Guard I/O DeviceNet Safety Modules User Manual: 1 - About the Modules

Pages 13 to 24 of 178, from Guard I/O DeviceNet Safety Modules User Manual

The original document is the PDF (5.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12

Page 13

Chapter

1

About the Modules

Topic

Page

Understand Suitability for Use

14

Follow Precautions for Use

14

Precautions to Mount, Wire, and Clean

17

I/O Module Overview

17

Guard I/O Catalog Numbers

19

About CIP Safety in DeviceNet Safety Architectures

19

Identify Major Parts of the Modules

21

This chapter includes important overview information and precautions for using Guard I/O modules that implement the DeviceNet safety protocol. Also included is an overview of how these Guard I/O modules are used within a safety system.

Before You Begin

Always observe the following guidelines when using a module, noting that in this manual we use safety administrator to mean a person qualified, authorized, and responsible to secure safety in the design, installation, operation, maintenance, and disposal of the machine. • Thoroughly read and understand this manual before installing and operating the module. • Keep this manual in a safe place where personnel can refer to it when necessary. • Use the module properly according to the installation environment, performance, and functions of the machine. • Verify that a safety administrator conducts a risk assessment on the machine and determines module suitability before installation. • Verify for CE LVD compliance, the external power supply that provides power to the modules is safety extra-low voltage (SELV) rated. Some Rockwell Automation Bulletin 1606 power supplies are SELV-compliant. Verify this in the Bulletin 1606 Installation Instructions. Verify that the Guard I/O firmware version is correct prior to commissioning the safety system, noting that firmware information related to safety controllers is available at http://www.rockwellautomation.com/products/certification/safety.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

13

Page 14

Chapter 1

About the Modules

Understand Suitability for Use

Rockwell Automation is not responsible for conformity with any standards, codes, or regulations that apply to the combination of the products in your application or use of the product. Take all necessary steps to determine the suitability of the product for the systems, machine, and equipment with which it is used. Know and observe all prohibitions of use applicable to this product. Never use the products for an application involving serious risk to life or property without making sure that the system as a whole was designed to address the risks and that the Rockwell Automation product is properly rated and installed for the intended use within the overall equipment or system.

Follow Precautions for Use ATTENTION: Safety state of the inputs and outputs is defined as the off state. Safety state of the module and its data is defined as the off state. Use the Guard I/O module only in applications where the off state is the safety state. Serious injury may occur due to breakdown of safety outputs. Do not connect loads beyond the rated value to the safety outputs. Serious injury may occur due to loss of required safety functions. Wire the module properly so that supply voltages or voltages for loads do not touch the safety outputs accidentally or inadvertently.

ATTENTION: Use DC supply satisfying the following requirements to prevent electric shock: • A DC power supply with double or reinforced insulation, for example, according to IEC/EN 60950 or EN 50178 or a transformer according to IEC/EN 61558 • A DC supply satisfies requirement for class 2 circuits or limited voltage/current circuit stated in UL 508 • Use an external power supply that is safety extra-low voltage (SELV) rated

14

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 15

About the Modules

Chapter 1

ATTENTION: Follow these precautions for safe use. • Wire conductors correctly and verify operation of the module before placing the system into operation. Incorrect wiring may lead to loss of safety function. • Do not apply DC voltages exceeding the rated voltages to the module. • Apply properly specified voltages to the module inputs. Applying inappropriate voltages may cause the module to fail to perform it’s specified function, which could lead to loss of safety functions or damage to the module. • Never use test outputs as safety outputs. Test outputs are not safety outputs. • Note that after installation of the module, a safety administrator must confirm the installation and conduct trial operation and maintenance. • Do not disassemble, repair, or modify the module. This may result in loss of safety functions. • Use only appropriate components or devices complying with relevant safety standards corresponding to the required safety category and safety integrity level. - Conformity to requirements of the safety category and safety integrity level must be determined for the entire system. - We recommend you consult a certification body regarding assessment of conformity to the required safety integrity level or safety category. • Note that you must confirm compliance with the applicable standards for the entire system. • Disconnect the module from the power supply before wiring. Devices connected to the module may operate unexpectedly if wiring is performed while power is supplied.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

15

Page 16

Chapter 1

About the Modules

For 1791DS-IB4XOW4 modules, follow these instructions on isolating transformer use. Refer to the isolating transformer figure. • Use an isolating transformer to isolate between over-voltage category III and II, such as TR1, to conform to IEC 60742. • Be sure the insulation between first input and secondary output satisfies at least basic insulation of over-voltage category III. • Be sure one side of a secondary output of the isolating transformer is grounded to prevent electric shock to personnel due to a short to ground or short to the frame of the isolating transformer. • Insert fuses, in case of a short to the frame, to protect the isolating transformer and prevent electric shock to personnel, per transformer specifications, at points such as F1, F2, and F3. Figure 1 - Use of Isolating Transformer 1791DS-IB4XOW4 Module 400V AC/ 230V AC L1

