Page 25
Chapter
2
Understand the Operation of Safety Functions
Topic
Page
Safety I/O Modules
25
Self-diagnostic Functions
26
Configuration Lock
26
I/O Status Data
26
Safety Inputs
26
Test Outputs Configured as Muting Outputs
34
Safety Outputs
36
Controlling Devices
38
Safety Precautions
38
Legislation and Standards
39
EC Directives
41
Read this chapter for information related to the safety functions of the modules. Also included is a brief overview on international standards and directives that you should be familiar with.
Safety I/O Modules
The following status is the safety state of the Guard I/O modules: • Safety outputs: off • Safety input data to network: off Figure 10 - Safety Status DeviceNet Network
Inputs to Network
Safety Status
Output Off
Input
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
44076
25
Page 26
Chapter 2
Understand the Operation of Safety Functions
The module is designed for use in applications where the safety state is the off state.
Self-diagnostic Functions
Self-diagnostics are performed when the power is turned on and periodically during operation. If a fatal internal module error occurs, the red module status (MS) indicator is illuminated, and the safety outputs and input data and status to the network turn off.
Configuration Lock
After configuration data has been downloaded and verified, the configuration data within the module can be protected by using RSNetWorx for DeviceNet software. For GuardLogix systems, this status indicator is not used. Reference information about safety signatures in the GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093 or the GuardLogix 5570 Controller System Safety Reference Manual, publication 1756-RM099.
I/O Status Data
In addition to I/O data, the module provides status data for monitoring the I/O circuits. The status data includes the following data, which can be read by the controllers. Note that 1 = ON/Normal and 0 = OFF/Fault/Alarm. • Individual Point Input Status • Combined Input Status • Individual Point Output Status • Combined Output Status • Individual Test Output Status • Individual Output Readback (actual ON/OFF state of the outputs) Status data indicates whether each safety input, safety output, or test output is normal (normal status: ON, faulted status: OFF). For fatal errors, communication connections may be broken, so the status data cannot be read. Status bits are OFF in the GuardLogix data table when the connection is lost. Combined status is provided by an AND of the status of all safety inputs or all safety outputs. When all inputs or outputs are normal the respective combined status is ON. When one or more of them has an error, the respective combined status is OFF. This is known as the combined safety input status or combinedsafety output status.
Safety Inputs
26
Read this section for information about safety inputs and their associated test outputs. A safety input may be used with test outputs. Safety inputs are used to monitor safety input devices.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 27
Understand the Operation of Safety Functions
Chapter 2
Using a Test Output with a Safety Input A test output can be used in combination with a safety input for short circuit detection. Configure the test output as a pulse test source and associate it to a specific safety input. The test output can also be configured for a power supply to source 24V DC for an external device, for example, a light curtain. Figure 11 - Example Use of a 1791DS-IB12 Module
24V DC Output with Test Pulse
Safety Input Terminal
External Contact
44078
24V Cat. No.
Pulse Width (X)
Pulse Period (Y)
1732DS-IB8
500 μs
600 ms
1732DS-IB8XOBV4
500 μs
600 ms
1791DS-IB12
700 μs
648 ms
1791DS-IB8XOB8
700 μs
648 ms
1791DS-IB4XOW4
700 μs
648 ms
1791DS-IB8XOBV4
500 μs
600 ms
1791DS-IB16
500 μs
600 ms
Figure 12 - Test Pulse in a Cycle On
OUT X
Y
Off
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
27
Page 28
Chapter 2
Understand the Operation of Safety Functions
When the external input contact is closed, a test pulse is output from the test output terminal to diagnose the field wiring and input circuitry. Using this function, short-circuits between input signal lines and the power supply (positive side), and short-circuits between input signal lines can be detected. Figure 13 - Short-circuit Between Input Signal Lines
24V
V
G 24V 0V
T0
External Contact
IN0
Short-circuit Between Input Signal Lines and Power Supply (positive side)
T1 External Contact
IN1
44079
Short-circuit Between Input Signal Lines
28
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 29
Understand the Operation of Safety Functions
Chapter 2
Single Channel Mode If an error is detected, safety input data and safety input status turn off. Figure 14 - Normal Operation and Fault Detection (not to scale) Normal Operation
T0
24V 0V ON
External Device OFF Input Terminal 0
ON OFF
Safety Input 0 Remote I/O Data
ON OFF
Safety Input Status 0
ON OFF 24V
Fault Detection
T0 0V ON External Device OFF Input Terminal 0
ON OFF ON
Fault Detected
Safety Input 0 OFF
Remote I/O Data Safety Input Status 0
ON OFF
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
29
Page 30
Chapter 2
Understand the Operation of Safety Functions
Dual-channel Mode and Discrepancy Time To support redundant-channel safety devices, the consistency between signals on two channels can be evaluated. Either equivalent or complementary can be selected. This function monitors the time during which there is a discrepancy between the two channels. If the length of the discrepancy exceeds the configured discrepancy time (0…65,530 ms in increments of 10 ms), the safety input data and the individualsafety input status turns off for both channels. IMPORTANT
The dual-channel function is used with two consecutive inputs that are paired together, starting at an even input number, such as inputs 0 and 1, 2 and 3, and so on.
