The text of a manual · part 11 of 22
Guard I/O DeviceNet Safety Modules User Manual: 6 - Configure Modules in RSNetWorx for DeviceNet Software, pages 81 to 89
Pages 81 to 89 of 178, from Guard I/O DeviceNet Safety Modules User Manual
The original document is the PDF (5.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12
Page 81
Chapter
6
Configure Modules in RSNetWorx for DeviceNet Software
Topic
Page
Before You Begin
81
Add Modules to the I/O Configuration
82
Configure the I/O Module
86
Save and Download the Module Configuration
92
Set Up the 1791DS I/O Module Definition
93
Troubleshooting
109
This chapter provides information about how to configure Guard I/O modules by using RSNetWorx for DeviceNet software and a SmartGuard controller. Refer to the corresponding software help files for network-configurator operating procedures. This chapter covers how to configure a SmartGuard controller and Guard I/O module by using Universal Serial Bus (USB) connectivity.
Before You Begin
Be sure you have these required items: • RSNetWorx for DeviceNet software, version 8.0 or later • RSLinx software, version 2.51 or later • SmartGuard USB driver The SmartGuard USB driver should already be in your RSLinx software. If it is not, load the driver onto your computer, noting the folder location as you need to browse to it later. • Personal computer with a Microsoft Windows 2000, Microsoft Windows 2000 Terminal Server, or Microsoft Windows XP operating system
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
81
Page 82
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software
Add Modules to the I/O Configuration
Follow these steps to add modules to the I/O configuration. 1. In RSNetWorx for DeviceNet software, drag the appropriate hardware onto the window to match your physical layout.
The devices have default names and node numbers when created.
2. Right-click a device and choose Properties.
82
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 83
Configure Modules in RSNetWorx for DeviceNet Software
Chapter 6
3. From the General tab, change these values. a. In the Name box, type a unique name. b. In the Description box, type a description (optional). c. In the Address box, enter the DeviceNet node number. This DeviceNet node number and the switches on the actual module must match. 4. Click the Safety tab.
On the Safety tab, you set the safety network number (SNN) and the configuration signature.
Safety Network Number (SNN) The purpose of the safety network number (SNN) is to make sure that every module in a system can be uniquely identified. For example, assume there are two identical GuardLogix control systems - System A and System B - that are connected to a common Ethernet network. System A and System B have three DeviceNet networks with assorted standard and safety I/O modules. In systems like this, modules can have the same node number, but if each DeviceNet network has a unique SNN, each node will not have the same SNN and node number combination. Another example of the usage of SNNs is when 1756-DNB modules are in the same chassis and the DeviceNet cables are inadvertently disconnected. If the cables are reattached incorrectly, the connection in the safety modules are broken because each 1756-DNB module is now connected to devices with different SNNs. We suggest that all safety modules on a network have the same SNN, to make documentation easier. During configuration, the Logix Designer application Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
83
Page 84
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software software defaults a safety device’s SNN to match the SNN of the lowest safety node on the network. The safety connection between a controller and I/O module is based on many items, one of which is the SNN of both devices. They do not have to match for a safety connection to be established, but the connection will be broken if the SNN of either device changes. The safety network defaults to match the SNN of the lowest node on the network. If your safety controller is the lowest node on the network, then all of the safety I/O modules on the network will have the same SNN as the controller. As this is the recommended method of configuring the SNN, you may not need to do anything more with the SNN. For a detailed explanation of the SNN, see the GuardLogix Controller Systems Safety Reference Manuals listed in the Additional Resources on page 10.
84
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 85
Configure Modules in RSNetWorx for DeviceNet Software
Chapter 6
Configuration Signature The configuration signature is generated by the safety module each time the configuration is changed. It consists of an ID of the module configuration and the time and date the module configuration was created or changed. The configuration signature provides SIL 3 integrity of the configuration of a Guard I/O module. The safety connection between a controller and I/O module is based on many items, one of which can be the configuration signature of the safety I/O module. If the configuration signature must match, the configuration signature must remain the same once the safety connection is established or the connection will be broken. Figure 24 - Safety Connection and Configuration Signature SmartGuard Safety Controller’s Safety Connection Tab
Safety Module’s
When configured as shown below, the I/O module configuration signature must match the offline signature for a connection to be established.