L2 L3

F4

F5 MA

MB

F3

F1 TR1 F6

F7

F8

F2

MA F1…F8 - Fuses MA, MB - Electromagnetic Switches TR1 - Insulated Transformer

MB

Load III

Over-voltage Category

II 44151

16

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 17

About the Modules

Precautions to Mount, Wire, and Clean

Chapter 1

Observe these precautions to prevent operation failure, malfunctions, or undesirable effects on product performance. Follow these precautions when mounting modules: • Use DIN rail that is 35 mm (1.38 in.) wide to mount the module into the control panel. • Mount modules to DIN rail securely. • Leave at least 50 mm (1.96 in.) above and below the module to allow adequate ventilation and room for wiring for 1791DS-IB12, 1791DSIB8XOB8, and 1791DS-IB4XOW4 modules. • Leave at least 15 mm (0.6 in.) around the module to allow adequate ventilation and room for wiring for 1732DS-IB8, 1732DS-IB8XOBV4, 1791DS-IB8XOBV4, and 1791DS-IB16 modules. Follow these precautions when wiring modules: • Do not place communication lines and I/O lines in the same wiring duct or track as high voltage lines. • Wire correctly after confirming the signal names of all terminals. • Do not remove the shield from a module before wiring, but always remove the shield after completing wiring to be sure of proper heat dispersion for 1791DS-IB12, 1791DS-IB8XOB8, and 1791DS-IB4XOW4 modules. • Follow torquing specifications as indicated in the installation instructions. When cleaning modules, do not use the following: • Thinner • Benzene • Acetone

I/O Module Overview

The Guard I/O modules implement the CIP-safety protocol extensions over DeviceNet networks and provide various features for a safety system. Use the modules to construct a safety-control network system that meets the requirements up to Safety Integrity Level 3 (SIL 3) as defined in IEC 61508, Functional Safety of Electrical, Electronic, and Programmable Electronic Safetyrelated Systems, and the requirements for Safety Category 4 of the EN 954-1 standard, Safety of machinery - Safety related parts of control systems. All 1791DS modules can be mounted vertically or horizontally. Remote I/O communication for safety I/O data are performed through safety connections supporting CIP safety over a DeviceNet network. Data processing is performed in the safety controller. The status and fault diagnostics of Guard I/O modules are monitored by a safety controller through a safety connection using a new or existing DeviceNet network.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

17

Page 18

Chapter 1

About the Modules

The following is a list of features common to Guard I/O modules: • CIP-safety and DeviceNet protocol conformance • Safety inputs – Safety devices, such as emergency stop push buttons, gate switches, and safety light curtains, can be connected. – Dual-channel mode evaluates consistency between two input signals (channels), which allows use of the module for Safety Category 3 and 4. – The time of a logical discrepancy between two channels can be monitored using a discrepancy time setting. – An external wiring short-circuit check is possible when inputs are wired in combination with test outputs. The module must be wired in combination with test outputs when this function is used. – Independently adjustable on and off delay is available per channel. • Test outputs – Separate test outputs are provided for short circuit detection of a safety input (or inputs). – Power (24V) can be supplied to devices, such as safety sensors. – Test outputs can be configured as standard outputs. – All Guard I/O modules have numerous test outputs, of which some can be used for broken wire detection of a muting lamp. • Safety outputs – Solid state outputs • Dual-channel mode evaluates consistency between two output signals (channels). • Safety outputs can be pulse tested to detect field wiring shorts to 24V DC. • All 1791DS-IB8XOBV4 modules’ safety outputs use pulse testing to detect a short to 24V DC on the safety source output (P), and a short to 0V DC on the safety sink output (M). – Relay Outputs • Dual-channel mode evaluates consistency between two output signals (channels). • Up to 2 A is provided per output point. • Safety relays can be replaced. • I/O status data - In addition to I/O data, the module includes status data for monitoring I/O circuits. • Security - The configuration information of the module can be protected by a password. • Removable I/O connectors - I/O connectors support mechanical keying.

18

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 19

About the Modules

Chapter 1

Use the minimum software versions listed here.

Programming Requirements Cat. No.

