The text of a manual · part 16 of 22
Guard I/O DeviceNet Safety Modules User Manual: 8 - Interpret Status Indicators
Pages 129 to 136 of 178, from Guard I/O DeviceNet Safety Modules User Manual
The original document is the PDF (5.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12
Page 129
Chapter
8
Interpret Status Indicators
Module Indicators
Topic
Page
Module Indicators
129
Module Status and Network Status Indicators Combination
130
1791DS-IB12, 1791DS-IB8XOB8, and 1791DS-IB4XOW4 Status Indicators
131
1732DS-IB8XOBV4, 1732DS-IB8, 1791DS-IB8XOBV4, and 1791DS-IB16 Status Indicators
133
See the figure and tables for information on how to interpret LED module indicators. Figure 29 - LED Module Indicators 24V DC Input Power Indicator 24V DC Output Power Indicator (1791DS-IB8XOBV4 modules only) Module Status Indicator
Network Activity Indicator
Configuration Lock Indicator Network Status Indicator
I0…I15 - Safety Input Status Indicator T0…T15 - Test Output Status indicator 00…07 - Safety Output Status Indicator (1791DS-IB8XOBV4 module)
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
129
Page 130
Chapter 8
Interpret Status Indicators
The Module Status (MS) indicator displays the status of a node on the network. The Network Status (NS) indicator displays the status of the entire network. See the table for meanings indicated by the combination of colors and status.
Module Status and Network Status Indicators Combination State M
NS MS NS MS NS
Solid green Solid green Flashing green Solid green Flashing green Off
Status Normal operation Online/connected Standby Online/connected Standby
Description
- normal status - safety I/O communication and standard I/O Safety I/O communication in progress. None communication are being performed. Standard I/O communication or message communication in progress.
Not online or not powered
MS NS MS NS MS NS MS NS MS NS MS NS
Flashing green Flashing green Flashing green/red Off Solid red Off Flashing red Off Flashing green Solid red Flashing green Solid red
Standby Online/not connected Initialization status Not online or not powered Fatal fault Not online or not powered Minor fault Not online or not powered Standby Fatal link fault Standby
Flashing Green Flashing red
Standby
: Lit
: Not lit
Fatal link fault
MS NS
130
: Flashing
Recommended Action
Minor communication fault
None - normal status - standard I/O communication and/or message communication are being performed.
this indicator status occurred for only specific module terminals, Waiting for completion of node address Ifcheck that the module communication rate settings are correct and duplication check at the master. restart the module. Waiting for safety or standard connection.
None - wait for connection to complete.
Module performing initialization process or waiting for configuration.
None - wait for process or configuration to complete.
Watchdog timer error.
Replace the module.
Switch settings are incorrect.
Check the switch settings and restart the module.
Node address duplication.
Reset the module so that it has a unique node address, and then restart the module.
Bus Off status (communication stopped Check the following items and restart the module: due to consecutive data errors). ·Do master and module communication rates match? ·Are lengths of cables (trunk and branch lines) correct? ·Are cables broken or loose? ·Are terminating resistors connected to both ends of the trunk line only? ·Is noise interference excessive? Communication timeout. Check the following items and restart the module: ·Do master and module communication rates match? ·Are lengths of cables (trunk and branch lines) correct? ·Are cables broken or loose? ·Are terminating resistors connected to both ends of the trunk line only? ·Is noise interference excessive? ·Is the network grounded properly ?
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 131
Interpret Status Indicators
Chapter 8
Refer to the tables for information on how to interpret status indicators on the 1791DS-IB12, 1791DS-IB8XOB8, and 1791DS-IB4XOW4 modules.
1791DS-IB12, 1791DS-IB8XOB8, and 1791DS-IB4XOW4 Status Indicators Table 3 - Module Status (MS) Indicator State
Status
Description
Recommended Action
Solid green
Normal
Normal operating status.
None- normal operation.
Flashing green
Standby
Waiting for safety communication from the safety controller.
Wait for module to establish communication.
Solid red
Fatal fault
Hardware fault.
Check for electrical noise and eliminate the source. If the anomaly persists, replace the module.
Flashing red
Minor fault
Switch settings incorrect.
Correct the switch settings.