IMPORTANT
Do not set the discrepancy time longer than necessary. The purpose of the discrepancy time is to allow for normal differences between contact switching when demands are placed on safety inputs. For this testing to operate correctly, only a single demand on the safety input is expected during the discrepancy time. If the discrepancy time is set too high, and multiple demands occur during this time, then both safety input channels will fault.
This table shows the relation between input terminal states and controller input data and status. Table 1 - Terminal Input Status and Controller I/O Data Dual-channel Mode
Dual-channels, Equivalent
Dual-channels, Complementary
Input Terminal IN0 IN1
Controller Input Data and Status Safety Safety Safety Input 0 Data Input 1 Data Input 0 Status
Safety Input 1 Status
OFF OFF ON ON OFF OFF ON ON
OFF OFF OFF ON OFF OFF ON OFF
ON OFF OFF ON OFF ON ON OFF
OFF ON OFF ON OFF ON OFF ON
OFF OFF OFF ON ON ON OFF ON
ON OFF OFF ON OFF ON ON OFF
Dual- channel DualResultant channel Data Resultant Status OFF Normal OFF Fault OFF Fault ON Normal OFF Fault OFF Normal ON Normal OFF Fault
Dual-channels, Equivalent In Equivalent mode, both inputs of a pair should typically be in the same (equivalent) state. When a transition occurs in one channel of the pair prior to the transition of the second channel of the pair, a discrepancy occurs. If the second channel transitions to the appropriate state prior to the discrepancy time elapsing, the inputs are considered equivalent. If the second transition does not occur before the discrepancy time elapses, the channels will fault. In the fault state the input and status for both channels are set low (off ). When configured as an
30
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 31
Understand the Operation of Safety Functions
Chapter 2 equivalent dual pair, the data bits for both channels will always be sent to the controller as equivalent, both high or both low. Figure 15 - Equivalent, Normal Operation and Fault Detection (not to scale) Normal Operation
IN0
ON OFF ON
IN1 OFF Discrepancy Time Safety Input 0
ON OFF
Remote I/O Data
Safety Input 1
ON OFF ON
Safety Input Status 0, 1
Fault Detection
OFF ON
IN0 OFF ON IN1 OFF Discrepancy Time Safety Input 0
ON OFF
Remote I/O Data
ON Safety Input 1 OFF Safety Input Status 0, 1
ON
Fault Detected
OFF
Dual-channels, Complementary In Complementary mode, the inputs of a pair should typically be in the opposite (complementary) state. When a transition occurs in one channel of the pair prior to the transition of the second channel of the pair, a discrepancy occurs. If the second channel transitions to the appropriate state prior to the discrepancy time elapsing, the inputs are considered complementary. If the second transition does not occur before the discrepancy time elapses, the channels will fault. The fault state of complementary inputs is the evennumbered input turned off and the odd-numbered input turned on. Note that if faulted, both channel status bits are set low. When configured as a
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
31
Page 32
Chapter 2
Understand the Operation of Safety Functions complementary dual-channel pair, the data bits for both channels will always be sent to the controller in complementary, or opposite states. Figure 16 - Complementary, Normal Operation and Fault Detection (not to scale) Normal Operation
IN0
ON OFF ON
IN1 OFF Safety Input 0
ON
Discrepancy Time
OFF Remote I/O Data
Safety Input 1
ON OFF ON
Safety Input Status 0, 1
OFF ON
Fault Detection
IN0 OFF ON IN1 OFF
Safety Input 0
Discrepancy Time
ON OFF
Remote I/O Data
ON Safety Input 1 OFF Safety Input Status 0, 1
32
ON OFF
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Fault Detected
Page 33
Understand the Operation of Safety Functions
Chapter 2
Safety Input Fault Recovery If an error is detected, the safety input data remains in the off state. Follow this procedure to activate the safety input data again. 1. Remove the cause of the error. 2. Place the safety input (or safety inputs) into the safe state. The safety input status turns on (fault cleared) after the input-error latch time has elapsed and the I/O indicator (red) turns off. The input data can now be controlled.
Input Delays On-delay - An input signal is treated as Logic 0 during the on-delay time (0…126 ms, in increments of 6 ms) after the input contact’s rising edge. The input turns on only if the input contact remains on after the on-delay time has elapsed. This helps prevent rapid changes of the input data due to contact bounce. Figure 17 - On-delay Input Signal Signal Input
ON ON OFF OFF
Remote I/O Remote I/O Data Data Safety Safety Input Input
ON ON OFF OFF
44094
On-delay ON-delay
Off-delay - An input signal is treated as Logic 1 during the off-delay time (0…126 ms, in increments of 6 ms) after the input contact’s falling edge. The input turns off only if the input contact remains off after the off delay time has elapsed. This helps prevent rapid changes of the input data due to contact bounce. Figure 18 - Off-delay Input InputSignal Signal
ON OFF OFF
Remote I/O Data Safety Input Safety Input
ON ON OFF OFF Off-delay OFF-delay 44095
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
33