Guard I/O DeviceNet Safety Modules User Manual: 4 - Wiring Examples

Pages 47 to 60 of 178, from Guard I/O DeviceNet Safety Modules User Manual

The original document is the PDF (5.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12

Page 47

Chapter

4

Wiring Examples

Topic

Page

Input Examples

47

Source Output Examples

53

Bipolar Output Examples

55

Relay Output Examples

57

Test Output Examples

59

Read this chapter for information about wiring and safety categories. These examples show wiring and configuration methods for various safety categories used in SIL 2 or SIL 3 systems. For other wiring examples, refer to the Safety Accelerator Toolkit for GuardLogix Systems CD, publication SAFETY-CL002, or download toolkit files from the Integrated Architecture Tools and Resources website at http://www.ab.com/go/iatools.

Input Examples

Read this section for input examples by application. For details, refer to the installation instructions for each catalog number.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

47

Page 48

Chapter 4

Wiring Examples

Emergency Stop Switch Dual-channel Inputs with Manual Reset This example shows wiring and controller configuration when using a Guard I/O module with an emergency stop switch that has dual-channel inputs with manual reset. If used in combination with the programs in a safety controller, this wiring is Safety Category 4 in accordance with EN 954-1 wiring requirements.

FE

IN+

I0

I1

IN-

T0

T1

I2

T2

E1 S1 E1: 24V DC Power Supply S1: Emergency Stop Switch (positive opening mechanism) S2: Reset Switch FE: Functional Earth Ground

S2

Controller Configuration

Configuration Setting

Safety Input 0

Safety Input 1 Safety Input 2

48

Parameter Name

31802-M

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Dual-channel Equivalent

Dual-channel Safety Input 0/1 Discrepancy Time

100 ms (application dependent)

Safety Input 1 Channel Mode

Test Pulse from Test Output

Safety Input 1 Test Source

Test Output 1

Safety Input 2 Channel Mode

Used as Standard Input

Safety Input 2 Test Source

Not Used

Dual-channel Safety Input 2/3 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Test Output 1

Test Output 1 Mode

Pulse Test Output

Test Output 2

Test Output 2 Mode

Power Supply Output

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 49

Wiring Examples

Chapter 4

Two-hand Monitor This example shows wiring and controller configuration when using a Guard I/O module with a two-hand monitor. If used in combination with the programs in a safety controller, this wiring is Safety Category 4 in accordance with EN 954-1 wiring requirements.

S11 I0

I2

I1

I3

IN+

IN-

FE

T1 S12

T0

T2

T1

T3

T1

E1: 24V DC Power Supply S11 and S12: Two-hand Switches +

31803-M

E1

Controller Configuration Safety Input 0

Safety Input 1 Safety Input 2

Safety Input 3

Parameter Name

Configuration Setting

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Dual-channel Complementary

Dual-channel Safety Input 0/1 Discrepancy Time

100 ms (application dependent)

Safety Input 1 Channel Mode

Test Pulse from Test Output

Safety Input 1 Test Source

Test Output 1

Safety Input 2 Channel Mode

Test Pulse from Test Output

Safety Input 2 Test Source

Test Output 0

Dual-channel Safety Input 2/3 Mode

Dual-channel Complementary

Dual-channel Safety Input 2/3 Discrepancy Time

100 ms (application dependent)

Safety Input 3 Channel Mode

Test Pulse from Test Output

Safety Input 3 Test Source

Test Output 1

Test Output 0

Test Output 0 Mode

Pulse Test Output

Test Output 1

Test Output 1 Mode

Pulse Test Output

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

49

Page 50

Chapter 4

Wiring Examples

Mode Select Switch This example shows wiring and controller configuration when using a Guard I/O module with a mode select switch.

