For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12
Page 99
Configure Modules in RSNetWorx for DeviceNet Software
Chapter 6
Choose
Description
Combined
Creates these tags and enables all modules outputs, safety and test.
Typically, you should choose Combined Status for the input status. This limits the packet size for normal communication. If you need detailed status when a fault occurs, that data is read explicitly via MSG instructions. Choose the appropriate input connection and add the output connection, if necessary.
Set the Connection Type From the Connection Type pull-down menu, choose the appropriate connection type.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
99
Page 100
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software
The Multicast connection type enables other safety controllers to read the safety input data by using this input connection. The Point to Point connection type does not enable this functionality. For other safety controllers to use this safety connection to read the input data, the connections must be identical. The RPI, connection name, and channel configuration must match so that this connection can be used by the other safety controller.
Set the Connection Configuration The safety connection between a controller and I/O module is based on many items, one of which can be the configuration signature of the safety I/O module. If the configuration signature must match, the configuration signature must remain the same once the safety connection is established or the connection is broken. To obtain SIL 3 integrity of a Guard I/O module, from the Configuration pulldown menu, choose ‘Configuration signature must match’. For more information about the configuration signature, refer to 85.
100
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 101
Configure Modules in RSNetWorx for DeviceNet Software
Chapter 6
Set the Communication Parameters Follow these steps to configure the communication parameters. 1. From the Add Safety Connection dialog box, click Advanced.
The Advanced Safety Connection Properties dialog box appears.
For more information about the Connection Reaction Time Limit, see the GuardLogix Controllers User Manual, publication 1756-UM020.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
101
Page 102
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software
2. In the Requested Packet Interval (RPI) box, enter the input connection RPI to support your application (from 6…500 ms). Selecting too small an RPI unnecessarily consumes network bandwidth; selecting too large an RPI increases safety reaction time. Selecting the appropriate RPI results in a system with optimized performance. As an example, a safety input module with only ESTOP switches connected to it generally may work well with settings of 50…100 ms. An input module with a light curtain guarding a hazard may need the fastest response that is possible. IMPORTANT
Analyze each safety channel to determine what is appropriate. The default Time-out Multiplier of 2 and Network Delay Multiplier of 200 will create an input-connection reaction time limit of four times the RPI and an output-connection reaction time limit of three times the RPI. Changes to these parameters should be approved by a safety administrator.
TIP
We recommend keeping the Time-out Multiplier and Network Delay Multiplier at their default values of 2 and 200.
A connection status tag exists that sums up all the safety I/O connections.
Safety I/O Error Status OFF No errors. ON Errors exist in one or more of the safety connections. Safety I/O Communication Status OFF Errors exist in one or more of the safety connections. ON No errors.
When the connection reaction time limit and requested packet interval are set appropriately, these status tags should remain in their ‘no errors’ condition. Monitor these connection status bits to verify that they are not changing intermittently due to timeouts.
102
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 103
Configure Modules in RSNetWorx for DeviceNet Software
Chapter 6
Configuration Ownership - Reset Ownership The connection between the owner and the Guard I/O module is based on the following: • Guard I/O DeviceNet node address • Guard I/O safety network number • GuardLogix slot number • GuardLogix safety network number • Path from GuardLogix controller to Guard I/O module • Configuration signature If any of these change, the connection between the controller and the Guard I/O module is lost. Reset the Guard I/O module to attempt to reestablish the connection by using this procedure. The most common use of resetting the device is when the 1791DS module has previously had a safety connection to another controller. Until that prior owner is reset, the module will not make a new safety connection. 1. When online with the 1791DS module, right-click the module and choose Reset Safety Device.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
103
Page 104
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software
The Reset Safety Device dialog box appears.
Configuration Owner and Output Connection Owner(s) are checked by default. 2. To reset the device to an out-of-box condition, check Password and Safety Network Number. If you attempt to reset the device when a safety connection is active and the SmartGuard controller is in Run mode, you see this message.
Put the SmartGuard controller into Idle mode and attempt to reset the 1791DS module again.
104
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 105
Configure Modules in RSNetWorx for DeviceNet Software
Chapter 6
Set the Safety Network Number (SNN) If you attempt to set the safety network number (SNN) when a safety connection is active and the SmartGuard controller is in Run mode, you see this message.
When you attempt to change the SNN, this dialog box appears.
Current SNN
Follow these steps to change the SNN. 1. To change the SNN based on time, click Time-based and then click Generate. 2. To change the SNN based on a value of your own, click Manual and enter your value in the box. 3. Once you have your new SNN established, click OK.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
105
Page 106
Chapter 6
Configure Modules in RSNetWorx for DeviceNet Software
The new SNN is sent to the 1791DS module. This dialog box appears informing you that the 1791DS configuration will be cleared when the SNN is changed.
Next, this dialog box appears to allow you to confirm which module is about to have its SNN set.
The network status indicator on the module that is about to have its SNN set is flashing red/green. 4. Click OK to confirm. This dialog box appears and the network status indicator should stop flashing red/green.
106
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 107
Configure Modules in RSNetWorx for DeviceNet Software
Chapter 6
Set Your Password You can set a password so that the configuration of the 1791DS module cannot be changed without first entering the password. Use of this password is not required to obtain SIL 3 integrity, because the configuration signature is part of the safety connection. If the configuration signature changes, the safety connection is lost.
If you forget your password, you must contact Rockwell Automation to have it reset.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013