The text of a manual · part 10 of 22

Guard I/O DeviceNet Safety Modules User Manual: 5 - Configure Modules with the Logix Designer Application, pages 71 to 80

Pages 71 to 80 of 178, from Guard I/O DeviceNet Safety Modules User Manual

The original document is the PDF (5.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12

Page 71

Configure Modules with the Logix Designer Application

Configure the Safety Tab

Chapter 5

Read this for information about how to complete entries when you click the Safety tab. 1. From the Module Properties dialog box, click the Safety tab.

2. To configure the Requested Packet Interval (RPI), click Advanced. You see the Advanced Connection Reaction Time Limit Configuration dialog box.

For more information about the Connection Reaction Time Limit, see the GuardLogix Controllers User Manual, publication 1756-UM020.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

71

Page 72

Chapter 5

Configure Modules with the Logix Designer Application

3. In the Requested Packet Interval (RPI) box, enter the input connection RPI to support your application (between 6 and 500 ms). Selecting too small an RPI unnecessarily consumes network bandwidth; selecting too large an RPI increases safety reaction time. Selecting the appropriate RPI results in a system with optimized performance. As an example, a safety input module with only ESTOP switches connected to it generally may work well with settings of 50…100 ms. An input module with a light curtain guarding a hazard may need the fastest response that is possible. IMPORTANT

Analyze each safety channel to determine what is appropriate. The default Time-out Multiplier of 2 and Network Delay Multiplier of 200 will create an input-connection reaction time limit of four times the RPI and an output-connection reaction time limit of three times the RPI. Changes to these parameters should be approved by a safety administrator.

TIP

We recommend keeping the Time-out Multiplier and Network Delay Multiplier at their default values of 2 and 200.

A connection status tag exists for every connection.

When the connection reaction time limit and requested packet interval are set appropriately, this status tag always remains LO. Monitor all connection status bits to verify that they are not going HI intermittently due to timeouts.

72

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 73

Configure Modules with the Logix Designer Application

Chapter 5

Configuration Ownership - Reset Ownership The connection between the owner and the Guard I/O module is based on the following: · Guard I/O DeviceNet node address · Guard I/O safety network number · GuardLogix slot number · GuardLogix safety network number · Path from GuardLogix controller to Guard I/O module · Configuration signature If any of these change, the connection between the GuardLogix controller and the Guard I/O module is lost, and the yellow yield in the project tree appears. Reset ownership to reestablish the connection by using this procedure. 1. From within the Logix Designer application, open the safety I/O module properties. 2. Click the Safety tab. 3. Click Reset Ownership.

Configuration Signature The configuration signature is created by the Logix Designer application and verified by the safety module. The configuration signature provides SIL 3 integrity of the configuration of a Guard I/O module. · When a GuardLogix controller first connects to an unconfigured Guard I/O module, the complete configuration is downloaded to the I/O module. · Any time the GuardLogix controller attempts to connect to a Guard I/O module, if the configuration signatures are the same, then the configuration does not need to be downloaded, because they already match. · Any time the GuardLogix controller attempts to connect to a Guard I/O module and the signatures do not match, the module checks the module node address, electronic keying, and safety network number. If these are all correct, the controller will attempt to configure the module.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

73

Page 74

Chapter 5

Configure Modules with the Logix Designer Application

Configure the Input Configuration Tab

Follow this procedure to complete the input configuration. Refer to Chapter 2 for related information. 1. From the Module Properties dialog box, click the Input Configuration tab.

2. Assign the Point Operation Type. When you choose Equivalent or Complementary, you must also assign an appropriate Discrepancy Time. Choose

Description

Single

Inputs are treated as single channels. Note that in many cases, dualchannel safety inputs are configured as two individual single channels. This does not affect pulse testing because it is handled on an individual channel basis.

Equivalent(1)

Inputs are treated as a dual-channel pair. The channels must match within the discrepancy time or an error is generated.

Complementary(1)

Input are treated as a dual-channel pair. They must be in opposite states within the discrepancy time or an error is generated.

(1) Be aware that configuring discrepancy time on safety I/O modules masks input discrepancies detected by the controller safety instructions. Status can be read by the controller to obtain this fault information.

A discrepancy time setting of 0 ms means that the channels in a dual configuration can be discrepant for an infinite amount of time without a fault being declared. For a discrepancy time setting of 0 ms, the evaluated status of the inputs still go to the Safe State in the event of a ‘cycle inputs’ required condition, but due to the 0 ms discrepancy time, a fault will not be declared. A ‘cycle inputs’ required condition occurs when one input terminal goes from its normal Active>Inactive>Active state while the other input terminal remains in its normal Active state. Even though no fault is declared, the inputs must be cycled before the evaluated status of the inputs can return to the Active state.

74

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 75

Configure Modules with the Logix Designer Application

Chapter 5

3. Assign the Point Mode. Choose

Description

Not Used

The input is disabled. It remains logic 0 if 24V is applied to the input terminal.

Safety Pulse Test

Pulse testing is performed on this input circuit. A test source on the Guard I/O module must be used as the 24V source for this circuit. The test source is configured by using the test source pull-down menu. The pulse test will detect shorts to 24V and channel-to-channel shorts to other inputs.

