The text of a manual · part 6 of 22
Guard I/O DeviceNet Safety Modules User Manual: 2 - Understand the Operation of Safety Functions, pages 34 to 42
Pages 34 to 42 of 178, from Guard I/O DeviceNet Safety Modules User Manual
The original document is the PDF (5.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12
Page 34
Chapter 2
Understand the Operation of Safety Functions
Test Outputs Configured as Muting Outputs
When test outputs are used as muting outputs, typically for a muting lamp, a circuit test is used to diagnose whether the circuit and lamp are operational. The muting circuit test is run every 3 seconds, regardless of whether the circuit is logic HI or LO. This could cause your muting output to flicker during normal operation when it is logic LO. The muting circuit test must fail twice in succession when the muting circuit is logically HI, before a fault is declared. The results of the muting circuit test do not affect the muting status when the circuit is logically LO. A muting circuit fault will cause the muting status bit to go LO. A muting circuit fault is declared 3…6 seconds after the fault occurs if the muting circuit is logically HI for at least 6 seconds, because of the 3-second test interval and that the muting circuit test must fail twice in successession. If the muting circuit is logically HI for less than 6 seconds during a machine cycle, then the asynchronous test and program scans could cause the fault detection to be delayed for several machine cycles. There is a difference in the operation of the muting status between some of the DeviceNet safety I/O modules. This table shows the operation of the muting status of all modules. Cat. No.
Lamp
Circuit
Description
1791DS-IB16(1)
HI
Good
Muting status HI/1
Bad
Muting status LO 1 second/HI 5 seconds (repeats)
1791DS-IB8XOBV4(1) 1732DS-IB8(1) 1732DS-IB8XOBV4(1)
LO status typically appears 3…6 seconds after fault Muting status resets automatically LO
1791DS-IB12
HI
Good
Muting status LO/0
Bad
Muting status LO/0
Good
Muting status HI/1
Bad
Muting status Lo 1 second/HI 5 seconds (repeats)
1791DS-IB8XOB8 1791DS-IB4XOW4
Muting status resets automatically LO
Good
Muting status HI/1
Bad
Muting status HI/1
(1) This module’s muting status bit goes LO when a fault occurs or when the circuit is logically LO.
For catalog numbers 1791DS-IB16, 1791DS-IB8XOBV4, 1732DS-IB8, and 1732DS-IB8XOBV4, when using these GuardLogix safety application instructions that monitor muting, should include the following codes to operate properly when the muting status bit goes LO if the circuit is logically LO: • DCSTM • FSBM • TSAM • TSSM 34
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 35
Understand the Operation of Safety Functions
Chapter 2
In this code, the actual muting status bit is used in the first rung, and the DN bit of the timer is used in the muting status parameter of the instruction. The actual test output data bit is used in both the first and last rungs.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
35
Page 36
Chapter 2
Understand the Operation of Safety Functions
Safety Outputs
Read this section for information about safety outputs.
Safety Output with Test Pulse When the safety output is on, the safety output can be test pulsed, as shown in the figure and table. Using this function, short-circuits between output signal lines and the power supply (positive side) and short-circuits between output signal lines can be detected. If an error is detected, the safety output data and individual safety output status turn off. Cat. No.
Pulse Width (X)
Pulse Period (Y)
1732DS-IB8
Not applicable
Not applicable
1732DS-IB8XOBV4
700 μs
600 ms
1791DS-IB12
Not applicable
Not applicable
1791DS-IB8XOB8
470 μs
648 ms
1791DS-IB4XOW4
Not applicable
Not applicable
1791DS-IB8XOBV4
700 μs
600 ms
1791DS-IB16
Not applicable
Not applicable
Figure 19 - Test Pulse in a Cycle On
OUT X
Y
Off 44096
IMPORTANT
36
To prevent the test pulse from causing the connected device to malfunction, pay careful attention to the input response time of the device.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 37
Understand the Operation of Safety Functions
Chapter 2
Dual-channel Setting When the data of both channels is in the on state, and neither channel has a fault, the outputs are turned on. The status is normal. If a fault is detected on one channel, the safety output data and individual safety output status turn off for both channels. Figure 20 - Dual-channel Setting (not to scale) Normal Operation
OUT0
ON OFF ON
OUT1 OFF Remote I/O Data
Safety Output Status 0, 1
ON OFF ON
Fault Detection OUT0
OUT1
OFF ON OFF
Remote I/O Data
Safety Output Status 0, 1
ON
Error Detected
OFF
Safety Output Fault Recovery If a fault is detected, the safety outputs are switched off and remain in the off state. Follow this procedure to activate the safety output data again. 1. Remove the cause of the error. 2. Place the safety output (or safety outputs) into the safety state. The safety output status turns on (fault cleared) when the output-error latch time has elapsed. The I/O indicator (red) turns off. The output data can now be controlled.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
37
Page 38
Chapter 2
Understand the Operation of Safety Functions
Controlling Devices
See this table for information about controlling devices. ATTENTION: Use appropriate devices as indicated in the Controlling Device Requirements table. Serious injury may occur due to loss of safety functions.
