Page 31
Understand the Operation of Safety Functions
Chapter 2
Dual-channel When the data of both channels is in the on state, and neither channel has a fault, the outputs are turned on. The status is normal. If a fault is detected on one channel, the safety output data and individual safety output status turn off for both channels. Figure 16 - Dual-channel (not to scale) Normal Operation
OUT0
ON OFF ON
OUT1 OFF Remote I/O Data
Safety Output Status 0, 1
ON OFF ON
Fault Detection OUT0
OUT1
OFF ON OFF
Remote I/O Data
Safety Output Status 0, 1
ON
Error Detected
OFF
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
31
Page 32
Chapter 2
Understand the Operation of Safety Functions
Single-channel When the data of the channel is in the on state, and the channel does not have a fault, the output is turned on. The status is normal. If a fault is detected on the channel, the safety output data and individual safety output status turn off for the channel. Safety outputs configured for single-channel operation must be controlled as pairs for use in functional safety applications.
IMPORTANT
Figure 17 - Single-channel (not to scale) Normal Operation
OUT0
ON OFF
Remote I/O Data
Safety Output Status 0
OFF
ON
Fault Detection OUT0
Remote I/O Data
ON
Safety Output Status 0, 1
OFF
ON
Error Detected
OFF
Safety Output Fault Recovery If a fault is detected, the safety outputs are switched off and remain in the off state. Follow this procedure to reactivate the safety output data for modules with bipolar safety outputs (1791ES and 1732ES-IB12XOBV2 modules). 1. Remove the cause of the error. 2. Place the safety output (or safety outputs) into the safety state. The safety output status turns on (fault cleared) when the output-error latch time has elapsed. The I/O indicator (red) turns off. The output data can now be controlled.
32
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 33
Understand the Operation of Safety Functions
Chapter 2
For modules with sourcing-only safety outputs (only 1732ES-IB12XOB4 modules), safety output faults are considered critical enough to require a module power cycle to clear (a sourcing safety output channel shorted to output power supply positive). For modules with sourcing-only safety outputs (only 1732ES-IB12XOB4 modules), one of these faults on any safety output channel results in all sourcingonly safety outputs being placed in the safe state (off ). Follow this procedure to reactivate the safety outputs after one of these faults. 1. Remove the cause of the error. 2. Power cycle the module. The output data can now be controlled.
Controlling Devices
See the table for information about controlling devices. ATTENTION: Use appropriate devices as indicated in the Controlling Device Requirements table. Serious injury can occur due to loss of safety functions.
Table 5 - Controlling Device Requirements Device Emergency stop switches Door interlocking switches, limit switches Safety sensors Relays with forcibly- guided contacts, contactors Other devices
Requirement Allen-Bradley Bulletin Safety Components Use approved devices with direct opening mechanisms complying with IEC/EN Bulletin 800F, 800T 60947-5-1. Use approved devices with direct opening mechanisms complying with IEC/EN Bulletin 440K, 440G, 440H for interlock switch 60947-5-1 and capable of switching microloads of 24V DC 5 mA. Bulletin 440P, 802T for limit switch Use approved devices complying with the relevant product standards, Any Guardmaster product regulations, and rules in the country where used. Use approved devices with forcibly-guided contacts complying with EN 50205. For feedback purposes, use devices with contacts capable of switching micro loads of Bulletin 700S, 100S 24V DC 5 mA. Evaluate whether devices used are appropriate to satisfy the requirements of, safety category levels.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
33
Page 34
Chapter 2
Understand the Operation of Safety Functions
Notes:
34
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 35
Chapter
3
Install the Module
Topic
Page
Topic
Page
Environment and Enclosure
35
Mount the Module
39
Prevent Electrostatic Discharge
36
Set Network IP Address
45
Environmental Considerations for Use
37
Make Connections for 1791ES Modules
46
Follow Wiring Precautions
37
Make Connections for 1732ES Modules
49
Follow DC Power Supply Precautions
39
Read and understand this section before you begin to install the module.
Environment and Enclosure
For 1791ES Modules ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments. This equipment is supplied as open-type equipment for indoor use. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, or be approved for the application if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see the following: • Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for more installation requirements. • NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
ATTENTION: 1791ES modules are certified for use only within the surrounding air temperature range of -20…60 °C (-4…140 °F). The 1791ES modules must not be used outside of this range.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
35
Page 36
Chapter 3
Install the Module
For 1732ES Modules This equipment is intended for use in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is not intended for use in residential environments and may not provide adequate protection to radio communication services in such environments. This equipment is supplied as enclosed equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication. Subsequent sections of this publication may contain more information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications. In addition to this publication, see the following: • Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for more installation requirements. • NEMA Standard 250 and EN/IEC 60529, as applicable, for explanations of the degrees of protection provided by enclosures.
ATTENTION: 1732ES modules are certified for use only within the surrounding air temperature range of -20…55 °C (-4…131 °F). The 1732ES modules must not be used outside of this range.
