For the Allen-Bradley 1791DS-IB8XOB8 and Allen-Bradley 1791DS-IB12
Page 165
Appendix
C
Configuration Reference Information
Topic
Page
Understanding Parameter Groups
165
Allocate Remote I/O
167
I/O Data Supported by Each Module
167
The modules have these parameter groups: • General Parameters • Safety Input Parameters • Test Output Parameters • Safety Output Parameters
Understanding Parameter Groups
Set all parameters by using the Logix Designer application or RSNetWorx for DeviceNet software. Table 38 - General Parameters Parameter Name
Value
Description
Default
Safety Output Error Latch Time
0…65,530 ms (in increments of 10 ms)
Safety output errors are latched for this time.
1000 ms
Safety Input Error Latch Time
0…65,530 ms (in increments of 10 ms)
Safety input or test output errors are latched for this time.
1000 ms
Test Output Idle State
Clear OFF or Keep Output Data
Definition of output data is in idle state.
Clear OFF
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
165
Page 166
Appendix C
Configuration Reference Information
Table 39 - Safety Input Parameters Parameter Name
Value
Description
Input Point Operation Type
Single Channel
Use as single channel.
Dual-channel Equivalent
Use as dual-channel. Normal when both channels are ON or OFF.
Dual-channel Complementary
Use as dual-channel. Normal when one channel is ON and the other channel is OFF.
Not Used
External input device is not connected.
Safety Test Pulse
Use with a contact output device and in combination with a test output. By using this setting, short-circuits between input signal lines and the power supply (positive side) and short-circuits between input signal lines can be detected.
Safety
A solid-state output safety sensor is connected.
Standard
A standard device, such as a reset switch, is connected.
Not Used
The test output that is used with the input.
Input Point Mode
Safety Input Test Source
Test Output 0 Test Output 1 Test Output 2 Test Output 3 Input Delay Time Off -> On
0…126 ms (in increments of 6 ms)
Filter time for OFF to ON transition.
Input Delay Time On -> Off
0…126 ms (in increments of 6 ms)
Filter time for ON to OFF transition.
IMPORTANT
166
If the test pulse from test output is set to the Safety Input Channel mode, the safety-input test source and pulse test output of the test output must be set to the Test Output mode.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
Page 167
Configuration Reference Information
Appendix C
Table 40 - Test Output Parameters Parameter Name
Value
Description
Default
Test Output Mode
Not Used
An external device is not connected.
Not Used
Standard
The output is connected to a standard device.
Pulse Test
A contact output device is connected. Use in combination with a safety input.
Power Supply
The power supply of a Safety Sensor is connected. The voltage supplied to I/ O power (V, G) is output from the test output terminal.
Muting Lamp Output (Terminal T3 or T7 only)
An indicator is connected and turned ON to detect broken lines in an external indicator.
Clear OFF
Action to perform when a communication error is detected.
Test Output Fault Action(1)
Clear OFF
Hold Last Data (1) Not directly related to safety.
Table 41 - Safety Output Parameters Parameter Name
Value
Description
Default
Output Point Mode
Not Used
An external output devices is not connected.
Not Used
Safety
When the output is ON, the test pulse is not output (remains ON).
Safety Pulse Test
By using this function, short-circuits between output signal lines and the power supply (positive side) and short-circuits between output signal lines can be detected.
Single Channel
Use as single channel.
Dual-channel
Use as dual-channel. When both channels are normal, outputs can be turned ON.
Output Point Operation Type
Allocate Remote I/O
Dual-channel
The module internally stores I/O allocation data. Use the Logix Designer application or RSNetWorx for DeviceNet software to set the connection paths for the allocation of I/O data in the master unit. No settings are made by default. Be sure to set the required connection paths. The module stores this I/O data: • SAFETY: Information the controller can use in safety-related functions • STANDARD: Additional information that must not be relied on for safety functions
I/O Data Supported by Each Module
These tables show the I/O data supported by each module. Refer to I/O Assembly Data for data arrangements. You can allocate up to four items of I/O-data safety connections, including one output, and up to two items of I/O-data standard connections for the master unit (such as a scanner).
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
167
Page 168
Appendix C
Configuration Reference Information
Table 42 - 1791DS-IB12 Modules Outputs Standard Output Data
• • • •
• •
•
•
21 340
(1) Found in the Logix Designer application, I/O Module Properties, General tab.
168
Safety Output Data
Test Test Output Status with General Status Assembly
Individual Test Output Status
• •
Safety Output Readback
•
Muting Lamp Status
Safety - Point Status - Muting Status - Test Output Status 312
Individual Safety Output Status
•
Combined Safety Output Status
• • • • •
Individual Safety Input Status
20C 224 22C 310 311
Combined Safety Input Status
Safety Small Safety - Point Status Safety - Point Status Safety - Combined Status - Muting Status Safety - Point Status - Muting Status
Inputs Safety Input Data
• • • •
Assembly Instance No.
•
Standard Connection
Safety Connection • • • •
Configuration Software Setting (see module definition(1))
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
• • •
Page 169
Configuration Reference Information
Appendix C
Table 43 - 1791DS-IB8XOB8 Modules Inputs
Outputs
• •
• •
Safety Safety - Combined Status - Muting Status
204 320
• •
•
•
Safety - Point Status - Muting Status
321
•
•
•
•
•
•
Safety - Readback - Point Status - Muting Status
322
•
•
•
•
•
•
•
Safety - Readback - Point Status - Muting Status - Test Output Status
323
•
•
•
•
•
•
Test
21
•
Safety
234
•
•
Combined
351
•
Output Readback/Test Output Status with General Status Assembly
341
•
•
•
Standard Output Data
Safety Output Data
Individual Test Output Status
Safety Output Readback
Muting Lamp Status
Individual Safety Output Status
Combined Safety Output Status
Individual Safety Input Status
Combined Safety Input Status
Safety Input Data
Assembly Instance No.