Note that the configuration signature of the safety module matches that of the SmartGuard controller, so the safety
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
85
Page 86
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software
Configure the I/O Module
The following sections use the Safety Configuration tab. Input and output points change based on the type of module that you configure.
Configure the Input Channel Follow these steps to configure the input channel. 1. Double-click Input Points xx/xx. The Input Points folder expands. In this example, 00/01 is shown.
86
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 87
Configure Modules in RSNetWorx for DeviceNet Software
Chapter 6
2. Assign the Operation Type. When you choose Equivalent or Complementary, you must also assign an appropriate operation discrepancy time. Choose
Description
Single
Inputs are treated as single channels. In many cases, dual-channel safety inputs are configured as two individual, single channels. This does not affect pulse testing because it is handled on an individual basis.
Equivalent(1)
Inputs are treated as a dual-channel pair. The channels must match within the discrepancy time or an error is generated.
Complementary(1)
Inputs are treated as a dual-channel pair. They must be in opposite states within the discrepancy time or an error is generated.
(1) Be aware that configuring discrepancy time on safety I/O modules masks input discrepancies detected by the controller safety instructions. Status can be read by the controller to obtain this fault information.
A discrepancy time setting of 0 ms means that the channels in a dual configuration can be discrepant for an infinite amount of time without a fault being declared. For a discrepancy time setting of 0 ms, the evaluated status of the inputs still go to the safe state in the event of a ‘cycle inputs’ required condition. But, due to the 0 ms discrepancy time, a fault will not be declared. A ‘cycle inputs’ required condition occurs when one input terminal goes from its normal active>inactive>active state while the other input terminal remains in its normal active state. Even though no fault is declared, the inputs must be cycles before the evaluated status of the inputs can return to the active state.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
87
Page 88
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software
3. Assign the Mode. Choose
Description
Not Used
The input is disabled. It remains logic 0 if 24V is applied to the input terminal.
Safety Pulse Test
Pulse testing is performed on this input circuit. A test source on the Guard I/o module must be used as the 24V source for this circuit. The test source is configured by using the test source pull-down menu. The pulse test will detect shorts to 24V and channel-to-channel shorts to other inputs.
Safety
A safety input is connected but there is no requirement for the Guard I/O module to perform a pulse test on this circuit. An example is a safety device that performs its own pulse tests on the input wires, such as a light curtain.
Standard
A standard device, such as a reset switch, is connected. This point cannot be used in dual-channel operation.
4. Assign the Test Source for each safety input on the module you want pulse tested. Choose
Description
None
If pulse testing is being performed on an input point, then the test source that is sourcing the 24V for the input circuit must be selected. If the incorrect test source is entered, the result is pulse test failures on that input circuit.
0 1 2 3 4…15(1)
(1) The number of test outputs varies per catalog number.
5. Assign the Input Delay Time, Off -> On (0…126 ms, in increments of 6 ms). Filter time is for OFF to ON transition. Input must be HI after input delay has elapsed before it is set logic 1. This delay time is configured per channel with each channel specifically tuned to match the characteristics of the field device, for maximum performance.
88
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 89
Configure Modules in RSNetWorx for DeviceNet Software
Chapter 6
6. Assign the Input Delay Time, Off -> On (0…126 ms, in increments of 6 ms). Filter time is ON to OFF transition. Input must be LO after input delay has elapsed before it is set logic 0. This delay time is configured per channel with each channel specifically tuned to match the characteristics of the field device, for maximum performance.
Configure the Test Output Follow these steps to configure the test outputs. 1. Double-click Test Output Points. The Test Output Points folder expands.
2. Assign the Test Output Mode. Choose
Description
Not Used (default)
The standard output is disabled.
Standard
The output point is enabled for use by the GuardLogix controller.
Pulse Test
The test output is being used as a pulse test source.
Power Supply
A constant 24V is placed on the output terminal. It can be used to provide power to a field device.
Muting Lamp Output (terminal T3, T7, T11, and T15 only)
An indicator lamp is connected to the output. When this lamp is energized, a burned-out bulb, broken wire, or short to GND error condition can be detected. Typically, the lamp is an indicator used in light curtain applications.
There is also a Test Output Fault Action parameter that can only be read or written to via explicit messaging. If communication to the module times out, you can set the test outputs to Clear OFF (default) or Hold Last State.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
89