The text of a manual · part 9 of 22
Guard I/O DeviceNet Safety Modules User Manual: 5 - Configure Modules with the Logix Designer Application, pages 61 to 70
Pages 61 to 70 of 178, from Guard I/O DeviceNet Safety Modules User Manual
The original document is the PDF (5.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12
Page 61
Chapter
5
Configure Modules with the Logix Designer Application
.
Use the Help Button
Topic
Page
Use the Help Button
61
Add Modules to the I/O Configuration Tree
62
Set Up the Module Definition
64
Configure the Safety Tab
71
Configure the Input Configuration Tab
74
Configure the Test Output Tab
76
Configure the Output Configuration Tab
77
Save and Download Module Configuration
79
At the bottom of a dialog box, click Help for information about how to complete entries in the dialog box. At the bottom of a warning dialog box, click Help to get information about that specific error.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
61
Page 62
Chapter 5
Configure Modules with the Logix Designer Application
Add Modules to the I/O Configuration Tree
To add a module to the I/O configuration tree, follow these guidelines. 1. From the I/O Configuration tree, right-click the 1756-DNB module and choose New Module. The Select Module dialog box appears with a list that includes Safety.
2. Expand the Safety category, select the appropriate module, and click OK.
62
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 63
Configure Modules with the Logix Designer Application
Chapter 5
3. From the Module Properties dialog box, complete entries for the General dialog box.
a. For Name, type a unique name. b. For Node, choose the DeviceNet Node number, noting this number and the switches on the actual modules must match. c. For Description, if desired, type a description. d. For Safety Network Number, use the default setting. For a detailed explanation of the safety network number (SNN), see the GuardLogix Controller Systems Safety Reference Manuals listed in the Additional Resources on page 10. The purpose of the Safety Network Number (SNN) is to make sure that every module in a system can be uniquely identified. For example, assume there are two identical GuardLogix control systems - System A and System B - that are connected to a common Ethernet network. System A and System B have three DeviceNet networks with assorted standard and safety I/O modules. In systems like this, modules can have the same node number, but if each DeviceNet network has a unique SNN, each node will not have the same SNN and node number combination. Another example of the usage of SNNs is when 1756-DNB modules are in the same chassis and the DeviceNet cables are inadvertently disconnected. If the cables are reattached incorrectly, the connection in the safety modules are broken because each 1756-DNB module is now connected to devices with different SNNs. We suggest that all safety modules on a network have the same SNN, to make documentation easier. During configuration, the Logix Designer application defaults a safety device’s SNN to match the SNN of the lowest safety node on the network.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
63
Page 64
Chapter 5
Configure Modules with the Logix Designer Application
Set Up the Module Definition Follow these steps to edit the module definition. Refer to Values and States of Tags on page 70.
1. From the Module Properties dialog box, click Change.
This dialog box appears.
Integer is the only Data Format available.
2. From the Series pull-down menu, choose your module’s series level. 3. From the Revision pull-down menu, choose your module’s revision level. 4. Assign the electronic keying.
64
Choose
Description
Exact Match
All of the parameters must match or the inserted module rejects a connection to the controller.
Compatible Module
Allows an I/O module to determine whether it can emulate the module defined in the configuration sent from the controller.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 65
Configure Modules with the Logix Designer Application
Chapter 5
5. Assign the input data. Choose
Description
Safety
These tags are created for the target module: ·RunMode for module mode ·ConnectionFaulted for communication status ·Safety Data for safety inputs from the module
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
65
Page 66
Chapter 5
66
Configure Modules with the Logix Designer Application
Choose
Description
Safety-Readback
This option creates safety and readback tags, with readback indicating the presence of 24V on the output terminal. SafetyReadback is not available for input-only safety modules.
Small Safety (1791DS-IB12 module only)
This option is for 12-point safety input modules that use 8 or fewer safety inputs. The Small Safety option reduces the amount of data that the 12-point module sends to the controller to improve network performance. Safety data and point status tags are created. Point status is diagnostic status for each of the eight input points.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 67
Configure Modules with the Logix Designer Application
Chapter 5
6. Assign the input status. Choose
Description
None
There are no status tags, only data for the inputs.
Pt. Status
There is one status tag for each input and output point.
Pt. Status - Muting
There is a muting status tag for test output T3, T7, T11, and T15 with point status for each input and output point.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
67
Page 68
Chapter 5
Configure Modules with the Logix Designer Application
Choose
Description
Combined Status - Muting
·A single BOOL tag represents an AND of the status bits for all the input points. For example, if any input channel has a fault, this bit goes LO.(1) ·A single BOOL tag represents an AND of the status bits for all the output points. ·A muting status tag for test output T3, T7, T11, and T15.
Pt. Status-Muting-Test Output
·Status tags for each of the input and output points. ·Muting status tag for test output T3, T7, T11, and T15. ·Status tags for each of the test outputs.
(1) When using combined status, use explicit messaging to read individual point status for diagnostic purposes.
7. Assign the output data. IMPORTANT
68
The test outputs that are configured as standard outputs on the module must not be used for safety purposes.
Choose
Description
None
Results in an input only connection to the module. Inputs and status are read, but no outputs are written.
Safety
Creates these safety tags and enables these outputs for use in the safety task.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 69
Configure Modules with the Logix Designer Application
Chapter 5
Choose
Description
Test
Creates these tags and enables the test outputs on the module. These outputs are standard outputs and must not be used for safety purposes.
Combined
Creates these tags and enables all modules outputs, safety and test.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
69
Page 70
Chapter 5
Configure Modules with the Logix Designer Application
Values and States of Tags Use this table to determine the values and states of the tags. Data
Description
Input data Safety Input Data SAFETY
Indicates the ON/OFF status of each input circuit. ·ON: 1 OFF: 0
Output data
Combined Safety Input Status SAFETY
An AND of the status of all input circuits. ·All circuits are normal: 1 ·An error was detected in one or more input circuits: 0
Individual Safety Input Status SAFETY
Indicates the status of each input circuit. · Normal: 1 Fault (Alarm): 0
Combined Safety Output Status SAFETY
An AND of the status of all safety output circuits. ·All circuits are normal: 1 ·An error has been detected in one or more output circuits: 0
Individual Safety Output Status SAFETY
Indicates the status of each safety output circuit. ·Normal: 1 Fault (Alarm): 0
Muting Lamp Status SAFETY
Indicates the status when circuit T3, T7, T11, and T15 is configured as the muting lamp output. ·Normal: 1 Fault (Alarm): 0
Output Readback STANDARD
Monitors the presence of 24V on the output circuit. Readback is ON (1) if 24V is on output terminal. ·ON: 1 OFF: 0
Individual Test Output Status STANDARD
Indicates the status of each of the test output circuits. ·Normal:1 Fault (Alarm): 0
Safety Output Data SAFETY
Controls the safety output. ·ON: 1 OFF: 0
Standard Output Data STANDARD
Controls the test output when Test Output mode is set to a standard output. ·ON: 1 OFF: 0
IMPORTANT
70
Safety denotes information the controller can use in safety-related functions. Standard denotes additional information that must not be relied on for safety functions.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013