Get Point Status from Modules by Using Explicit Messaging
Considerations for Obtaining Point Status
Topic
Page
Considerations for Obtaining Point Status
137
1791DS-IB8XOB8 Module Definition Configuration
138
1791DS-IB4XOW4 Module Definition Configuration
142
I/O Assembly and Reference Data
148
Explicit Messages
155
Basic Format of Explicit Messages
157
Explicit Messages
158
This appendix provides information about how to use explicit messaging to get diagnostic status information from the modules. To maximize throughput when using DeviceNet safety I/O modules, consider the requested packet interval, baud rate, and the size of the I/O assembly. Keeping the I/O assembly at 2-bytes or fewer does not provide individual point status necessary to quickly diagnose what point faulted from an operator terminal.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
137
Page 138
Appendix A
Get Point Status from Modules by Using Explicit Messaging
To obtain individual point status of the Guard I/O module from the Module Definition dialog box, from the Input Status pull-down menu, choose Pt. Status.
TIP
1791DS-IB8XOB8 Module Definition Configuration
138
You can also obtain overall status implicitly from this dialog box by choosing Combined Status from the Input Status pull-down menu. If the Combined Status changes, use explicit messaging to obtain the point-level status.
Follow this procedure to configure the 1791DS-IB8XOB8 module definition. 1. In the Module Definition dialog box, from the Input Status pull-down menu, choose Combined Status.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 139
Get Point Status from Modules by Using Explicit Messaging
Appendix A
This creates a 2-byte input assembly, as shown for the 1791DS-IB8XOB8 module.
2. Use the InputStatus and OutputStatus bits to detect if one or more of the I/O points on the module have a fault. • If any input or output status bit goes to a value of 0 (0=bad, 1=good), use an explicit message to determine which individual data points have faulted. Use the InputState and OutputStatus bits to condition your msg rung as follows. • Note that the second rung can be used to read the status on mode transition and once a fault is detected, continue reading until the fault is corrected. • Place these rungs in the standard task.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
139
Page 140
Appendix A
Get Point Status from Modules by Using Explicit Messaging
This figure shows the MSG instruction parameters for reading Instance 803 from the 1791DS-IB8XOB8 module.
In this example, we created a UDT from the destination type. • You can find the UDT called Assembly803_1791DS_IB8XOB8 in an ACD file. This UDT is based on the Assembly803 for 1791DS_IB8XOB8 module. • There are other assemblies in the EDS file that can be used, but this one is the most inclusive. • Make sure the Communication Path is set to the correct module.
140
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 141
Get Point Status from Modules by Using Explicit Messaging
Appendix A
This figure shows the 1791DS-IBXOB8 Assembly803 UDT.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
141
Page 142
Appendix A
Get Point Status from Modules by Using Explicit Messaging
1791DS-IB4XOW4 Module Definition Configuration
Follow this procedure to configure the 1791DS-IB4XOW4 module definition. 1. In the Module Definition dialog box, from the Input Status pull-down menu, choose Combined Status-Muting.
This creates a 1-byte input assembly, as shown for the 1791DS-IB4XOW4 module.
142
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 143
Get Point Status from Modules by Using Explicit Messaging
Appendix A
2. Use the InputStatus and OutputStatus bits to detect if one or more of the I/O points on the module have a fault. • If any input or output status bit goes to a value of 0 (0=bad, 1=good), use an explicit message to determine which individual data points have faulted. Use the InputState and OutputStatus bits to condition your msg rung as follows. • Note that the second rung can be used to read the status on mode transition and once a fault is detected, continue reading until the fault is corrected. • Place these rungs in the standard task.
This figure shows the MSG instruction parameters for reading Instance 819 from the 1791DS-IB4XOW4 module.
In this example, we created a UDT from the destination type. • You can find the UDT called Assembly819_1791DS_IB4XOW4 in an ACD file. This UDT is based on the Assembly819 for 1791DS_IB4XOW4 module. • There are other assemblies in the EDS file that can be used, but this one is the most inclusive. • Make sure the Communication Path is set to the correct module.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
143
Page 144
Appendix A
Get Point Status from Modules by Using Explicit Messaging
This figure shows the 1791DS-IB4XOW4 Assembly819 UDT.
144