The text of a manual · part 2 of 14
Guard I/O EtherNet/IP Safety Modules User Manual, pages 11 to 20
Pages 11 to 20 of 140
The original document is the PDF (7.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1791ES
Page 11
Chapter
1
About the Modules
Topic
Page
Before You Begin
11
Understand Suitability for Use
12
Follow Precautions for Use
12
I/O Module Overview
13
About Catalog Numbers
15
Selecting a Power Supply
15
Programming Requirements
15
About CIP Safety in EtherNet/IP Safety Architectures
16
Identify Major Parts of the Module
17
Read this chapter for important overview information and precautions for use for the Guard I/O modules that implement the EtherNet/IP safety protocol. This chapter also includes an overview on how these I/O modules are used within a safety system.
Before You Begin
Follow these guidelines when using a module, noting that in this manual we use safety administrator to mean a person qualified, authorized, and responsible to secure safety in the design, installation, operation, maintenance, and disposal of the machine. • Read and understand this manual before installing and operating the module. • Keep this manual in a safe and accessible place where personnel can refer to it when necessary. • Use the module properly according to the installation environment, performance, and functions of the machine. • Verify that a safety administrator conducts a risk assessment on the machine and determines module suitability before installation. For CE Low Voltage Directive (LVD) compliance, verify that the external power supply that provides power to the modules is rated safety extra-low voltage (SELV). Some Rockwell Automation Bulletin 1606 power supplies are SELVcompliant. See Switched Mode Power Supply Specifications Technical Data, publication 1606-TD002, and the installation instructions for the power supplies.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
11
Page 12
Chapter 1
About the Modules
Firmware Information and Downloads
Verify that the Guard I/O firmware revision is correct prior to commissioning the safety system. Firmware information and downloads for safety modules are available at this link: http://www.rockwellautomation.com/rockwellautomation/support/pcdc.page.
Functional Safety Certificates
Safety certificates for Functional Safety modules are available at this link: http://www.rockwellautomation.com/rockwellautomation/certification/ safety.page?
Understand Suitability for Use
Rockwell Automation is not responsible for conformity with any standards, codes, or regulations that apply to the combination of products in your application or use of the product. Take all necessary steps to determine the suitability of the product for the systems, machine, and equipment with which it is used. Know and observe all prohibitions of use applicable to this product. Never use the products for an application involving serious risk to life or property without making sure that the system as a whole is designed to address the risks and that the Rockwell Automation product is properly rated and installed for the intended use within the overall equipment or system. Use the module only in an environment that is within the general specifications of the module.
Follow Precautions for Use
Follow the precautions for use listed here and throughout this manual. ATTENTION: Follow Safety Standards for Installation and Testing • Use only appropriate components or devices complying with relevant safety standards corresponding to the required safety category and safety integrity level: • Conformity to requirements of the safety category and safety integrity level must be determined for the entire system. • We recommend you consult a certification body regarding assessment of conformity to the required safety integrity level or safety category. • You must confirm compliance with the applicable standards for the entire system. • Perform testing to confirm that all device configuration data and operation is correct before starting system operation. • After installation of the module, a safety administrator must confirm the installation and conduct trial operation and maintenance procedures.
12
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 13
About the Modules
Chapter 1
ATTENTION: Personnel responsible for the application of safety-related programmable electronic systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in using the system.
ATTENTION: Do not disassemble, repair, or modify the module. Any changes to the module can result in the loss of safety functions.
ATTENTION: Do not use EtherNet/IP standard I/O data or explicit message data as safety data.
ATTENTION: Installing or Replacing Modules • When installing or replacing modules, clear any previous configuration before connecting the module to the network or connecting input or output power to the module. • When replacing a device, configure the replacement device suitably and confirm that it operates correctly.
ATTENTION: In case of malfunction or damage, no attempts at repair should be made. The module should be returned to the manufacturer for repair. Do not dismantle the module.