Safety

A safety input is connected but there is no requirement for the Guard I/O module to perform a pulse test on this circuit. An example is a safety device that performs its own pulse tests on the input wires, such as a light curtain.

Standard

A standard device, such as a reset switch, is connected. This point cannot be used in dual-channel operation.

4. Assign the Test Source for each safety input on the module you want pulse tested. Choose

Description

None

If pulse testing is being performed on an input point, then the test source that is sourcing the 24V for the input circuit must be selected. If the incorrect test source is entered, the result is pulse test failures on that input circuit.

Test Output 0 Test Output 1 Test Output 2 Test Output 3 Test Output 4…15(1)

(1) The number of test outputs varies per catalog number.

5. Assign the Input Delay Time, Off -> On (0…126 ms, in increments of 6 ms). Filter time is for OFF to ON transition. Input must be HI after input delay has elapsed before it is set logic 1. This delay time is configured per channel with each channel specifically tuned to match the characteristics of the field device, for maximum performance.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

75

Page 76

Chapter 5

Configure Modules with the Logix Designer Application

6. Assign the Input Delay Time, On -> Off (0…126 ms, in increments of 6 ms). Filter time is ON to OFF transition. Input must be LO after input delay has elapsed before it is set logic 0. This delay time is configured per channel with each channel specifically tuned to match the characteristics of the field device, for maximum performance. 7. From the Input Error Latch Time box, enter the time the module holds an error to make sure the controller can detect it (0…65,530 ms, in increments of 10 ms - default 1000 ms). This provides you more reliable diagnostics and enhances the chances that a nuisance error is detected. The purpose for latching input errors is to make sure that intermittent faults that may only exist for a few milliseconds are latched long enough to be read by the controller. The amount of time to latch the errors should be based on the RPI, the safety task watchdog, and other application-specific variables. 8. Click OK.

Configure the Test Output Tab

This section describes how to work with the Test Output Configuration dialog box. Refer to this table for information on configuring test outputs. Follow this procedure to complete the test output configuration. 1. From the Module Properties dialog box, click the Test Output tab.

76

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 77

Configure Modules with the Logix Designer Application

Chapter 5

2. Assign the Point Mode(1). Choose

Description

Not Used (default)

The standard output is disabled.

Standard

The output point is enabled for use by the GuardLogix controller.

Pulse Test

The test output is being used as a pulse test source.

Power Supply

A constant 24V is placed on the output terminal. It can be used to provide power to a field device.

Muting Lamp Output (terminal T3, T7, T11, and T15 only)

An indicator lamp is connected to the output. When this lamp is energized, a burned-out bulb, broken wire, or short to GND error condition can be detected. Typically, the lamp is an indicator used in light curtain applications.

There is also a Test Output Fault Action parameter that can only be read or written to via explicit messaging. If communication to the module times out, you can set the test outputs to Clear OFF (default) or Hold Last State. 3. Click OK.

Configure the Output Configuration Tab

This section provides a procedure for configuring safety outputs by using the information in this table and completing the entries referring to the figure. Follow this procedure to complete the safety output configuration. 1. From the Module Properties dialog box, click the Output Configuration tab.

2. Assign the Point Operation Type. Choose

Description

Single(1)

The output is treated as a single channel.

Dual (default)

The Guard I/O module treats the outputs as a pair. It always sets them HI or LO as a matched pair. Safety logic must set both of these outputs ON or OFF as the same time or the module declares a channel fault.

(1) Does not apply to bipolar outputs. (1) Directly related to safety.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

77

Page 78

Chapter 5

Configure Modules with the Logix Designer Application

3. Assign the Point Mode. Choose

Description

Not Used (default)

The output is disabled.

Safety

The output point is enabled, and it does not perform a pulse test on the output.

Safety Pulse Test

The output point is enabled and performs a pulse test on the output. When the output is energized, the output pulses LO briefly. The pulse test detects if 24V remains on the output terminal during this LO pulse due to a short to 24V or if the output is shorted to another output terminal.

4. From the Output Error Latch Time box, enter the time the module holds an error to make sure the controller can detect it (0…65,530 ms, in increments of 10 ms - default 1000 ms). This provides you more reliable diagnostics and enhances the changes that a nuisance error is detected. The purpose for latching output errors is to make sure that intermittent faults that may only exist for a few milliseconds are latched long enough to be read by the controller. The amount of time to latch the errors will be based on the RPI, the safety task watchdog, and other application-specific variables. 5. Click OK.

78

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 79

Configure Modules with the Logix Designer Application

Save and Download Module Configuration

Chapter 5

We recommend that after a module is configured you save your work. If after downloading the program the MS and NS status indicators on the Guard I/O module are not both solid green, this may be due to loss of ownership. The ownership is based on the following: · Guard I/O DeviceNet node number · Guard I/O safety network number · GuardLogix slot number · GuardLogix safety network number · Path from GuardLogix controller to Guard I/O module · Configuration signature If any of these change, the connection between the GuardLogix controller and the Guard I/O module is lost, and the yellow yield in the project tree appears. Reset ownership to reestablish the connection using this procedure. 1. From the Module Properties dialog box, click the Safety tab.

2. Click Reset Ownership. 3. Click OK.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

79

Page 80

Chapter 5

Configure Modules with the Logix Designer Application

Notes:

80

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013