For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12

Page 25

Chapter

2

Understand the Operation of Safety Functions

Topic

Page

Safety I/O Modules

25

Self-diagnostic Functions

26

Configuration Lock

26

I/O Status Data

26

Safety Inputs

26

Test Outputs Configured as Muting Outputs

34

Safety Outputs

36

Controlling Devices

38

Safety Precautions

38

Legislation and Standards

39

EC Directives

41

Read this chapter for information related to the safety functions of the modules. Also included is a brief overview on international standards and directives that you should be familiar with.

Safety I/O Modules

The following status is the safety state of the Guard I/O modules: • Safety outputs: off • Safety input data to network: off Figure 10 - Safety Status DeviceNet Network

Inputs to Network

Safety Status

Output Off

Input

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

44076

25

Page 26

Chapter 2

Understand the Operation of Safety Functions

The module is designed for use in applications where the safety state is the off state.

Self-diagnostic Functions

Self-diagnostics are performed when the power is turned on and periodically during operation. If a fatal internal module error occurs, the red module status (MS) indicator is illuminated, and the safety outputs and input data and status to the network turn off.

Configuration Lock

After configuration data has been downloaded and verified, the configuration data within the module can be protected by using RSNetWorx for DeviceNet software. For GuardLogix systems, this status indicator is not used. Reference information about safety signatures in the GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093 or the GuardLogix 5570 Controller System Safety Reference Manual, publication 1756-RM099.

I/O Status Data

In addition to I/O data, the module provides status data for monitoring the I/O circuits. The status data includes the following data, which can be read by the controllers. Note that 1 = ON/Normal and 0 = OFF/Fault/Alarm. • Individual Point Input Status • Combined Input Status • Individual Point Output Status • Combined Output Status • Individual Test Output Status • Individual Output Readback (actual ON/OFF state of the outputs) Status data indicates whether each safety input, safety output, or test output is normal (normal status: ON, faulted status: OFF). For fatal errors, communication connections may be broken, so the status data cannot be read. Status bits are OFF in the GuardLogix data table when the connection is lost. Combined status is provided by an AND of the status of all safety inputs or all safety outputs. When all inputs or outputs are normal the respective combined status is ON. When one or more of them has an error, the respective combined status is OFF. This is known as the combined safety input status or combinedsafety output status.

Safety Inputs

26

Read this section for information about safety inputs and their associated test outputs. A safety input may be used with test outputs. Safety inputs are used to monitor safety input devices.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 27

Understand the Operation of Safety Functions

Chapter 2

Using a Test Output with a Safety Input A test output can be used in combination with a safety input for short circuit detection. Configure the test output as a pulse test source and associate it to a specific safety input. The test output can also be configured for a power supply to source 24V DC for an external device, for example, a light curtain. Figure 11 - Example Use of a 1791DS-IB12 Module

24V DC Output with Test Pulse

Safety Input Terminal

External Contact

44078

24V Cat. No.

Pulse Width (X)

Pulse Period (Y)

1732DS-IB8

500 μs

600 ms

1732DS-IB8XOBV4

500 μs

600 ms

1791DS-IB12

700 μs

648 ms

1791DS-IB8XOB8

700 μs

648 ms

1791DS-IB4XOW4

700 μs

648 ms

1791DS-IB8XOBV4

500 μs

600 ms

1791DS-IB16

500 μs

600 ms

Figure 12 - Test Pulse in a Cycle On

OUT X

Y

Off

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

27

Page 28

Chapter 2

Understand the Operation of Safety Functions

When the external input contact is closed, a test pulse is output from the test output terminal to diagnose the field wiring and input circuitry. Using this function, short-circuits between input signal lines and the power supply (positive side), and short-circuits between input signal lines can be detected. Figure 13 - Short-circuit Between Input Signal Lines

24V

V

G 24V 0V

T0

External Contact

IN0

Short-circuit Between Input Signal Lines and Power Supply (positive side)

T1 External Contact

IN1

44079

Short-circuit Between Input Signal Lines

28

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 29

Understand the Operation of Safety Functions

Chapter 2

Single Channel Mode If an error is detected, safety input data and safety input status turn off. Figure 14 - Normal Operation and Fault Detection (not to scale) Normal Operation

T0

24V 0V ON

External Device OFF Input Terminal 0

ON OFF

Safety Input 0 Remote I/O Data

ON OFF

Safety Input Status 0

ON OFF 24V

Fault Detection

T0 0V ON External Device OFF Input Terminal 0

ON OFF ON

Fault Detected

Safety Input 0 OFF

Remote I/O Data Safety Input Status 0

ON OFF

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

29

Page 30

Chapter 2

Understand the Operation of Safety Functions

Dual-channel Mode and Discrepancy Time To support redundant-channel safety devices, the consistency between signals on two channels can be evaluated. Either equivalent or complementary can be selected. This function monitors the time during which there is a discrepancy between the two channels. If the length of the discrepancy exceeds the configured discrepancy time (0…65,530 ms in increments of 10 ms), the safety input data and the individualsafety input status turns off for both channels. IMPORTANT

The dual-channel function is used with two consecutive inputs that are paired together, starting at an even input number, such as inputs 0 and 1, 2 and 3, and so on.