I/O Module Overview
The Guard I/O modules implement the CIP safety protocol extensions over EtherNet/IP networks and provide various features for a safety system. Use the modules to construct a safety-control network system that meets the requirements up to Safety Integrity Level Claim Limit 3 (SIL CL 3), as defined in IEC 61508 and Category 4 (CAT. 4), Performance Level e (PLe), as defined in ISO 13849-1. Remote I/O communication for safety I/O data is performed through safety connections supporting CIP safety over an EtherNet/IP network, and data processing is performed in the safety controller. The status and fault diagnostics of the I/O modules are monitored by a safety controller through a safety connection by using a new or existing EtherNet/IP network.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
13
Page 14
Chapter 1
About the Modules
The following is a list of features common to Guard I/O modules: • CIP safety and EtherNet/IP protocol conformance • Safety inputs – Safety devices, such as emergency stop push buttons, gate switches, and safety light curtains, can be connected. – Dual-channel mode evaluates consistency between two input signals (channels), which allows use of the module for Safety Category 3 and 4. – Single-channel evaluates one input signal (channel), which allows use of the module Safe Inputs for safety Category 2 and in applications rated up to and including Performance Level d / SIL CL2. – The time of a logical discrepancy between two channels can be monitored by using a discrepancy time setting. – An external wiring short-circuit check is possible when inputs are wired in combination with test outputs. – Independently adjustable on and off delay is available per channel. • Test outputs – Separate test outputs are provided for short circuit detection of a safety input (or inputs). – Power (24V) can be supplied to devices, such as safety sensors. – Test outputs can be configured as standard outputs. – All Guard I/O modules have numerous test outputs, of which some can be used for broken wire detection of a muting lamp. • Safety outputs – Dual-channel mode evaluates consistency between two output signals (channels). – Safety outputs can be pulse tested to detect field wiring shorts to 24V DC and 0V DC. • I/O status data – In addition to I/O data, the module includes status data for monitoring I/O circuits. • Removable I/O connectors (only 1791ES modules) – I/O connectors support mechanical keying. • Network address translation (NAT) support – Available in Logix Designer version 24 or later, NAT is a service that translates one IP address to another IP address via a NAT-configured switch. The switch translates the source and destination addresses within data packets as traffic passes between subnets. This service is useful if you need to reuse IP addresses throughout a network. For example, NAT makes it possible for devices that share a single IP address on a private subnet to be segmented into multiple identical private subnets while maintaining unique identities on the public subnet.
14
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 15
About the Modules
About Catalog Numbers Catalog Number
Chapter 1
See the table for a description of the Guard I/O modules.
Description
Enclosure Type Rating
1791ES-IB16
CompactBlock safety input module
1791ES-IB8XOBV4
CompactBlock safety I/O module with solid-state outputs
1732ES-IB12XOB4
ArmorBlock® safety I/O module with solid-state outputs
1732ES-IB12XOBV2
ArmorBlock safety I/O module with solid-state outputs
Safety Inputs Test Outputs(1)
Meets IP20 Meets IP67/IP65
Safety Outputs (solid-state)
16
16, 8
8
8 bipolar outputs (4 pairs)
12
12
4 sourcing outputs
12
12
4 bipolar outputs (2 pairs)
(1) Broken wires can be detected on the muting outputs.
For CE LVD compliance, verify that the external power supply that provides power to the modules is safety extra-low voltage (SELV) rated. Some Rockwell Automation Bulletin 1606 power supplies are SELV-compliant. See Switched Mode Power Supply Specifications Technical Data, publication 1606-TD002, and the installation instructions for the modules.
Selecting a Power Supply
ATTENTION: Prevent Electric Shock To prevent electric shock, use a DC power supply that meets the following requirements: • A DC power supply with double or reinforced insulation; for example, according to IED/EN 60950, or EN 50178, or a transformer according to IEC/EN 61558. • A DC power supply satisfies requirement for class 2 circuits or limited voltage/ current circuit stated in UL 508. • An external power supply that is safety extra-low voltage (SELV) rated.
ATTENTION: Do not Exceed Specified Voltage • Do not apply DC voltages exceeding the rated voltages to the module. • Apply properly specified voltages to the module inputs. Applying inappropriate voltages causes the module to fail to perform its specified function, which leads to loss of safety functions or damage to the module.
Programming Requirements
Use the minimum software versions listed here. Cat. No.
