Page 21
Understand the Operation of Safety Functions
Chapter 2
Read this section for information about safety inputs and their associated test outputs. A safety input can be used with test outputs. Safety inputs are used to monitor safety input devices.
Safety Inputs
Using a Test Output with a Safety Input A test output can be used in combination with a safety input for short circuit detection. Configure the test output as a pulse test source and associate it to a specific safety input. The test output can also be used as a power supply to source 24V DC for an external input circuit. Figure 6 - Example Use of a 1791ES-IB16 Module 24V DC
IN+ IN-
I8
I9
T8
T9
I10
I11
T10
T11M
I12
I13
T12
T13
I14
I15
T14
T15M
I0
I1
T0
T1
I2
I3
T2
T3M
I4
I5
T4
T5
I6
I7
T6
T7M
24V DC Output with Test Pulse
Safety Input External Contact
Table 1 - Typical Pulse Width and Period Cat. No.
Pulse Width
Period
500 μs
150 ms
1791ES-IB8XOBV4 1791ES-IB16 1732ES-IB12XOB4 1732ES-IB12XOBV2
Figure 7 - Test Pulse in a Cycle OUT Typical 500 μs
On Typical 150 ms
Off
ATTENTION: Do not use test outputs as safety outputs. Test outputs do not function as safety outputs.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
21
Page 22
Chapter 2
Understand the Operation of Safety Functions
When the external input contact is closed, a test pulse is output from the test output terminal to diagnose the field wiring and input circuitry. By using this function, short-circuits between input signal lines and the power supply (positive side), and short-circuits between input signal lines can be detected. Figure 8 - Short-circuit Between Input Signal Lines
24V
IN+
IN24V 0V
T0
External Contact Short-circuit Between Input Signal Lines and Power Supply (positive side)
IN0
T1
IN1
22
External Contact
Short-circuit Between Input Signal Lines
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 23
Understand the Operation of Safety Functions
Chapter 2
If an error is detected, safety input data and safety input status turns off. Figure 9 - Single Channel Normal Operation and Fault Detection (not to scale) Normal Operation
T0
24V 0V ON
External Device OFF Input Terminal 0
ON OFF
Safety Input 0 Remote I/O Data
ON OFF
Safety Input Status 0
ON OFF 24V
Fault Detection
T0 0V ON External Device OFF Input Terminal 0
ON OFF ON
Fault Detected
Safety Input 0 OFF
Remote I/O Data Safety Input Status 0
ON OFF
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
23
Page 24
Chapter 2
Understand the Operation of Safety Functions
Set Dual-channel Mode and Discrepancy Time To support redundant channel safety devices, the consistency between signals on two channels can be evaluated. Either equivalent or complementary can be selected. This function monitors the time during which there is a discrepancy between the two channels. If the length of the discrepancy exceeds the configured discrepancy time (0…65,530 ms in increments of 10 ms), the safety input data and the individual-safety input status turn off for both channels. IMPORTANT
The dual-channel function is used with two consecutive inputs that are paired together, starting at an even input number, such as inputs 0 and 1; 2 and 3; and so on.
IMPORTANT
Do not set the discrepancy time longer than necessary. The purpose of the discrepancy time is to allow for normal differences between contact switching when demands are placed on safety inputs. For this testing to operate correctly, only a single demand on the safety input is expected during the discrepancy time. If the discrepancy time is set too high, and multiple demands occur during this time, then both safety input channels will fault.