Studio 5000 Environment Version(1)

RSLogix 5000 Software Version(1) (EtherNet/IP Network)

RSNetWorx for DeviceNet RSLinx Software Software Version(1) Version(1) (DeviceNet Network)

1732DS-IB8, 1732DS-IB8XOBV4, 1791DS-IB12, 1791DS-IB8XOB8, 1791DS-IB4XOW4, 1791DS-IB8XOBV4, 1791DS-IB16

21

17

8

2.51

(1) This version or later.

Guard I/O Catalog Numbers Cat. No.

See the table for a listing of the types of Guard I/O modules.

Description

Enclosure Type Safety Inputs Test Outputs Rating

Safety Outputs Solid State

Relays

1732DS-IB8

Safety input module

-

-

Safety I/O module with solid state outputs

Meets IP64/65/ 8 67 8

8

1732DS-IB8XOBV4

8

4 bipolar pairs

-

1791DS-IB12

Safety input module

Meets IP20

12

4

-

-

1791DS-IB8XOB8

Safety I/O module with solid state outputs

8

4

8

-

1791DS-IB4XOW4

Safety I/O module with relay outputs

4

4

-

4

1791DS-IB8XOBV4

Safety I/O module with solid state outputs

8

8

4 bipolar pairs

-

1791DS-IB16

Safety input module

16

16

-

-

About CIP Safety in DeviceNet Safety Architectures

Use Guard I/O modules in DeviceNet safety architectures as shown below. The Guard I/O family is a set of I/O modules that when connected to a DeviceNet safety network are suitable for applications up to SIL3, as defined in the IEC 61508 standard, and Safety Category 4, as defined in the EN 954-1 standard.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

19

Page 20

Chapter 1

About the Modules

Figure 2 - Guard I/O Modules in DeviceNet Safety Architectures Logix Controller

GuardLogix Controller Guard PLC Controller

SmartGuard 600 Controller

DeviceNet Scanner Interface

Logix Controller

DeviceNet Network CompactBlock Guard I/O Module

RSNetWorx, Studio 5000, and RSLogixGuard Plus Software ArmorBlock Guard I/O Module

44196

Safety Communication Standard Communication

Safety controllers control the safety outputs. Safety or standard PLC controllers can control the standard outputs.

20

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 21

About the Modules

Identify Major Parts of the Modules

Chapter 1

See the figures for module identification. For pin-out information, refer to the relevant installation instructions. Figure 3 - 1791DS-IB4XOW4 Module Identification Status Indicators

Node Address Switches

Safety Relay

Communication Connector

I/O Connections

44195

Figure 4 - 1791DS-IB8XOB8 Module Identification Status Indicators

Node Address Switches

IN PWR

MS NS LOCK

0 1 2 3 4 5 6 7

OUT PWR

1791DS-IB8XOB8

0 1 2 3 4 5 6 7

CompactBlock 8 Inputs - 8 Outputs 24VDC

Communication Connector

44091

I/O Connections

Figure 5 - 1791DS-IB12 Module Identification Status Indicators

Node Address Switches

MS NS LOCK

IN PWR

0 1 2 3 4 5 6 7

8 9 10

11

CompactBlock 12 Inputs 24VDC

1791DS-IB12

Communication Connector

44091

I/O Connections

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

21

Page 22

Chapter 1

About the Modules

Figure 6 - 1791DS-IB8XOBV4 Module Identification Power Connector

I/O Connectors (output)

0

0 8 6

2 X10

Status Indicators

8

2

4 4 NODE 6 X1 ADR

Communication Connector

44224

I/O Connectors (input)

Node Address Switches

Figure 7 - 1732DS-IB8 Module Identification Node Address Switches

Communication Connector

44123

I/O Power

Inputs Status Indicators

FE

Figure 8 - 1732DS-IB8XOBV4 Module Identification Outputs

Node Address Switches

Communication Connector

44122

Inputs

Status Indicators

FE

I/O Power

22

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 23

About the Modules

Chapter 1

Figure 9 - 1791DS-IB16 Module Identification Power Connector

I/O Connectors (input)

FE

I8

I9

T8

T9

I10

I11

T10

T11M

2 X10

I13

T12

T13

I14

I15

T 14

T15M

I4

I5

T4

T5

I6

I7

T6

T7M

0

0 6

I12 1791DSIB16

NC NC

8

Status Indicators

8

2

4 4 NODE 6 X1 ADR

16 INPUTS 24 Vdc FE

I0

I1

Communication Connector

T0

T1

I2

I3

T2

T3M

44118

I/O Connectors (input)

Node Address Switches

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

23

Page 24

Chapter 1

About the Modules

Notes:

24