Standard Connection
Safety Connection
Configuration Software Setting (see Module Definition(1))
•
•
•
•
•
•
(1) Found in the Logix Designer application, I/O Module Properties, General tab.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
169
Page 170
Appendix C
Configuration Reference Information
Table 44 - 1791DS-IB4XOW4 Modules Inputs
Outputs
• •
• •
Safety Safety - Combined Status - Muting Status
203 330
• •
•
•
Safety - Point Status - Muting Status
331
•
•
•
•
•
•
Safety - Readback - Point Status - Muting Status
332
•
•
•
•
•
•
•
Safety - Readback - Point Status - Muting Status - Test Output Status
333
•
•
•
•
•
•
Test
21
•
Safety
233
•
•
Combined
350
•
Output Readback/Test Output Status with General Status Assembly
342
•
•
•
•
(1) Found in the Logix Designer application, I/O Module Properties, General tab.
170
Standard Output Data
Safety Output Data
Individual Test Output Status
Safety Output Readback
Muting Lamp Status
Individual Safety Output Status
Combined Safety Output Status
Individual Safety Input Status
Combined Safety Input Status
Safety Input Data
Assembly Instance No.
Standard Connection
Safety Connection
Configuration Software Setting (see Module Definition(1))
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
•
•
•
•
•
Page 171
Configuration Reference Information
Appendix C
Table 45 - 1791DS-IB8XOBV4 Modules Inputs
Outputs
• •
• •
Safety Safety - Combined Status - Muting
204 324
• •
•
•
Safety - Point Status - Muting
344
•
•
•
•
•
•
Safety - Readback - Point Status - Muting
354
•
•
•
•
•
•
•
Safety - Readback - Point Status - Muting - Test 374 Output
•
•
•
•
•
•
Test
22
•
Safety
234
•
•
Combined
2C4
•
•
•
Standard Output Data
Safety Output Data
Individual Test Output Status
Safety Output Readback
Muting Lamp Status
Individual Safety Output Status
Combined Safety Output Status
Individual Safety Input Status
Combined Safety Input Status
Safety Input Data
Assembly Instance No.
Standard Connection
Safety Connection
Configuration Software Setting (see Module Definition(1))
•
•
•
•
(1) Found in the Logix Designer application, I/O Module Properties, General tab.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
171
Page 172
Appendix C
Configuration Reference Information
Table 46 - 1732DS-IB8 Modules Inputs
Outputs
•
•
Safety - Point Status - Muting - Test Output
364
•
•
•
•
Safety - Combined Status - Muting
314
•
•
•
Safety - Point Status
224
•
•
Test
22
•
•
•
•
•
•
•
•
(1) Found in the Logix Designer application, I/O Module Properties, General tab.
172
Standard Output Data
•
Safety Output Data
• •
Individual Test Output Status
204 334
Safety Output Readback
Safety Safety - Point Status - Muting Status
Muting Lamp Status
• •
Individual Safety Output Status
• •
Combined Safety Output Status
Individual Safety Input Status
Combined Safety Input Status
Safety Input Data
Assembly Instance No.
Standard Connection
Safety Connection
Configuration Software Setting (see Module Definition(1))
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
•
Page 173
Configuration Reference Information
Appendix C
Table 47 - 1732DS-IB8XOBV4 Modules Inputs
Outputs Standard Output Data
Safety Output Data
Individual Test Output Status
Safety Output Readback
•
Muting Lamp Status
•
Individual Safety Output Status
• •
Combined Safety Output Status
204 324
Individual Safety Input Status
Safety Safety - Combined Status - Muting
Combined Safety Input Status
Safety Input Data
•
Assembly Instance No.
Standard Connection
Safety Connection •
Configuration Software Setting (see Module Definition(1))
•
•
•
Safety - Point Status - Muting
344
•
•
•
•
•
•
Safety - Readback - Point Status - Muting
354
•
•
•
•
•
•
•
Safety - Readback - Point Status - Muting - Test 374 Output
•
•
•
•
•
•
Test
22
•
Safety
234
•
•
Combined
2C4
•
•
•
•
(1) Found in the Logix Designer application, I/O Module Properties, General tab.
Rockwell Automation Publication 1791DS-UM001J-EN-P - May 2013
173
Page 174
Appendix C
Configuration Reference Information
Table 48 - 1791DS-IB16 Modules Inputs
Outputs
205 335
• •
•
•
•
•
Safety - Point Status - Muting - Test Output
365
•
•
•
•
•
Safety - Combined Status - Muting
315
•
•
•
Safety - Point Status
225
•
•
•
Test
23
None
C7
•
•
•
•
(1) Found in the Logix Designer application, I/O Module Properties, General tab.
174
Standard Output Data
Safety Safety - Point Status - Muting
Safety Output Data
• •
Individual Test Output Status
• •
Safety Output Readback
Muting Lamp Status
Individual Safety Output Status
Combined Safety Output Status
Individual Safety Input Status
Combined Safety Input Status
Safety Input Data
Assembly Instance No.
Standard Connection
Safety Connection
Configuration Software Setting (see Module Definition(1))