Page 41

Install the Module

Chapter 3

Use horizontal or vertical mounting.

Wiring Duct or Other Object

25.4 mm (1.0 in.) Min To allow for right-angle cables.

25.4 mm (1.0 in.) Min To allow for right-angle cables.

Wiring Duct or Other Object

51 mm (2 in.) Min To allow for right-angle cables.

Wiring Duct or Other Object

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

41

Page 42

Chapter 3

Install the Module

Mount the 1791ES Modules on a DIN Rail Use a DIN rail that is 35 mm (1.38 in.) wide to install the module in the control panel. Secure the 35 mm (1.4 in.) DIN rail properly with fasteners every 200 mm (7.87 in.). Use an end plate on each end of the module to secure it to the DIN rail. Follow these steps to mount the module on a DIN rail. 1. Pry open the two gray latches to lock them in the open position. 2. Hook the module over the top of the DIN rail.

3. Rotate the module down until it makes full contact with the DIN rail. 4. Snap the latches back into place to secure the module to the rail.

5. Verify that the module is securely attached to the DIN rail.

Grounding ATTENTION: This product is grounded through the DIN-rail-to-chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum and plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure the DIN rail to the mounting surface approximately every 200 mm (7.87 in.) and use end plates to secure it to the DIN rail.

42

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 43

Install the Module

Chapter 3

Mount the 1732ES Modules on a Wall or Panel To mount the module on a wall or panel, use the screw holes provided in the module. Follow these steps to mount the module. 1. Use the mounting holes in the module as a guide to lay out the drill locations. 2. Mark the center of drill location with a pencil or marker. 248 mm (9.8 in.)

3. Use a center punch to mark the drill locations. 4. Use a 4.5 mm (0.177 in.) drill to make the pilot holes. 5. Mount the module with two #8 (M4) screws.

Mount the Module in High Vibration Areas If you mount the module in an area that is subject to shock or vibration, use a flat washer and a lock washer to mount the module.

Lock Washer Flat Washer

Torque the mounting screws to 0.68 N•m (6 lb•in.).

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

43

Page 44

Chapter 3

Install the Module

Grounding the 1732ES Modules This figure shows the grounding features for the 1732ES modules. Functional Earth Ground for Ethernet Shorting Bar

Ethernet Shield Mounting Point

Functional Earth Ground for EMC

Functional Earth Ground for Ethernet The mounting screw at the top of the module is for the complex Ethernet shield grounding features. The rectangular ‘shorting’ bar is held in place by a conductive screw/washer combination which connects electrically to the metal shields of the Ethernet connectors internal to the module. To ground the Ethernet shields at the module, leave the factory-installed ‘shorting’ bar with the conductive screw/washer combination in place and mount the module to an earth-grounded, conductive surface with conductive mounting hardware. If you do not want to ground the Ethernet shields at the module, remove the ‘shorting’ bar and conductive screw/washer combination and mount the module to wall or panel. TIP

If the Ethernet shields are not grounded at the module, the mounting screw at the Ethernet end of the module is not required to make a connection with earth ground.

Functional Earth Ground for EMC The mounting screw at the bottom of the module is required to be a conductive screw for EMC compliance. Mount the module to an earth-grounded, conductive surface using conductive mounting hardware to make the required connection with earth ground.

44

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 45

Install the Module

Set Network IP Address

Chapter 3

The module ships with the rotary switches set to 999 and DHCP enabled. WARNING: If you change the network IP switch settings while the power is on, an electrical arc can occur. This can cause an explosion in hazardous location installations. Be sure that power is removed, or the area is nonhazardous, before you change the network IP switch settings while the power is on.

ATTENTION: Set a suitable network IP addresses before connecting the module to a network.

IMPORTANT

Catalog number 1732ES-IB12XOB4 and 1732ES-IB12XOBV2 modules have plastic dust caps that cover the network IP switches. Remove the dust caps to adjust the IP address switches. The dust caps must be installed to maintain an IP65/67 rating. Torque the dust caps to 0.3 ± 0.03 N•m (2.5 ±0.3 lb•in).