FE

IN+

I0

I1

I2

I3

I4

I5

I6

I7

IN-

T0

T1

T2

T3

T4

T5

T6

T7

S1

E1

S1

S1

S1

S1

S1

S1

E1: 24V DC Power Supply S1: Mode Select Switch FE: Functional Earth Ground

31804-M

Controller Configuration Safety Input 0

Safety Input 1 Safety Input 2

Safety Input 3 Safety Input 4

Safety Input 5 Safety Input 6

Safety Input 7

50

S1

Parameter Name

Configuration Setting

Safety Input 0 Channel Mode

Safety Input

Safety Input 0 Test Source

None

Dual-channel Safety Input 0/1 Mode

Single Channel

Safety Input 1 Channel Mode

Safety Input

Safety Input 1 Test Source

None

Safety Input 2 Channel Mode

Safety Input

Safety Input 2 Test Source

None

Dual-channel Safety Input 2/3 Mode

Single Channel

Safety Input 3 Channel Mode

Safety Input

Safety Input 3 Test Source

None

Safety Input 4 Channel Mode

Safety Input

Safety Input 4 Test Source

None

Dual-channel Safety Input 4/5 Mode

Single Channel

Safety Input 5 Channel Mode

Safety Input

Safety Input 5 Test Source

None

Safety Input 6 Channel Mode

Safety Input

Safety Input 6 Test Source

None

Dual-channel Safety Input 6/7 Mode

Single Channel

Safety Input 7 Channel Mode

Safety Input

Safety Input 7 Test Source

None

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 51

Wiring Examples

Chapter 4

Light Curtain This example shows wiring and controller configuration when using a Guard I/O module with a light curtain. If used in combination with the programs in a safety controller, this wiring is Safety Category 2, 3, or 4, based on the light curtain being used, in accordance with EN 954-1 wiring requirements. FE

IN+

IN-

0SSD2

0SSD1

24 COM

T0

I0

E1

I1

T1

Connect the OSSD1 and OSSD2 to I0 and I1, respectively. Connect the 24V power supply commons. E1: 24V DC Power Supply 31805-M

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Safety

Safety Input 0 Test Source

None

Dual-channel Safety Input 0/1 Mode

Dual-channel Equivalent

Dual-channel Safety Input 0/1 Discrepancy Time

100 ms (application dependent)

Safety Input 1 Channel Mode

Safety

Safety Input 1 Test Source

None

Safety Input 1

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

51

Page 52

Chapter 4

Wiring Examples

Reset Switch These examples show wiring and controller configuration when using a Guard I/O module with a reset switch.

I0

T0

I1

T1

Connect the switch between I0 and T0. T0 must be configured as a 24V power supply.

24V

31819-M

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Standard

Safety Input 0 Test Source

None

Test Output 0

I0

Dual-channel Safety Input 0/1 Mode

Single channel

Test Output 0 Mode

Power supply

T0

I1

T1

Connect the switch between 24V DC and I0.

24V

52

31820-M

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Standard

Safety Input 0 Test Source

None

Dual-channel Safety Input 0/1 Mode

Single channel

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 53

Wiring Examples

Chapter 4

Read this section for source output examples by application. For details, refer to the installation instructions for each catalog number.

Source Output Examples

Redundant Safety Contactors This example shows wiring and controller configuration when using a Guard I/O module with redundant safety contactors. Note that all safety outputs of this Guard I/O module are permanently configured for use as Dual-channel mode only. When used in combination with the programs of the safety controller, this circuit configuration is Safety Category 4 in accordance with EN 954-1 requirements. K1

V0

IN0

V1

OUT 0

OUT 1 K2

G0

T0

G1

G1

G1

M

K1 K1 E1

K2

E1, E2: 24V DC Power Source K1, K2: Contactor Controller Configuration Safety Input 0

K2

E2 V0, G0: Input Power Connection V1, G1: Output Power Connection

Parameter Name

31806-M

Configuration Setting

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Safety Output 0

Safety Output 0 Channel Mode

Safety Pulse Test

Dual-channel Safety Output 0/1 Mode

Dual-channel

Safety Output 1 Channel Mode

Safety Pulse Test

Safety Output 1

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

53

Page 54

Chapter 4

Wiring Examples

Single Channel This example shows wiring and controller configuration when using a Guard I/O module with a single channel. If used in combination with the programs in a safety controller, this wiring is Safety Category 4 in accordance with EN 954-1 wiring requirements.

V0

IN0

V1

OUT 0 K1

G0

T0

G1 K1

FE1

M

K1 FE2

V0, G0: Input Power Connection V1, G1: Output Power Connection M: Three-phase Motor

54

G1

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

31821-M

Page 55

Wiring Examples

Chapter 4

Read this section for bipolar output examples by application. For details, refer to the installation instructions for each catalog number.

