The text of a manual ยท part 20 of 22
Guard I/O DeviceNet Safety Modules User Manual: B - Safety Data
Pages 161 to 164 of 178, from Guard I/O DeviceNet Safety Modules User Manual
The original document is the PDF (5.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12
Page 161
Appendix
B
Safety Data
This appendix lists calculated values for probability of failure on demand (PFD), probability of failure per hour (PFH), and mean time between failures. PFD and PFH calculations comply with IEC61508, edition 2, 2010. Calculated values of probability of failure on demand and probability of failure per hour appear in Table 36 and Table 37 and must be calculated for the devices within the system to comply with the SIL level required for application. You must be responsible for following the requirements of ISO 13849-1:2008, to assess performance levels in your safety system. Within the proof test interval, every I/O module must be functionally tested by individually toggling each input point and verifying that each point is detected by the controller. Additionally, each output point must be individually toggled by the controller and you must verify that the output point changes state. For more information, refer to these publications. Resource
Description
GuardLogix 5570 Controller Systems Safety Reference Manual, publication 1756-RM099
Provides information on safety application requirements for GuardLogix 5570 controllers in Studio 5000 Logix Designer projects.
GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093
Provides information on safety application requirements for GuardLogix 5560 and 5570 controllers in RSLogix 5000 projects.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
161
Page 162
Appendix B
Safety Data
Figure 30 - PFD versus Proof Test Interval 1791DS-IB8XOBV4, 1732DS-IB8XOBV4
PFD
Proof Test Interval [years]
Figure 31 - PFD versus Proof Test Interval 1791DS-IB12, 1791DS-IB8XOB8, 1791DS-IB4XOW4
PFD
Proof Test Interval [years]
162
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 163
Safety Data
Appendix B
Table 36 - Probability of Failure Data (IEC 61508, Edition 2, 2010) Cat. No.
1791DS-IB8XOBV4
1791DS-IB16 1732DS-IB8XOBV4
1732DS-IB8
Description
CIP Safety 8-point input/4 bi-polar output module CIP Safety 16-point input module CIP Safety 8-point input/4 bi-polar output module CIP Safety 8-point input module
Calculated PFD 2 Years 5 Years (17,520 (43,800 hours) hours) 4.16E-06 1.04E-05
10 Years (87,600 hours) 2.08E-05
20 Years (175,200 hours) 4.16E-05
PFH (1/hour)
Spurious Trip Rate (SPR)
MTTF (years)
5.02E-10
5.608E-06
20.34
4.11E-06
1.03E-05
2.06E-05
4.11E-05
4.96E-10
3.301E-06
34.56
4.16E-06
1.04E-05
2.08E-05
4.16E-05
5.02E-10
5.608E-06
20.34
4.11E-06
1.03E-05
2.06E-05
4.11E-05
4.96E-10
3.301E-06
34.56
2 Years (17,520 hours) 1.754E-06
5 Years (43,800 hours) 4.419E-06
PFH 10 Years 20 Years(1) (87,600 hours) (175,200 hours) (1/hour)(1) 8.962E-06
6.013E-06
6.84E-11
1.755E-06
4.421E-06
8.963E-06
6.013E-06
6.84E-11
4.151E-05
1.207E-04
2.978E-04
7.684E-04
4.072E-09
Table 37 - Probability of Failure Data (IEC 61508, Edition 1, 1999) Cat. No.
1791DS-IB12 1791DS-IB8XOB8
1791DS-IB4XOW4
(1)
Description
Calculated PFD
CIP Safety 12-point input module CIP Safety 8-point input/8-point output module CIP Safety 4-point input/4-point relay output module
The 20-year PFD data for this product applies only to product with a manufacture date code of 2009/ 01/01 (January 1, 2009) or later. See the product label for the date code.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
163
Page 164
Appendix B
Safety Data
Notes:
164
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013