits 0
|
4
8
0
|
2 |
|
2 |
8 6
|
|
|
|
6
|
4
X10
X1
Tens Digit
Ones Digit
1. Set the node address by using the two rotary switches on the front panel of the module, noting that the default setting is 63 and a value between 00…63 is valid for proper use. 2. Use the left rotary switch to set the tens digit of node address (decimal). 3. Use the right rotary switch to set the ones digit. If the node address switches are set from 64…99, the node address needs to be set from RSNetWorx for DeviceNet software.
46
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013