Perform one of these steps to set the network IP address: • adjust the switches on the front of the module. • use a Dynamic Host Configuration Protocol (DHCP) server, such as Rockwell Automation BootP/DHCP Server Utility. • retrieve the IP address from nonvolatile memory. The module reads the switches first to determine if the switches are set to a valid number. You set the network address by adjusting the three switches on the front of the module. Use a small-blade screwdriver to rotate the switches. Line up the small notch on the switch with the number setting you wish to use. Valid settings range from 001…254. When the switches are set to a valid number, the module’s IP address is 192.168.1.xxx (where xxx represents the number set on the switches). The module’s subnet mask is 255.255.255.0 and the gateway address is set to 0.0.0.0. When the module is reading the network address set on the switches, the module does not have a host name assigned to it or use any Domain Name System. If the switches are set to an invalid number (such as 000 or a value greater than 254), the module checks to see if DHCP is enabled. If DHCP is enabled, the module asks for an address from a DHCP server. The DHCP server also assigns other Transport Control Protocol (TCP) parameters. If DHCP is not enabled, the module uses the IP address (along with other TCP configurable parameters) stored in nonvolatile memory. See Figure 20 on page 46 for an example of the network address switches.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

45

Page 46

Chapter 3

Install the Module

Figure 20 - Example Network Address This example shows the switches set at 163 with a network address being 192.168.1.163. 1791ES Network Address Switches

X100

X10

0

0 2

8

X1

0

0 2 4

0 2

8 6

4

6

X10

8 6

2

8

4

6

X100 1732ES Network Address Switches

0 2

8

4

6

X1

2

8

4

6

4

Make Connections for 1791ES Follow these guidelines when wiring the module: • For stranded wire, install an insulation-covered ferrule (DIN 46228-4 Modules standard compatible-type) at the ends before making wiring connections. • Torque screws for the power connector to 0.56…0.79 N•m (5…7 lb•in). • Torque screws for the I/O connectors to 0.5…0.56 N•m (4.5…5 lb•in).

See the Ethernet Design Considerations Reference Manual, publication ENET-RM002, for information about Ethernet cable.

Power Connections See Table 6 for a description of the pins in the power connector. Table 6 - Power Connector Pin Descriptions Pin No.

Signal

1

Input +24V DC power

2

Input power common

3

Output +24V DC power(1)

4

Output power common(1)

1

(1) NC on catalog number 1791ES-IB16 modules.

46

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

2 3 4

Page 47

Install the Module

Chapter 3

EtherNet/IP Connections See Table 7 for a description of the pins in the EtherNet/IP connector. Table 7 - EtherNet/IP Connector Pin Descriptions Pin No.

Signal

8

No connection

7

No connection

6

Receive data minus

5

No connection

4

No connection

3

Receive data plus

2

Transmit data minus

1

Transmit data plus

8 RJ45

1

I/O Connections For wiring diagrams, see Wiring Examples on page 57. Because the I/O connector has a structure that helps prevent incorrect wiring, make connections at the specified locations corresponding to the terminal numbers.

IMPORTANT

See Figure 21 for a description of the pins in the I/O connector. Figure 21 - I/O Connector Pin Descriptions I/O Field Power: 1 2 3 4

18 19 20 21 22 23 24 25 26

27 28 29 30 31 32 33 34

123456789

10 11 12 13 14 15 16 17

Table 8 - Terminal Positions for I/O Field Power Terminal No.

Signal

Terminal No.

Signal

1

Input +24V DC

3

Output +24V DC(1)

2

Input -24V DC

4

Output -24V DC(1)

(1) Applies only to catalog number 1791ES-IB8XOBV4 module.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

47

Page 48

Chapter 3

Install the Module

Table 9 - Terminal Positions for Terminal Numbers 1…18 Terminal No.

Signal

Terminal No.

