Page 90
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software
Configure the Output Channel Follow these steps to configure the safety output channel. 1. Double-click Output Points xx/xx. The Output Points folder expands. In this example, 00/01 is shown.
2. Assign the Operation Type. Choose
Description
Single(1)
The output is treated as a single channel.
Dual (default)
The Guard I/O module treats the outputs as a pair. It always sets them HI or LO as a matched pair. Safety logic must set both of these outputs ON or OFF as the same time or the module declares a channel fault.
(1) Does not apply to bipolar outputs.
3. Assign the channel Mode. Choose
Description
Not Used (default)
The output is disabled.
Safety
The output point is enabled, and it does not perform a pulse test on the output.
Safety Pulse Test
The output point is enabled and performs a pulse test on the output. When the output is energized, the output pulses LO briefly. The pulse test detects if 24V remains on the output terminal during this LO pulse due to a short to 24V or if the output is shorted to another output terminal.
Configure Input and Output Error Latch Times Follow these steps to configure the input and output error latch times. 1. Double-click General.
90
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 91
Configure Modules in RSNetWorx for DeviceNet Software
Chapter 6
The General folder expands.
2. Enter the Input Error Latch Time, the time the module holds an error to make sure the controller can detect it (0…65,530 ms, in increments of 10 ms - default 1000 ms). This provides you more reliable diagnostics and enhances the changes that a nuisance error is detected. The purpose for latching input errors is to make sure that intermittent faults that may only exist for a few milliseconds are latched long enough to be read by the controller. The amount of time to latch the errors will be based on the RPI, the safety task watchdog, and other application-specific variables. 3. Enter the Output Error Latch Time, the time the module holds an error to make sure the controller can detect it (0…65,530 ms, in increments of 10 ms - default 1000 ms). This provides you more reliable diagnostics and enhances the changes that a nuisance error is detected. The purpose for latching output errors is to make sure that intermittent faults that may only exist for a few milliseconds are latched long enough to be read by the controller. The amount of time to latch the errors will be based on the RPI, the safety task watchdog, and other application-specific variables. 4. Click Apply.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
91
Page 92
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software
Save and Download the Module Configuration
92
We recommend that you save your work after configuring a module. If the download is successful, you see a similar message to the message below.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 93
Configure Modules in RSNetWorx for DeviceNet Software
Set Up the 1791DS I/O Module Definition
Chapter 6
Follow these steps to set up the 1791DS I/O module definition. 1. Right-click the SmartGuard controller and choose Properties. 2. Click the Safety Connection tab. All 1791DS modules that the controller could make a safety connection to should appear in the list.
The rest of these steps assumes that the module is a combination input and output module. We describe how to add two connections: one of inputs and one of outputs. You can add individual safety connections for the inputs and outputs. SmartGuard 600 controller can have as many as 32 connections. 3. Right-click the I/O module and choose Add Connection.
4. Choose the Connection Name from the pull-down menu.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
93
Page 94
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software
Make your choice based on the input data and status needs of your application.
To see the specific data that will be generated for each connection name, in the 1791DS module properties dialog box click the Safety I/O tab. Expand each choice to see the tags created for input data, input status, output data, and output status.
5. Assign the input data.
94
Choose
Description
Safety
The Safety Data tag for safety inputs from the module is created for the target module.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 95
Configure Modules in RSNetWorx for DeviceNet Software
Chapter 6
Choose
Description
Readback
This option creates safety and readback tags, with readback indicating the presence of 24V on the output terminal. SafetyReadback is not available for input-only safety modules.
Small Safety (1791DS-IB12 module only)
This option is for 12-point safety input modules that use 8 or fewer safety inputs. The Small Safety option reduces the amount of data that the 12-point module sends to the controller to improve network performance. Safety data and point status tags are created. Point status is diagnostic status for each of the eight input points.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
95
Page 96
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software
6. Assign the input status.
96
Choose
Description
None
There are no status tags, only data for the inputs.
Pt. Status
There is one status tag for each input and output point.
Pt. Status - Muting
There is a muting status tag for test output T3, T7, T11, and T15 with point status for each input and output point.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 97
Configure Modules in RSNetWorx for DeviceNet Software
Choose
Chapter 6
Description
Combined Status - Muting
·A single BOOL tag represents an AND of the status bits for all the input points. For example, if any input channel has a fault, this bit goes LO.(1) ·A single BOOL tag represents an AND of the status bits for all the output points. ·A muting status tag for test output T3, T7, T11, and T15.
Pt. Status-Muting-Test Output
·Status tags for each of the input and output points. ·Muting status tag for test output T3, T7, T11, and T15. ·Status tags for each of the test outputs.
(1) When using combined status, use explicit messaging to read individual point status for diagnostic purposes.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
97
Page 98
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software
7. Assign the output data. IMPORTANT
98
The test outputs that are configured as standard outputs on the module must not be used for safety purposes.
Choose
Description
None
Results in an input only connection to the module. Inputs and status are read, but no outputs are written.
Safety
Creates these safety tags and enables these outputs for use in the safety task.
Test
Creates these tags and enables the test outputs on the module. These outputs are standard outputs and must not be used for safety purposes.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013