Table 2 - Controlling Device Requirements Device Emergency stop switches Door interlocking switches, limit switches Safety sensors Relays with forcibly- guided contacts, contactors Other devices
Requirement Allen-Bradley Bulletin Safety Components Use approved devices with direct opening mechanisms complying with IEC/EN Bulletin 800F, 800T 60947-5-1. Use approved devices with direct opening mechanisms complying with IEC/EN Bulletin 440K, 440G, 440H for interlock switch 60947-5-1 and capable of switching microloads of 24V DC, 3 mA. Bulletin 440P, 802T for limit switch Use approved devices complying with the relevant product standards, Guardmaster products, refer to specific product publications for regulations, and rules in the country where used. details Use approved devices with forcibly-guided contacts complying with EN 50205. For Bulletin 700S, 100S feedback purposes, use devices with contacts capable of switching micro loads of 24V DC, 3 mA. Evaluate whether devices used are appropriate to satisfy the requirements of safety category levels.
Safety Precautions ATTENTION: As serious injury may occur due to loss of required safety function, follow these safety precautions. • Do not use test outputs of the modules as safety outputs. • Do not use DeviceNet standard I/O data or explicit message data as safety data. • Do not use LED status indicators on the I/O modules for safety operations. • Do not connect loads beyond the rated value to the safety outputs. • Wire the Guard I/O modules properly so that 24V DC line does not touch the safety outputs accidentally or unintentionally. • Clear previous configuration data before connecting devices to the network. • Set unique DeviceNet node addresses before connecting devices to the network. • Perform testing to confirm that all of the device configuration data and operation is correct before starting system operation. • When replacing a device, configure the replacement device suitably and confirm that it operates correctly. • When installing or replacing modules, clear any previous configuration before connecting input or output power to the device.
38
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 39
Understand the Operation of Safety Functions
Legislation and Standards
Chapter 2
Read this section to familiarize yourself with related legislation and standards information. Relevant international standards include the following: • IEC 61508 (SIL 1-3) • IEC 61131-2 • IEC 60204-1 • IEC 61000-6-2 • IEC 61000-6-4 • IEC 62061 The modules received the following certification from ODVA, when product is marked. • DeviceNet Conformance Test • DeviceNet Safety Conformance Test
Europe In Europe, Guard I/O modules may be subject to the European Union (EU) Machinery Directive Annex IV, B, Safety Components, items 1 and 2. The type approval of TUV-Rheinland addresses compliance to applicable requirements of the following directives and standards. • EU legislation – Machinery Directive – Low-voltage Directive – EMC Directive • European standards – EN 61508 (SIL1-3) – EN 954-1 (Category 4, 3, 2, 1, B) – EN 61131-2 – EN 418 – EN 60204-1 – IEC 61000-6-2 – IEC 61000-6-4 – IEC 13849
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
39
Page 40
Chapter 2
Understand the Operation of Safety Functions
North America In North America, the TUV-Rheinland type approval includes Guard I/O compliance to the relevant standards and related information including the following: • U.S. standards - ANSI RIA15.06, ANSI B11.19, NFPA 79 • The modules are UL-certified functionally safe and carry the NRGF label, when product is marked. • The modules received UL Listing to standards of U.S. and Canada when product is marked.
Japan In Japan, type test requirements are provided in Article 44 of the Industrial Safety and Health Law. These requirements apply to complete systems and cannot be applied to a module by itself. Accordingly, to use the module in Japan as a safety device for press machine or shearing tool pursuant to Article 42 of the abovementioned law, it is necessary to apply for testing of the entire system.
40
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 41
Understand the Operation of Safety Functions
EC Directives
Chapter 2
These products conform to the EMC Directive and Low-voltage Directive. For additional information, refer to the relevant installation instructions.
EMC Directive Rockwell Automation devices that comply with EC directives also conform to the related EMC standards so that they can more easily be built into other devices or the overall machine. The actual products have been checked for conformity to EMC standards. Whether they conform to the standards in the system used by the customer, however, must be confirmed by the customer. EMC-related performance of Rockwell Automation devices that comply with EMC directive vary depending on the configuration, wiring, and other conditions of the equipment or control panel in which the Rockwell Automation devices are installed. The customer must, therefore, perform the final check to confirm that devices and the overall machine conform to EMC standards.
Compliance with EC Directives DeviceNet products that comply with EC directives must be installed as follows: • All Type IP20 DeviceNet units must be installed within control panels. • Use reinforced insulation or double insulation for the DC power supplies used for the communication power supply, internal- circuit power supply, and the I/O power supplies. • DeviceNet products that comply with EC directives also conform to the Common Emission Standard (EN 50081-2). Radiated emission characteristics (10-m regulations) may vary depending on the configuration of the control panel used, other devices connected to the control panel, wiring, and other conditions. You must confirm that the overall machine or equipment complies with EC directives.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
41
Page 42
Chapter 2
Understand the Operation of Safety Functions
Examples to Reduce Noise These examples show how to reduce noise in 1791DS-IB12, 1791DS-IB8XOB8, and 1791DS-IB4XOW4 modules. EXAMPLE
Reduce electrical noise from the communication cable by installing a ferrite core on the communication cable within 10 cm (3.93 in.) of the DeviceNet master unit. Use Ferrite Core (Data Line Filter) LF130B, manufactured by Easy Magnet Co., or an equivalent. Impedance Specifications ImpedanceValue 25 MHz 100 MHz 250 Ω 156 Ω Ferrite Core Dimensions are in mm (in.).
30 (1.18) 13 (0.51)
33 (1.30) 29 (1.14) 31522-M
42
EXAMPLE
Wire the control panel with cables that are as short as possible and ground to 100 Ω or less.
EXAMPLE
Keep DeviceNet communication cables as short as possible and ground to 100 Ω or less.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013