Guard I/O DeviceNet Safety Modules User Manual: 7 - Considerations When Replacing Guard I/O Modules

Pages 115 to 128 of 178, from Guard I/O DeviceNet Safety Modules User Manual

The original document is the PDF (5.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12

Page 115

Chapter

7

Considerations When Replacing Guard I/O Modules

Topic

Page

Considerations When Replacing Guard I/O Modules

115

Replacing an I/O Module When Using a SmartGuard Controller

117

Replacing an I/O Module When Using a GuardLogix Controller

121

This chapter provides things to consider when replacing Guard I/O modules when they are connected to GuardLogix or SmartGuard controllers. For more information, refer to the controller user manuals listed in the Additional Resources on page 10.

Considerations When Replacing Guard I/O Modules

When Guard I/O modules are connected to a GuardLogix or SmartGuard controller, consider the following when replacing the modules. The topic of replacing a safety I/O module that sits on a DeviceNet network is more complicated than standard devices because of the safety network number (SNN). The node number (Mac ID) and SNN make up the safety node’s identifier. Safety devices require this more complex identifier to guarantee that duplicate node numbers do not compromise communication between the correct nodes. The DeviceNet network supports 64 node numbers, so if you have 100 devices on multiple DeviceNet networks, there are at least 36 duplicate node numbers being used. Even though the duplicate nodes are on separate DeviceNet networks, this must still be considered in a safety system. In this example, the DNB scanner #1 is connected to node 5. The DNB scanner #2 is connected to another node 5. If the cables get inadvertently crossed, the scanners may be communicating with the incorrect node 5. Figure 25 - Crossed Cable Example DNB #1

DNB #2

DNB #1

DNB #2

5

5

5

5

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

115

Page 116

Chapter 7

Considerations When Replacing Guard I/O Modules

This crossed-cable scenario is unacceptable for a safety system. The SNN guarantees unique identification of every safety device. In this next example, all of the devices connected to DNB scanner #1 have an SNN of 100. All devices connected to DNB scanner #2 have an SNN of 101. If the cables get inadvertently crossed, the node connected to DNB scanner #1 changes from 100/5 to 101/5. The node connected to DNB scanner #2 changes from 101/5 to 100/5. Therefore, the safety connections are not made if the cables get crossed. Figure 26 - Connections Not Made Example DNB #1

DNB #2

DNB #1

DNB #2 Connections not made.

5 SNN 100

5 SNN 101

5 SNN 100

5 SNN 101

Why You Need to Manually Set the SNN The examples above showed how the SNN is used to guarantee safety-connection integrity after the system is operational. But the SNN is also used to guarantee integrity on the initial download to the Guard I/O module. If a safety signature exists, then the Guard I/O module must have a proper SNN/ node number identification that matches the module within the project, before it can receive its configuration. And to keep integrity, the setting of the module’s SNN is required to be a manual action. This manual action is to use the ‘set’ function on an out-of-box Guard I/O module.

116

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 117

Considerations When Replacing Guard I/O Modules

Chapter 7

Figure 27 - Setting the SNN with a GuardLogix Controller

Figure 28 - Setting the SNN with a SmartGuard Controller

GuardLogix Controllers versus SmartGuard Controllers There is one major difference in functionality between the GuardLogix and SmartGuard safety controllers that affects the replacement of safety I/O modules. GuardLogix controllers retain I/O module configuration on-board and are able to download the configuration to the replacement module. SmartGuard controllers do not retain I/O module configuration so you need to use RSNetWorx for DeviceNet software to download the configuration to the replacement module.

Replacing an I/O Module When Using a SmartGuard Controller

Follow these steps to replace an I/O module when using a SmartGuard controller. 1. Set the rotary switches of the replacement module to match the node number of the original module. 2. In RSNetWorx for DeviceNet software, open your project.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

117

Page 118

Chapter 7

Considerations When Replacing Guard I/O Modules

If the replacement module is out-of-box or has an SNN that does not match the original module, the module appears with an exclamation mark.

3. Right-click the module and choose Download to Device. This dialog box appears.

4. Click Yes. This dialog box appears informing you that the SNN of the replacement module does not match the SNN in the software.

5. Click Download to set the SNN on the replacement module.

118

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 119

Considerations When Replacing Guard I/O Modules

Chapter 7

This dialog box appears.

6. Click OK. This dialog box appears, confirming that the SNN has ben set.

The download now occurs. Once completed successfully, you see this message in the main project view: ‘The device at address xx has been downloaded. Any device-specific messages related to the download operation are displayed separately.’

Assuming this is the proper configuration from the original DNT file, the SNN and configuration signature now match that of the original. If you are already connected to the SmartGuard controller, a connection is made. The SmartGuard controller does not need to be taken out of RUN mode to download to the replacement module.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

119

Page 120

Chapter 7

Considerations When Replacing Guard I/O Modules

If you download this configuration to a temporary setup, place the module on the network and it automatically connects to the SmartGuard controller. If the configuration downloaded to the module was not from the original DNT file, the configuration signature will not match the original. Even if you recreate the same parameters in a new DNT file, the time and date portions of the signature will be different so the connection to the SmartGuard controller is not made. If this occurs, click the Safety Connection tab for the SmartGuard controller that prompts you that the signature is different and provides you with the option to match the new signature. However, you should first re-validate the safety system, because it is not using the original DNT file.

7. Click Yes. This takes the SmartGuard controller our of RUN mode. You see this dialog box.

8. Click Yes to download the new connection configuration to the SmartGuard controller. After the download is complete, place the SmartGuard controller back in RUN mode and the connection to the replacement module is established.