Flashing green/ red
Initialization status
The module is performing initialization process or waiting for configuration.
Wait for the configuration to complete.
Off
No power
Power is not being supplied to the module.
Supply power to the module.
Waiting for initial processing to start.
Wait for processing to start.
The module is being reset.
Wait for the module to reset.
Table 4 - Network Status (NS) Indicator State
Status
Description
Recommended Action
Solid green
Online/connected
Network is operating normally (communication established).
None - normal operation.
Flashing green
Online/not connected
Network is operating normally, however, communication is not established.
Verify your network and module configuration.
Solid red
Fatal link failure
Communication fault.
Correct the communication fault.
Module detected that network communication is not possible. Node address duplication detected. Abusive fault detected. Flashing red
Minor communication fault
Communication timeout.
Correct the communication fault.
Off
Not online or not powered
Waiting for node address duplication check at the master.
Wait for check to complete.
The power supply is off.
Apply power.
Table 5 - Configuration Lock (LOCK) Indicator State
Status
Description
Recommended Action
Solid yellow
Normal and locked
Normal configuration, and configuration is locked by RSNetWorx for DeviceNet software.
None.
Flashing yellow
Normal and not locked
Normal configuration, but configuration is not locked in the module.
None.
Off
Configuration not performed
Configuration has not been performed.
Perform the configuration.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
131
Page 132
Chapter 8
Interpret Status Indicators
Table 6 - Input Power (IN PWR) Indicator State
Status
Description
Recommended Action
Solid green
Normal
Normal status of input power.
None.
Off
No input power
Input power is not supplied.
Apply input power.
Table 7 - Output Power (OUT PWR) Indicator State
Status
Description
Recommended Action
Solid green
Normal
Normal status of output power.
None.
Off
No output power
Output power is not supplied.
Supply output power.
Output power exceeds power range
Output power exceeds the upper/lower limit of power range.
Correct output power.
IMPORTANT
The I/O indicators are not lit while the module is being configured.
Table 8 - Input (IN0 through INn(1)) Indicators State
Status
Description
Recommended Action
Solid yellow
On
Safety input is on.
None.
Off
Off
Safety input is off.
None.
Solid red
Fault
A fault occurred in an input circuit.
Check connected device and wiring.
Flashing red
Fault in other channel
When dual channels are set: a fault occurred in the other channel.
Correct fault in other channel.
(1) Where ‘n’ indicates the input number.
IMPORTANT
The I/O indicators are not lit while the module is being configured.
Table 9 - Output (OUT0 through OUTn(1)) Indicators State
Status
Description
Recommended Action
Solid yellow
On
Safety output is on.
None.
Off
Off
Safety output is off.
None.
Solid red
Fault
A fault occurred in an output circuit.
Check connected device and wiring.
Flashing red
Fault in other channel
When dual channels are set, a fault occurred in the other channel.
Correct fault in other channel.
(1) Where ‘n’ indicates the output number.
132
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 133
Interpret Status Indicators
1732DS-IB8XOBV4, 1732DS-IB8, 1791DS-IB8XOBV4, and 1791DS-IB16 Status Indicators
Chapter 8
Refer to the tables for information on how to interpret status indicators on the 1732DS-IB8XOBV4, 1732DS-IB8, 1791DS-IB8XOB8, and 1791DS-IB16 modules.
Table 10 - Module Status (MS) Indicator State
Status
Description
Recommended Action
Off
No power or autobauding
No power is applied to the DeviceNet connector.
Apply power to this connector.
Solid green
Normal operation
The module is operating normally.
None.
Solid red
Unrecoverable fault
The module has detected an unrecoverable fault.
Cycle power to the module. If the anomaly persists, replace the module.
Flashing green
Module needs commissioning Module is unconfigured. due to missing, incomplete, or incorrect configuration
Reconfigure the module. For additional information, inspect the Network Status (NS) indicator.
Flashing red
Recoverable fault
The module detected a recoverable fault.
Cycle power to the module or reset the module.
User-initiated firmware update
User-initiated firmware update is in progress.
Wait for the firmware update to complete.
Device in self test
The module is performing its power-cycle diagnostic tests.
Wait for the module to complete its power-cycle diagnostics.
