The text of a manual · part 1 of 14
Guard I/O EtherNet/IP Safety Modules User Manual, pages 1 to 10
Pages 1 to 10 of 140: Guard I/O EtherNet/IP Safety Modules User Manual; Back Cover
The original document is the PDF (7.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1791ES
Page 1
User Manual
Guard I/O EtherNet/IP Safety Modules Catalog Numbers 1791ES-IB8XOBV4, 1791ES-IB16, 1732ES-IB12XOB4, 1732ES-IB12XOBV2
Page 2
Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE). Allen-Bradley, ArmorBlock, CompactBlock, Guard I/O, Logix5000, Rockwell Automation, Rockwell Software, RSLogix, Studio 5000, Studio 5000 Automation Engineering & Design Environment, Studio 5000 Logix Designer, and RSNetWorx are trademarks of Rockwell Automation, Inc. ControlNet, DeviceNet, and EtherNet/IP are trademarks of the ODVA. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Page 3
Summary of Changes This manual contains new and updated information. Changes throughout this revision are marked by change bars, as shown to the right of this paragraph.
New and Updated Information
This table contains the changes made in this revision. Topic
Page
Updated the terminology table.
10
Added a statement for the suitability of use.
12
Updated the precautions for use.
12
Updated the SIL level description for the modules.
13, 16
Added a description of network address translation (NAT).
14
Added catalog numbers for the new modules.
15
Added information for programming requirements for the new modules.
15
Added a section for power supply requirements.
15
Added a catalog number 1732ES module to the linear and star topology example.
16
Added an example of Device-level Ring (DLR) topology.
16
Added an attention statement for safe state of the module.
19
Added typical pulse width and period data for the new catalog number 1732ES modules.
21
Added an attention statement to not use test outputs as safety outputs.
21
Added a section for muting lamp operation.
28
Added an attention statement for connected loads to safety outputs.
30
Added a section for single-channel operation.
32
Updated the installation instructions in Chapter 3.
35
Added wiring examples for the 1732ES modules in Chapter 4.
57
Updates for NAT and configuration steps in Chapter 5.
69
Added rows in the values and states of the tags table.
77
Added 1732ES modules status indicators to Chapter 6.
87
Added I/O assembly, reference data, explicit messaging, and getting status messages information for 1732ES modules to Appendix A.
91
Added safety data for the 1732ES modules to Appendix B.
117
Added Appendix D, Specifications.
123
Added Appendix E, History of Changes.
133
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
3
Page 4
Summary of Changes
Notes:
4
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 5
Table of Contents Preface
Studio 5000 Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 About the Specifications and Dimensions in This Manual . . . . . . . . . . . 10 Terminology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Chapter 1 About the Modules
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Firmware Information and Downloads . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Functional Safety Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Understand Suitability for Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Follow Precautions for Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 I/O Module Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 About Catalog Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Selecting a Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Programming Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 About CIP Safety in EtherNet/IP Safety Architectures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Identify Major Parts of the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Chapter 2 Understand the Operation of Safety Functions
Safe State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Self-diagnostic Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Configuration Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 I/O Status Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Safety Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Using a Test Output with a Safety Input . . . . . . . . . . . . . . . . . . . . . . . 21 Set Dual-channel Mode and Discrepancy Time . . . . . . . . . . . . . . . . . 24 Dual-channels, Equivalent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Dual-channels, Complementary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Safety Input Fault Recovery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Input Delays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Muting Lamp Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Safety Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Safety Output with Test Pulse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Dual-channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Single-channel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Safety Output Fault Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Controlling Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Chapter 3 Install the Module
Environment and Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 For 1791ES Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 For 1732ES Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 Prevent Electrostatic Discharge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
5
Page 6
Table of Contents
Environmental Considerations for Use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Follow Wiring Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Follow DC Power Supply Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Mount the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Module Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Mount the 1791ES Modules on a DIN Rail . . . . . . . . . . . . . . . . . . . . . 42 Mount the 1732ES Modules on a Wall or Panel . . . . . . . . . . . . . . . . . 43 Grounding the 1732ES Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Set Network IP Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Make Connections for 1791ES Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46 EtherNet/IP Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Make Connections for 1732ES Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Power Pass Through . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 EtherNet/IP Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Label the IP Address and Device Connections . . . . . . . . . . . . . . . . . . 55
Chapter 4 Wiring Examples
Wiring Examples for Safety Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57 Wiring by Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Chapter 5 Configure the I/O Modules by Using the Logix Designer Application
Add Modules to the I/O Configuration Tree . . . . . . . . . . . . . . . . . . . . . . . 69 Configure the Module Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71 Set the IP Address in the Logix Designer Application . . . . . . . . . . . . 71 Change the Module Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Configure the Safety Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 Configuration Ownership – Reset Ownership . . . . . . . . . . . . . . . . . . 79 Configuration Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Configure the Module Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Configure the Test Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 Configure the Module Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83 Save and Download the Module Configuration . . . . . . . . . . . . . . . . . . . . . 84
Chapter 6 Interpret the Module Status Indicators
1791ES Module Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 1732ES Module Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Appendix A Get Diagnostic Status from Modules by Using Explicit Messaging
6
Get Status Messages from 1791ES-IB8XOBV4 Modules . . . . . . . . . . . . 92 Get Status Messages from 1791ES-IB16 Modules . . . . . . . . . . . . . . . . . . . 97 Get Status Messages from 1732ES Modules. . . . . . . . . . . . . . . . . . . . . . . . 102 Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 7
Table of Contents
I/O Data Supported by Each Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 I/O Assembly and Reference Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 1791ES Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109 1732ES Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112 Explicit Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Appendix B Safety Data
Calculated Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Appendix C Configuration Reference Information Parameter Groups. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 Appendix D Specifications
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 1791ES Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123 1732ES Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127 Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 Legislation and Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130 Europe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 North America. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Japan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 EC Directives. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 EMC Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131 Compliance with EC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Appendix E History of Changes
1791ES-UM001D-EN-P, May 2013. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133 1791ES-UM001C-EN-P, April 2009 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
7
Page 8
Table of Contents
Notes:
8
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 9
Preface Read and understand this manual before using the described products. Consult your Rockwell Automation representative if you have any questions or comments. This manual describes how to use Guard I/O™ modules.