Bipolar Output Examples

Dual-load Bipolar Outputs This example shows wiring and controller configuration when using a Guard I/O module with solid-state outputs in Dual-channel mode. Note that all safety outputs of this Guard I/O module are permanently configured for use as Dual-channel mode only. When used in combination with the programs of the safety controller, this circuit configuration is Safety Category 4 in accordance with EN 954-1 requirements. K1 K2

K2 M

K1 PS1 IN+

PS2

IN-

OUT+

OU T-

FE

O0 P

O1 M

L-

S+

02 P

03 M

L-

S+

FE

I0

I1

T0

T1

I2

I3

T2

T3M

PS1, PS2: User 24V DC power supply. (A single power supply can be used for both input and output power.)

31807-M

K1

K2

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Safety Output 0

Safety Output 0 Channel Mode

Safety Pulse Test

Safety Output 1

Safety Output 1 Channel Mode

Safety Pulse Test

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

55

Page 56

Chapter 4

Wiring Examples

Single Channel This example shows wiring and controller configuration when using a Guard I/O module with a single channel. If used in combination with the programs in a safety controller, this wiring is Safety Category 4 in accordance with EN 954-1 wiring requirements. PS1

PS2 O0P

IN+

IN-

OUT+

OU T-

FE

O0P

O1M K1

FE

E1, E2: 24V DC Power Source K1: Contactor M: Three-phase Motor

56

I0

I1

K1 PS1, PS2: User 24V DC power supply. (A single power supply can be used for both input and output power.)

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

T0

T1

M

31822-M

Page 57

Wiring Examples

Chapter 4

Read this section for relay output examples by application. For details, refer to the installation instructions for each catalog number.

Relay Output Examples

Relay Outputs with Dual-channel Mode and External Device Monitoring Input This example shows wiring and controller configuration when using a Guard I/O module with relay outputs in dual-channel mode and an external device monitoring input. If used in combination with the programs in a safety controller, this wiring is Safety Category 4 in accordance with EN 954-1 wiring requirements.

V0

I0

V1

0

1

K1 K2

G0

T0

G1

K1 E1

C1

C0

E2

F1

M

F2

K2 K2

K1 , E2: 24V DC Power Source , K2: Magnetic Contactors Three-phase Motor , F2: Fuses

V0, G0: Input Power Connection V1, G1: Output Power Connection

AC Supply

31808-M

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Safety Output 0

Safety Output 0 Channel Mode

Safety

Dual-channel Safety Output 0/1 Mode

Dual-channel

Safety Output 1

Safety Output 1 Channel Mode

Safety

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

57

Page 58

Chapter 4

Wiring Examples

Interlock String This example shows wiring and controller configuration when using a Guard I/O module with an interlock string. If used in combination with the programs in a safety controller, this wiring is Safety Category 4 in accordance with EN 954-1 wiring requirements.

0

0e 24V 24V

OUT 0 C0 1

C0E 1e

C1

C1e

Robot

OUT 1

31823-M

58

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 59

Wiring Examples

Chapter 4

Read this section for test output examples by application. For details, refer to the installation instructions for each catalog number.

Test Output Examples

Standard Inputs and Outputs This example shows wiring and controller configuration when using a Guard I/O module with standard inputs and outputs. PS1: User 24V DC power supply.

SW1

Load PS1 IN+

IN-

OUT+

FE

OU T-

I0

I1

T0

T1

I2

I3

T2

T3M

31809-M

Controller Configuration Safety Input 1

Test Pulse 0

Parameter Name

Configuration Setting

Safety Input 1 Channel Mode

Standard Input

Safety Input 1 Test Source

None

Dual-channel Safety Input 0/1 Mode

Single Channel

Test Output 0 Mode 1

Standard Output

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

59

Page 60

Chapter 4

Wiring Examples

Muting Lamp Output This example shows wiring and controller configuration when using a Guard I/O module with a muting lamp output. PS1 IN+

IN-

FE

I0

I1

T0

T1

I2

I3

T2

T3M

L1 PS1: User 24V DC Power Supply

31810-M

60

Controller Configuration

Parameter Name

Configuration Setting

Test Output 3

Test Output 3 Mode

Muting Lamp Output

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013