Table 2 shows the relation between input terminal states and controller input data and status. Table 2 - Terminal Input Status and Controller I/O Data Dual-channel Mode
Dual-channels, Equivalent
Dual-channels, Complementary
24
Input Terminal IN0 IN1 OFF OFF ON ON OFF OFF ON ON
OFF ON OFF ON OFF ON OFF ON
Controller Input Data and Status Safety Safety Safety Input 0 Data Input 1 Data Input 0 Status OFF OFF ON OFF OFF OFF OFF OFF OFF ON ON ON OFF ON OFF OFF ON ON ON OFF ON OFF ON OFF
Safety Input 1 Status ON OFF OFF ON OFF ON ON OFF
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Dual- channel Dual-channel Resultant Resultant Data Status OFF OFF OFF ON OFF OFF ON OFF
Normal Fault Fault Normal Fault Normal Normal Fault
Page 25
Understand the Operation of Safety Functions
Chapter 2
Dual-channels, Equivalent In Equivalent mode, both inputs of a pair must typically be in the same (equivalent) state. When a transition occurs in one channel of the pair, prior to the transition of the second channel of the pair, a discrepancy occurs. If the second channel transitions to the appropriate state prior to the discrepancy time elapsing, the inputs are considered equivalent. If the second transition does not occur before the discrepancy time elapses, the channels fault. In the fault state the input and status for both channels are set low (off ). When configured as an equivalent dual pair, the data bits for both channels are sent to the controller as equivalent, both high or both low. Figure 10 - Equivalent, Normal Operation and Fault Detection (not to scale)
Normal Operation
IN0
ON OFF ON
IN1 OFF Discrepancy Time Safety Input 0
ON OFF
Remote I/O Data
Safety Input 1
ON OFF ON
Safety Input Status 0, 1
Fault Detection
OFF ON
IN0 OFF ON IN1 OFF Discrepancy Time Safety Input 0
ON OFF
Remote I/O Data
ON Safety Input 1 OFF Safety Input Status 0, 1
ON
Fault Detected
OFF
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
25
Page 26
Chapter 2
Understand the Operation of Safety Functions
Dual-channels, Complementary In Complementary mode, the inputs of a pair are typically in the opposite (complementary) state. When a transition occurs in one channel of the pair prior to the transition of the second channel of the pair, a discrepancy occurs. If the second channel transitions to the appropriate state prior to the discrepancy time elapsing, the inputs are considered complementary. If the second transition does not occur before the discrepancy time elapses, the channels fault. The fault state of complementary inputs is the even-numbered input turned off and the odd-numbered input turned on. Note that if faulted, both channel status bits are set low. When configured as a complementary dual-channel pair, the data bits for both channels are sent to the controller in complementary, or opposite states. Figure 11 - Complementary, Normal Operation and Fault Detection (not to scale) Normal Operation
IN0
ON OFF ON
IN1 OFF Safety Input 0
ON
Discrepancy Time
OFF Remote I/O Data
Safety Input 1
ON OFF ON
Safety Input Status 0, 1
OFF ON
Fault Detection
IN0 OFF ON IN1 OFF
Safety Input 0
Discrepancy Time
ON OFF
Remote I/O Data
ON Safety Input 1 OFF Safety Input Status 0, 1
26
ON OFF
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Fault Detected
Page 27
Understand the Operation of Safety Functions
Chapter 2
Safety Input Fault Recovery If an error is detected, the safety input data remains in the off state. Follow this procedure to activate the safety input data. 1. Remove the cause of the error. 2. Place the safety input (or safety inputs) into the safety state. The safety input status turns on (fault cleared) after the input-error latch time has elapsed. The I/O indicator (red) turns off. The input data can now be controlled.