Studio 5000 Environment
The Studio 5000 Automation Engineering & Design Environment™ combines engineering and design elements into a common environment. The first element is the Studio 5000 Logix Designer® application. The Logix Designer application is the rebranding of RSLogix™ 5000 software and will continue to be the product to program Logix5000™ controllers for discrete, process, batch, motion, safety, and drive-based solutions.
The Studio 5000® environment is the foundation for the future of Rockwell Automation® engineering design tools and capabilities. The Studio 5000 environment is the one place for design engineers to develop all of the elements of their control system.
Additional Resources
These documents contain additional information concerning related products from Rockwell Automation.
Resource
Description
CompactBlock™ Guard I/O EtherNet/IP Safety Modules Installation Instructions, publication 1791ES-IN001
Provides detailed specifications and information related to installation of 1791ES Guard I/O modules.
GuardLogix® 5570 Controllers User Manual, publication 1756-UM022
Provides information on how to install, configure, program, and use GuardLogix 5570 controllers in Studio 5000 Logix Designer projects.
GuardLogix 5570 Controller Systems Safety Reference Manual, publication 1756-RM099
Provides information on safety application requirements for GuardLogix 5570 controllers in Studio 5000 Logix Designer projects.
GuardLogix Controllers User Manual, publication 1756-UM020
Provides information on how to install, configure, program, and use GuardLogix 5560 and 5570 controllers in RSLogix 5000 projects.
GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093
Provides information on safety application requirements for GuardLogix 5560 and 5570 controllers in RSLogix 5000 projects.
GuardLogix Safety Application Instructions Safety Reference Manual, publication 1756-RM095
Provides reference information describing the GuardLogix Safety Application Instruction Set.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
9
Page 10
Preface
Resource
Description
EtherNet/IP Embedded Switch Technology Application Guide, publication ENET-AP005
Describes how to install, configure, and maintain linear and Device Level Ring (DLR) networks using Rockwell Automation EtherNet/IP devices with embedded switch technology.
Ethernet Design Considerations Reference Manual, publication ENET-RM002
Describes the required media components and how to plan for and install these required components.
ODVA Media Planning and Installation Manual, publication 00148-BR00, available from the EtherNet/IP™ Library at ODVA.org
Describes the required media components and how to plan for and install these required components.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
About the Specifications and Dimensions in This Manual
Product specifications and accessories can change at any time based on improvements and other reasons. Consult with your Rockwell Automation representative to confirm actual specifications of purchased product. Dimensions and weights are nominal and are not for use for manufacturing purposes, even when tolerances are shown.
Terminology
Refer to the table for the meaning of common terms.
Term
Definition
1732ES modules
Also known as ArmorBlock® Guard I/O EtherNet/IP Safety Modules.
1791ES modules
Also known as CompactBlock Guard I/O EtherNet/IP Safety Modules.
Connection
Logical communication channel for communication between nodes. Connections are maintained and controlled between masters and slaves.
DLR
Acronym for Device Level Ring, a type of network topology.
EDS
Acronym for Electronic Data Sheet, a template that RSNetWorx™ software uses to display the configuration parameters, I/O data profile, and connection-type support for a given I/O module. These are simple text files used by RSNetWorx software for you to identify products and commission them on a network.
L-
Output +24V DC common.
M
Sinking output common channel, output switches to the common voltage.
MTBF
Acronym for mean time between failure, the average time between failure occurrences.
NAT
Acronym for network address translation, a service that lets modules reuse IP addresses throughout a network.
ODVA
Acronym for Open DeviceNet Vendor Association, a nonprofit association of vendors established for the promotion of CIP networks.
P
Sourcing output channel, output switches to the plus voltage.
PFD
Acronym for probability of failure on demand, the average probability of a system to fail to perform its design function on demand.
PFH
Acronym for probability of failure per hour, the probability of a system to have a dangerous failure occur per hour.
Proof test
Periodic test performed to detect failures in a safety-related system so that, if necessary, the system can be restored to an as-new condition or as close as practical to this condition.
S+
Output +24V DC.
SNN
Acronym for safety network number, which uniquely identifies a network across all networks in the safety system. You are responsible for assigning a unique number for each safety network or safety sub-net within a system.
Standard
Devices or portions of devices that do not participate in the safety function.
10
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015