Studio 5000 Environment Version(1)
RSLogix 5000 Software Version (1) (EtherNet/IP Network)
21
16
1791ES-IB16 1791ES-IB8XOBV4 1732ES-IB12XOB4 1732ES-IB12XOBV2 (1) This version or later.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
15
Page 16
Chapter 1
About the Modules
Use Guard I/O modules in EtherNet/IP safety architectures as shown in the figure. The Guard I/O family is a set of I/O modules that when connected to an EtherNet/IP safety network are suitable for applications up to SIL CL 3 as defined in IEC 61508; and CAT. 4, PLe, as defined in ISO 13849-1.
About CIP Safety in EtherNet/IP Safety Architectures
Figure 1 - Safety Interlocking and Control Via CIP Safety (linear and star topology) EtherNet/IP Network RSLogix Software RSView Software
DeviceNet Network DeviceNet Network
ControlNet Network
DeviceNet Network
EtherNet/IP Network ControlNet™ Network DeviceNet™ Network Standard Communication
Figure 2 - Safety Interlocking and Control Via CIP Safety (DLR topology) Only 1732ES Modules
EtherNet/IP Network
RSLogix Software RSView Software
Only the 1732ES Modules are compatible with DLR topology
Safety controllers control the safety outputs. Safety or standard controllers can control the standard outputs. 16
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 17
About the Modules
Chapter 1
See the figure for module identification. See Chapter 3 for pinout information.
Identify Major Parts of the Module
Figure 3 - 1791ES Modules Power Connector
I/O Connectors
Status Indicators
Network Activity Indicator EtherNet/IP Connector
IP Address Switch
EtherNet/IP Address Label
I/O Connectors
Figure 4 - 1732ES Modules Functional Earth GND – Ethernet (removable) Port 1 Ethernet Connector
Port 1 Network Activity Indicator Module Status Indicator
Port 2 Ethernet Connector
Port 2 Network Activity Indicator Network Status Indicator
IP Address Switch (3 total) I/O Status Indicator (16 total)
I/O Connectors
Input Power Status Indicator Power Connector (power in)
I/O Connectors
Output Power Status Indicator Power Connector (power pass-thru)
Functional Earth GND – EMC
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
17
Page 18
Chapter 1
About the Modules
Notes:
18
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 19
Chapter
2
Understand the Operation of Safety Functions
Topic
Page
Self-diagnostic Functions
20
Configuration Lock
20
I/O Status Data
20
Safety Inputs
21
Muting Lamp Operation
28
Safety Outputs
30
Controlling Devices
33
Read this chapter for information related to the safety functions of the modules. Also included is a brief overview on international standards and directives that you must be familiar with.
Safe State ATTENTION: Safety State of the Module • Safety state of the inputs and outputs is defined as the off state. • Safety state of the module and its data is defined as the off state. • Use the Guard I/O module only in applications where the off state is the safety state. The following status is the safety state of the Guard I/O modules: • Safety outputs: off • Safety input data to network: off Figure 5 - Safety Status EtherNet/IP Network
Inputs to Network Off
Safety Status
Output Off
Input
The module is designed for use in applications where the safety state is the off state. Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
19
Page 20
Chapter 2
Understand the Operation of Safety Functions
Self-diagnostic Functions
Self-diagnostics are performed when the power is turned on and periodically during operation. If a fatal internal module error occurs, the red module status (MS) indicator illuminates, and the safety outputs and input data and status to the network turn off.
Configuration Lock
After configuration data has been downloaded and verified, the configuration data within the module can be protected. For GuardLogix systems, the status indicator is not used. Reference information about safety signatures in the GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093.
I/O Status Data
In addition to I/O data, the module provides status data for monitoring the I/O circuits. The status data includes the following data, which can be read by the controllers. Note that 1 = ON/Normal, and 0 = OFF/Fault/Alarm. • Individual point input status • Combined input status • Individual point output status • Combined output status • Individual test output status • Individual output readback (actual ON/OFF state of the outputs) Status data indicate whether each safety input, safety output, or test output is normal (normal status: ON, faulted status: OFF). For fatal errors, communication connections can be broken, so the status data cannot be read. Combined status is provided by an AND of the status of all safety inputs or all safety outputs. When all inputs or outputs are normal the respective combined status is ON. When one or more of them has an error the respective combined status is OFF. This is known as the combined safety input status or combined safety output status.
20
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015