Flashing red and green
Table 11 - Network Status (NS) Indicator State
Status
Description
Recommended Action
Off
Module not online or no power
The module is not online with the network.
Verify your network.
Flashing green
Module online with no connections in established state
The module identified the communication rate of the network but no connections are established.
Verify your network and module configuration.
Solid green
Module online with connections in established state
The module is operating normally.
None.
Flashing red
One or more I/O connections in timed-out state
The module detected a recoverable network fault.
Verify your network and module configuration.
User-initiated firmware update
User-initiated firmware update is in progress.
Wait for the firmware update to complete.
Solid red
Critical link failure
The module detected an error that prevents it from communicating on the network.
Cycle power to the module. If the anomaly persists, replace the module.
Flashing red and green
Communication faulted module
The module detected a network access error and is in communication faulted state. The module has received and accepted an Identity Communication Faulted Request-long protocol message.
Verify your network and module configuration.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
133
Page 134
Chapter 8
Interpret Status Indicators
Table 12 - Configuration Lock (LOCK) Indicator State
Status
Description
Recommended Action
Off
No configuration
Invalid configuration data.
Provide valid configuration data.
The configuration is owned by a CIP safety originator, such as GuardLogix software
The configuration is owned by a CIP safety originator, such as GuardLogix software.
None.
Solid yellow
Locked
Valid configuration, locked by a network configuration tool such as RSNetWorx for DeviceNet software.
None.
Flashing yellow
Not locked
Valid configuration, owned by a software configuration tool such as RSNetWorx for DeviceNet software.
None.
Table 13 - 24V DC Input Power Indicator State
Status
Description
Recommended Action
Off
No power
No power is applied.
Apply power to this section.
Solid green
Normal operation
The applied voltage is within specifications.
None.
Solid yellow
Input power out of specification
The input power is out of specification.
Check your connectors, wiring, and voltages, For additional information, see the applicable installation instructions.
Table 14 - 24V DC Output Power Indicator State
Status
Description
Recommended Action
Off
No power
No power is applied.
Apply power to this section.
Solid green
Normal operation
The applied voltage is within specifications.
None.
Solid yellow
Output power out of specification
The output power is out of specification.
Check your connectors, wiring, and voltages. For additional information, see the applicable installation instructions.
Table 15 - Safety Input Indicator State
Status
Description
Recommended Action
Off
Safety input off or module being configured
The safety input is off or the module is being configured.
Turn the safety input on or wait for the module to be configured.
Solid yellow
Safety input on
The safety input is on.
None.
Solid red
Fault detected
A fault in the external wiring or input circuit detected.
Check configuration, field wiring, and devices. If no anomaly is found, replace the module.
Flashing red
Partner fault detected
A fault in the partner input circuit of a dual input configuration detected.
Check the field wiring and verify your configuration for the partner circuit. If no anomaly is found, replace the module.
134
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 135
Interpret Status Indicators
Chapter 8
Table 16 - Safety Output Indicator State
Status
Description
Recommended Action
Off
Safety output off or module being configured
The safety output is off or the module is being configured.
Turn the safety output on or wait for the module to be configured.
Solid yellow
Safety output on
The safety output is on.
None.
Solid red
Fault detected
A fault in the output circuit was detected.
Check the circuit wiring and end device. If no anomaly is found, replace the module.
Both tags in a dual channel circuit do not have the same value.
Make sure logic is driving tag values to the same state (off or on).
A fault in the partner output circuit of a dual output configuration was detected.
Check the circuit wiring and end device of the partner. If no anomaly is found, replace the module.
Flashing red
Partner fault detected
Table 17 - Test Output Indicator (1791DS-IB8XOBV4, 1791DS-IB16 only) State
Status
Description
Recommended Action
Off
Test output off or module being configured
The test output is off or the module is being configured.
Turn the test output on or wait for the module to be configured.
Solid yellow
Output on
Output is on.
None.
Solid red
Fault detected
A fault in the external wiring or input circuit detected.
Check the field wiring. If no anomaly is found, replace the module. Outputs configured for muting could indicate undercurrent or burned-out lamp.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
135
Page 136
Chapter 8
Interpret Status Indicators
Notes:
136
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013