Page 108

Chapter 6

Configure Modules in RSNetWorx for DeviceNet Software

I/O Data Tab You can put the 1791DS module in the scan list of a DeviceNet scanner, for example, a 1756-DNB bridge module. The 1791DS module will automatically appear in your list of available devices. Open the properties for the 1756-DNB module and click the Scanlist tab.

The 1791DS module has preconfigured options for reading (and writing) standard data. To view them, open the properties of the 1791DS module and click the I/O Data tab. These sizes and data contained within them cannot be altered.

108

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 109

Configure Modules in RSNetWorx for DeviceNet Software

Chapter 6

These message types will appear differently, depending on the safety I/O module you select, but in general the: • bit-strobe and polled connections provide the I/O data values and channel status. • polled connection can write standard data to the I/O module. Only use this if the test outputs are configured as standard outputs, and those standard outputs can then be controlled from the scanner. • change of state (COS) and cyclic connections provide power status, which cannot be obtained from bit strobe or polled connections.

Troubleshooting

If you attempt to go into Execute mode after a change is made to the 1791DS module (which breaks the safety connection to the SmartGuard controller), you will see the D6 message on the SmartGuard controller’s ASCII display. To resolve this anomaly, in the SmartGuard 600 properties dialog box, click the Safety Connection tab. This message appears if there has been an update to a 1791DS module that is not reflected in the offline configuration.

Click Yes to resolve those differences. Next, click Apply and then Yes to download the updated software changes to the SmartGuard 600 controller. If the differences are resolved, you can go into Execute mode without seeing the D6 message on the SmartGuard controller’s ASCII display.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

109

Page 110

Chapter 6

Configure Modules in RSNetWorx for DeviceNet Software

If you see the following message after attempting to download, the likely scenario is that the 1791DS module was previously owned by a different safety controller. You must reset the owner before the 1791DS module will make a new safety connection.

To reset the 1791DS module, right-click the module and choose Reset Safety Device.

The Reset Safety Device dialog box appears.

Check Password and Safety Network Number so that the 1791DS module is totally reset. Click Reset.

110

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 111

Configure Modules in RSNetWorx for DeviceNet Software

Chapter 6

If the reset is successful, you see this message.

Note that the configuration owner is now reset, so the 1791DS module can connect to a new owner, that is, the SmartGuard controller. When you browse the network, the 1791DS module appears like this.

The exclamation point means the SNN has not been set (as shown below). This makes sense because the device has just been reset.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

111

Page 112

Chapter 6

Configure Modules in RSNetWorx for DeviceNet Software

Double-click the module. This dialog box appears.

The SNN that exists in the 1791DS module does not match what is in RSNetWorx for DeviceNet software. For more information about the SNN, see 83. Click Download. This dialog box appears.

This lets you confirm which 1791DS module is about to have its SNN set. The network status indicator on the module that is about to have its SNN set is flashing red/green. Click OK to confirm the set. This dialog box appears and the network status indicator on the affected module stops flashing red/green.

112

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 113

Configure Modules in RSNetWorx for DeviceNet Software

Chapter 6

Click OK. This dialog box appears.

Click Download to complete the download of your new configuration.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

113

Page 114

Chapter 6

Configure Modules in RSNetWorx for DeviceNet Software

Notes:

114

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013