Prevent Electrostatic Discharge
36
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment: • Touch a grounded object to discharge potential static. • Wear an approved grounding wriststrap. • Do not touch connectors or pins on component boards. • Do not touch circuit components inside the equipment. • Use a static-safe workstation, if available. • Store the equipment in appropriate static-safe packaging when not in use.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 37
Install the Module
Environmental Considerations for Use
Chapter 3
Do not use the module in locations that are subject to these conditions: • Direct sunlight • Temperatures or humidity beyond the ranges noted in Specifications on page 123 • Condensation as the result of severe changes in temperature • Corrosive or flammable gases • Dust, especially iron dust (only 1791ES modules) • Salts • Water (only 1791ES modules) • Oil or chemicals • Shock or vibration beyond the range noted in Specifications on page 123 Do not clean the modules with these materials: • Acetone • Benzene • Thinner
Follow Wiring Precautions WARNING: Connecting and Disconnecting Wiring and Cables • When you connect or disconnect the removable terminal block (RTB) or power cables with field-side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. • If you connect or disconnect wiring or cables while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. • If you connect or disconnect the communication cables with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
ATTENTION: Wiring Guidelines • Disconnect the module from the power supply before wiring or connecting cables. Devices connected to the module can operate unexpectedly if wiring is performed while power is supplied. • Wire correctly after confirming the signal names of all terminals. • Wire the Guard I/O modules properly so that 24V DC line does not touch the safety outputs accidentally or unintentionally. • Do not route communication, input, or output wiring with conduit containing high voltage. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. • Wire conductors correctly and verify operation of the module before placing the system into operation. Incorrect wiring can lead to loss of safety function.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
37
Page 38
Chapter 3
Install the Module
ATTENTION: Be Aware of Safety Requirements Personnel responsible for the application of safety-related programmable electronic systems (PES) shall be aware of the safety requirements in the application of the system and shall be trained in using the system.
ATTENTION: Electrical Safety Considerations To comply with the CE Low Voltage Directive (LVD), all connections to this equipment must be powered from a source compliant with the following: • Safety Extra Low Voltage (SELV) Supply. • Protected Extra Low Voltage (PELV) Supply. If the devices (sensors) connected to the input connections require Class 2 power to operate, the auxiliary power connections of this equipment must be powered by a Class 2 source.
ATTENTION: Maintain IP Rating for 1732ES Modules Make sure all connectors and caps on 1732ES modules are securely tightened to properly seal the connections against leaks and maintain IP enclosure type requirements. Applicable only to 1732ES modules.
ATTENTION: You can configure Test Outputs to be used as standard outputs. You can connect actuators to Test Output points that are expecting a Standard configuration. Test Output points configured as Pulse Test or Power Supply become active whenever you apply input power to the module. These configured functions are independent of the I/O connections to the module.
ATTENTION: If a module with Test Outputs configured as Pulse Test or Power Supply is incorrectly installed in an application where actuators are connected to these Test Output points, the actuators are activated when input power is applied. To prevent this possibility, follow these procedures. • When installing a module, be sure that the module is correctly configured for the application or in the out-of-box condition before applying input power. • When replacing a module, be sure that the module is correctly configured for the application or in the out-of-box condition before applying input power. • Reset modules to their out-of-box condition when removing them from an application. • Be sure that all modules in replacement stock are in their out-of-box condition.
38
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 39
Install the Module
Follow DC Power Supply Precautions
Mount the Module
Chapter 3
ATTENTION: To prevent electric shock, use a DC power supply that meets these requirements: • A DC power supply with double or reinforced insulation, for example, according to IED/EN 60950 or EN 50178 or a transformer according to IEC/EN 61558. • A DC supply satisfies requirement for class 2 circuits or limited voltage/current circuit stated in UL 508. • Use an external power supply that is safety extra-low voltage (SELV) rated. • Follow these precautions for safe use. • Wire conductors correctly and verify operation of the module before placing the system into operation. Incorrect wiring can lead to loss of safety function. • Do not apply DC voltages exceeding the rated voltages to the module. • Apply properly specified voltages to the module inputs. Applying inappropriate voltages causes the module to fail to perform its specified function, which leads to loss of safety functions or damage to the module. • Never use test outputs as safety outputs. Test outputs are not safety outputs. • Note that after installation of the module, a safety administrator must confirm the installation and conduct trial operation and maintenance. • Do not disassemble, repair, or modify the module. This can result in loss of safety functions. • Use only appropriate components or devices complying with relevant safety standards corresponding to the required safety category and safety integrity level. • Conformity to requirements of the safety category and safety integrity level must be determined for the entire system. • We recommend you consult a certification body regarding assessment of conformity to the required safety integrity level or safety category. • Note that you must confirm compliance with the applicable standards for the entire system. • Disconnect the module from the power supply before wiring. Devices connected to the module can operate unexpectedly if wiring is performed while power is supplied.
Follow these guidelines to mount the manual: • Modules can be mounted horizontally or vertically. • Do not mount the module near any heat source that can increase the operating temperature of the module. • Catalog number 1732ES-IB12XOB4 and 1732ES-IB12XOBV2 modules meets IP65/IP67 (when marked). • Mount catalog number 1791ES-IB16 and 1791ES-IB8XOBV4 modules in an enclosure rated IP54 (IEC60529) or higher.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
39
Page 40
Chapter 3
Install the Module
Module Spacing Leave minimum spacing to the wiring duct or other objects for adequate ventilation and room for wiring. Figure 18 - Required Spacing for 1791ES-IB16 and 1791ES-IB8XOBV4 Modules 35 mm (1.38 in.) DIN Rail Use horizontal or vertical mounting. End Plate
Wiring Duct or Other Object
15 mm (0.6 in.) Min
15 mm (0.6 in.) Min
Wiring Duct or Other Object
End Plate
Figure 19 - Required Spacing for 1732ES-IB12XOB4 and 1732ES-IB12XOBV2 Modules
40
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015