IMPORTANT

Do not set the discrepancy time longer than necessary. The purpose of the discrepancy time is to allow for normal differences between contact switching when demands are placed on safety inputs. For this testing to operate correctly, only a single demand on the safety input is expected during the discrepancy time. If the discrepancy time is set too high, and multiple demands occur during this time, then both safety input channels will fault.

This table shows the relation between input terminal states and controller input data and status. Table 1 - Terminal Input Status and Controller I/O Data Dual-channel Mode

Dual-channels, Equivalent

Dual-channels, Complementary

Input Terminal IN0 IN1

Controller Input Data and Status Safety Safety Safety Input 0 Data Input 1 Data Input 0 Status

Safety Input 1 Status

OFF OFF ON ON OFF OFF ON ON

OFF OFF OFF ON OFF OFF ON OFF

ON OFF OFF ON OFF ON ON OFF

OFF ON OFF ON OFF ON OFF ON

OFF OFF OFF ON ON ON OFF ON

ON OFF OFF ON OFF ON ON OFF

Dual- channel DualResultant channel Data Resultant Status OFF Normal OFF Fault OFF Fault ON Normal OFF Fault OFF Normal ON Normal OFF Fault

Dual-channels, Equivalent In Equivalent mode, both inputs of a pair should typically be in the same (equivalent) state. When a transition occurs in one channel of the pair prior to the transition of the second channel of the pair, a discrepancy occurs. If the second channel transitions to the appropriate state prior to the discrepancy time elapsing, the inputs are considered equivalent. If the second transition does not occur before the discrepancy time elapses, the channels will fault. In the fault state the input and status for both channels are set low (off ). When configured as an

30

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 31

Understand the Operation of Safety Functions

Chapter 2 equivalent dual pair, the data bits for both channels will always be sent to the controller as equivalent, both high or both low. Figure 15 - Equivalent, Normal Operation and Fault Detection (not to scale) Normal Operation

IN0

ON OFF ON

IN1 OFF Discrepancy Time Safety Input 0

ON OFF

Remote I/O Data

Safety Input 1

ON OFF ON

Safety Input Status 0, 1

Fault Detection

OFF ON

IN0 OFF ON IN1 OFF Discrepancy Time Safety Input 0

ON OFF

Remote I/O Data

ON Safety Input 1 OFF Safety Input Status 0, 1

ON

Fault Detected

OFF

Dual-channels, Complementary In Complementary mode, the inputs of a pair should typically be in the opposite (complementary) state. When a transition occurs in one channel of the pair prior to the transition of the second channel of the pair, a discrepancy occurs. If the second channel transitions to the appropriate state prior to the discrepancy time elapsing, the inputs are considered complementary. If the second transition does not occur before the discrepancy time elapses, the channels will fault. The fault state of complementary inputs is the evennumbered input turned off and the odd-numbered input turned on. Note that if faulted, both channel status bits are set low. When configured as a

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

31

Page 32

Chapter 2

Understand the Operation of Safety Functions complementary dual-channel pair, the data bits for both channels will always be sent to the controller in complementary, or opposite states. Figure 16 - Complementary, Normal Operation and Fault Detection (not to scale) Normal Operation

IN0

ON OFF ON

IN1 OFF Safety Input 0

ON

Discrepancy Time

OFF Remote I/O Data

Safety Input 1

ON OFF ON

Safety Input Status 0, 1

OFF ON

Fault Detection

IN0 OFF ON IN1 OFF

Safety Input 0

Discrepancy Time

ON OFF

Remote I/O Data

ON Safety Input 1 OFF Safety Input Status 0, 1

32

ON OFF

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Fault Detected

Page 33

Understand the Operation of Safety Functions

Chapter 2

Safety Input Fault Recovery If an error is detected, the safety input data remains in the off state. Follow this procedure to activate the safety input data again. 1. Remove the cause of the error. 2. Place the safety input (or safety inputs) into the safe state. The safety input status turns on (fault cleared) after the input-error latch time has elapsed and the I/O indicator (red) turns off. The input data can now be controlled.

Input Delays On-delay - An input signal is treated as Logic 0 during the on-delay time (0…126 ms, in increments of 6 ms) after the input contact’s rising edge. The input turns on only if the input contact remains on after the on-delay time has elapsed. This helps prevent rapid changes of the input data due to contact bounce. Figure 17 - On-delay Input Signal Signal Input

ON ON OFF OFF

Remote I/O Remote I/O Data Data Safety Safety Input Input

ON ON OFF OFF

44094

On-delay ON-delay

Off-delay - An input signal is treated as Logic 1 during the off-delay time (0…126 ms, in increments of 6 ms) after the input contact’s falling edge. The input turns off only if the input contact remains off after the off delay time has elapsed. This helps prevent rapid changes of the input data due to contact bounce. Figure 18 - Off-delay Input InputSignal Signal

ON OFF OFF

Remote I/O Data Safety Input Safety Input

ON ON OFF OFF Off-delay OFF-delay 44095

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

33