Input Delays On-delay – An input signal is treated as logic 0 during the on-delay time (0…126 ms, in increments of 6 ms) after the input contact’s rising edge. The input only turns on if the input contact remains on after the on-delay time has elapsed. This helps prevent rapid changes of the input data due to contact bounce. Figure 12 - On-delay Signal InputInput Signal
ON ON OFFOFF
Remote I/O I/O ON ON Remote Safety DataData Safety OFF Input OFF Input
ON-delay On-delay
44094
Off-delay – An input signal is treated as logic 1 during the off-delay time (0…126 ms, in increments of 6 ms) after the input contact’s falling edge. The input only turns off if the input contact remains off after the off delay time has elapsed. This helps prevent rapid changes of the input data due to contact bounce. Figure 13 - Off-delay Input InputSignal Signal
ON OFF OFF
ON ON Remote I/OI/O Data Remote Data OFF Safety SafetyInput Input OFF
Off-delay OFF-delay
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
27
Page 28
Chapter 2
Understand the Operation of Safety Functions
The 1732ES modules support this muting lamp feature. The feature was added to 1791ES modules in firmware revision 1.009. The operation of the muting status bits for the test outputs has changed. Certain test outputs are controlled by your PLC processor program to illuminate a muting lamp: • T3 and T7 for 1791ES-IB8XOBV4 • T3, T7, and T11 for 1732ES-IB12XOB4 and 1732ES-IB12XOBV2 • T3, T7, T11, and T15 for 1791ES-IB16
Muting Lamp Operation
Muting lamp status is monitored with a test that runs periodically during every test interval to detect a burned-out lamp. The test runs repeatedly when the test output is commanded on. The figure below explains how muting lamp operation, status, and fault detection are monitored. TIP
The lamp test interval is 3 seconds. Two consecutive failed lamp tests are required to declare a burned-out lamp condition. The lamp test may not run immediately after the test output is energized. It starts at the next 3-second interval. To allow time for two consecutive test intervals, program a minimum Test Output On Time of 6 seconds.
Figure 14 - Muting Lamp Timing Diagram Connected
Connected Disconnected
Muting Lamp
1. Burned-out lamp detected. 2. Good lamp detected. 3. Intermittent lamp testing stopped. 4. Intermittent lamp testing started.
Disconnected
Active
Test Time 1
Lamp Test
2
Inactive Test Interval
Bulb is Connected/Good Good Muting Status Bulb is Disconnected/Burned-out Burned-out
On
On
T3 Output* Off Off
* IMPORTANT: The output is controlled by the user’s program, not by the Muting Status bit.
28
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
3
4
Page 29
Understand the Operation of Safety Functions
Chapter 2
Table 3 shows the expected behavior of the muting status bits. Keep these points in mind as well: • When power is applied to the module, and a test output capable of operating as a muting output remains commanded off, the muting status defaults to on. This bit operation is designed to help prevent erroneous muting instruction faults from the GuardLogix controller. This bit status may not be the true indication of a burned-out lamp. IMPORTANT Before checking the state of the corresponding muting status, be sure the test output is commanded on. Once the test output is commanded on, a maximum time of 6 seconds is required for the module to detect a burned-out lamp. • If a muting lamp circuit is open when power is applied to the module, the condition is detected when the test output is commanded on. • When a lamp burns out and is replaced, the fault (muting status bit) returns to the normal condition, independent of the state of the test output. Table 3 - Muting Status Bit Operation Test Output Commanded State
Lamp Condition
Muting Status Bit
Description
ON
Bad (open circuit)
0
Repair lamp.
ON
Good
1
Normal condition. Lamp is operating properly.
OFF
Bad (open circuit)
0
If lamp remains off after a test output capable of operating as a muting output is cycled, repair the lamp.
OFF
Good
1
Normal condition.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
29
Page 30
Chapter 2
Understand the Operation of Safety Functions
Safety Outputs
Read this section for information about safety outputs.
ATTENTION: Serious injury can occur due to the breakdown of safety outputs. Do not connect loads beyond the rated value to the safety outputs.
Safety Output with Test Pulse When the safety output is on, the safety output can be test pulsed, as shown in Table 4 and Figure 15. Table 4 - Safety Output Test Pulse Cat. No.
Pulse Width
Period
700 μs
600 ms
1791ES-IB8XOBV4 1732ES-IB12XOB4 1732ES-IB12XOBV2
By using this function, short-circuits between sourcing output signal lines and the power supply (positive side), short-circuits between sinking output signal lines and the power supply (negative side), and short-circuits between output signal lines of the same polarity (from sourcing output to sourcing output or from sinking output to sinking output) can be detected. If an error is detected, the safety output data and individual-safety output status turns off. Figure 15 - Test Pulse in a Cycle OUT Typical 700 μs
IMPORTANT
30
On Typical 600 ms
Off
To prevent the test pulse from causing the connected device to malfunction, pay careful attention to the input response time of the device.