120

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 121

Considerations When Replacing Guard I/O Modules

Replacing an I/O Module When Using a GuardLogix Controller

Chapter 7

Follow the appropriate steps to replace an I/O module when using a GuardLogix controller.

I/O Replacement with ‘Configure Only When No Safety Signature Exists’ Enabled IMPORTANT

If you use a GuardLogix controller for SIL 3 during module replacement and functional testing, then you must choose ‘Configure Only When No Safety Signature Exists’. This option makes sure that if a safety signature exists (and you must have a safety signature to be SIL 3), that the safety network number (SNN) of the replacement distributed I/O module must match that of the GuardLogix controller before a connection between them can be made.

If a safety signature exists, clicking Set downloads the correct SNN from the correct GuardLogix project to the replacement module. The only exception would be when the SNN is already the same as the replacement module, in which case no action is required. Once the correct SNN has been downloaded to the Guard I/O module, the GuardLogix controller automatically configures the module.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

121

Page 122

Chapter 7

Considerations When Replacing Guard I/O Modules

If the project is configured as ‘Configure Only When No Safety Signature Exists’, follow the appropriate steps to replace a Guard I/O module based on your scenario. GuardLogix Project Safety Signature Exists

Replacement Module SNN

Fault

Action Required

Yes

Out-of-box

SNN not set, device out-of-box

Click Set. Refer to Scenario 1 - New Module is Out-of-box and Safety Signature Exists on page 122.

No

Out-of-box

None

None.

Yes or No

Same as original

None

None.

Yes

Different from original

SNN mismatch SNN not set, device out-of-box

1. Click Reset Ownership. 2. Click Set. Refer to Scenario 2 - New Module SNN is Different from Original and Safety Signature Exists on page 123.

No

Different from original

SNN mismatch

Click Reset Ownership. Refer to Scenario 3 - New Module SNN is Different from Original and No Safety Signature Exists on page 124.

Scenario 1 - New Module is Out-of-box and Safety Signature Exists 1. Remove the old I/O module and install the new module. 2. Right-click your GuardLogix controller and choose Properties. 3. Click to the right of the safety network number to open the Safety Network Number dialog box.

4. Click Set.

122

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 123

Considerations When Replacing Guard I/O Modules

Chapter 7

The Set Safety Network Number in Module confirmation dialog box appears. 5. Verify that the Network Status (NS) status indicator is alternating red/ green on the correct module before clicking Yes to set the SNN and accept the replacement module.

6. Follow your company-prescribed procedures to functionally test the replaced I/O module and system and to authorize the system for use.

Scenario 2 - New Module SNN is Different from Original and Safety Signature Exists 1. Remove the old I/O module and install the new module. 2. Right-click your Guard I/O module and choose Properties. 3. Click the Safety tab.

4. Click Reset Ownership. 5. Click OK. 6. Right-click your GuardLogix controller and choose Properties.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

123

Page 124

Chapter 7

Considerations When Replacing Guard I/O Modules

7. Click to the right of the safety network number to open the Safety Network Number dialog box.

8. Click Set.

The Set Safety Network Number in Module confirmation dialog box appears. 9. Verify that the Network Status (NS) status indicator is alternating red/ green on the correct module before clicking Yes to set the SNN and accept the replacement module.

10. Follow your company-prescribed procedures to functionally test the replaced I/O module and system and to authorize the system for use.

Scenario 3 - New Module SNN is Different from Original and No Safety Signature Exists 1. Remove the old I/O module and install the new module. 2. Right-click your Guard I/O module and choose Properties.

124

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 125

Considerations When Replacing Guard I/O Modules

Chapter 7

3. Click the Safety tab.

4. Click Reset Ownership. 5. Click OK. 6. Follow your company-prescribed procedures to functionally test the replaced I/O module and system and to authorize the system for use.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

125

Page 126

Chapter 7

Considerations When Replacing Guard I/O Modules

I/O Replacement with ‘Configure Always’ Enabled ATTENTION: Enable the ‘Configure Always’ feature only if the entire CIP Safety Control System is not being relied on to maintain SIL 3 behavior during the replacement and functional testing of a module. When the ‘Configure Always’ feature is enabled, the controller automatically checks for and connects to a replacement module that meets all of the following requirements: • The controller has configuration data for a compatible module at that network address. • The module is in out-of-box condition or has an SNN that matches the configuration. Although chances are small, this allows the possibility of the wrong controller taking ownership of the replacement module. For modules with different SNNs, clicking Reset Ownership places the module in an out-of-box condition. Once in out-of-box mode, no action is needed for the GuardLogix controller to take ownership of the module.

126

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

Page 127

Considerations When Replacing Guard I/O Modules

Chapter 7

If the project is configured for ‘Configure Always’, follow the appropriate steps to replace a Guard I/O module based on your scenario. GuardLogix Project Safety Signature Exists

Replacement Module SNN

Fault

Action Required

Yes or No

Out-of-box

None

None.

Yes or No

Same as original

None

None.

Yes or No

Different from original

SNN mismatch

Click Reset Ownership. Follow the steps below.

1. Remove the old I/O module and install the new module. 2. Right-click your Guard I/O module and choose Properties. 3. Click the Safety tab.

4. Click Reset Ownership. 5. Click OK. 6. Follow your company-prescribed procedures to functionally test the replaced I/O module and system and to authorize the system for use.

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013

127

Page 128

Chapter 7

Considerations When Replacing Guard I/O Modules

Notes:

128

Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013