Signal

1

Functional earth

10

Safety input 4

2

Safety input 0

11

Safety input 5

3

Safety input 1

12

Test output 4

4

Test output 0

13

Test output 5

5

Test output 1

14

Safety input 6

6

Safety input 2

15

Safety input 7

7

Safety input 3

16

Test output 6

8

Test output 2

17

Test output 7/muting

9

Test output 3/muting

18

Functional earth

Table 10 - Terminal Positions for Numbers 19…34 Terminal No.

48

Signal Cat. No. 1791ES-IB8XOBV4 Module

Cat. No. 1791ES-IB16 Module

19

Safety output 0(1)/switch +24V DC

Safety input 8

20

Safety output 1(1)/switch 24V DC common

Safety input 9

21

L-/24V DC common

Test output 8

22

S+/24V DC

Test output 9

23

Safety output 2(2)/switch +24V DC

Safety input 10

24

Safety output 3(2)/switch 24V DC common

Safety input 11/muting

25

L-/24V DC common

Test output 10

26

S+/24V DC

Test output 11

27

Safety output 4(3)/switch +24V DC

Safety input 12

28

Safety output 5(3)/switch 24V DC common

Safety input 13

29

L-/24V DC common

Test output 12

30

S+/24V DC

Test output 13

31

Safety output 6(4)/switch +24V DC

Safety input 14

32

Safety output 7(4)/switch 24V DC common

Safety input 15

33

L-/24V DC common

Test output 14

34

S+/24V DC

Test output 15/muting

(1) (2) (3) (4)

Safety outputs 0/1 must be controlled as a pair. Safety outputs 2/3 must be controlled as a pair. Safety outputs 4/5 must be controlled as a pair. Safety outputs 6/7 must be controlled as a pair.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 49

Install the Module

Chapter 3

Make Connections for 1732ES See the Ethernet Design Considerations Reference Manual, publication ENET-RM002, for information about Ethernet cable. Modules Power Connections This section describes the power connectors and recommended cables. Table 11 - Power Connector Pin Description Pin No.

Signal

1

Output +24V DC power

2

Input +24V DC power

3

Input power, common

4

Output power, common

Male Input (mates to female cable end)

Female Output (mates to male cable end)

Table 12 - Recommended Power Cables Description

Cat. No.

Mini right angle female to flying leads cord set

889N-R4AFC-6F(1)

Mini straight female to flying leads cord set

889N-F4AFC-6F(1)

Mini right angle male to flying leads cord set

889N-E4AFC-6F(1)

Mini straight male to flying leads cord set

889N-M4AFC-6F(1)

Mini right angle male to right angle female patch cord

889N-R4AFNE-2(2)

Mini straight male to straight female patch cord

889N-F4AFNM-2(2)

(1) Replace -6F (1.8 m [6 ft]) with -12 (3.7 m [12 ft]) or -20 (6.1 m [20 ft]) for additional standard cable lengths. (2) Replace -2 (2 m [6.6 ft]) with -5 (5 m [16.4 ft]) or -10 (10 m [32.8 ft]) for additional standard cable lengths.

See http://www.ab.com/en/epub/catalogs/6005557/6005561/10508712/ 10513424/10513435/Introduction.html for more information.

Power Pass Through The power required by the module is supplied via a 4-pin mini-style connector system. The module receives its required power through the male connector on the left. A female connector on the right is also provided so that power can be daisy chained from module to module. IMPORTANT

Use power pass through (daisy chaining of power) only for ‘de-energize to trip’ (safety state = OFF) applications.

Both modules require two 24V DC (nominal) supplies. These supplies are called the ‘input +24V DC power’ and the ‘output +24V DC power’. The input +24V DC power provides power for the module control and Ethernet portions of the module, the safety input/test output circuits, and the test output loads. The output +24V DC power provides power for the safety output circuits and the safety output loads.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

49

Page 50

Chapter 3

Install the Module

Internally, the input +24V DC power and output +24V DC power are isolated from each other. IMPORTANT

The maximum current that any pin on the power connectors can carry is10 A.

The input +24V DC power current required for a module in the daisy chain can be estimated as described here. IIP ~ IIPM + ITO + IIPDC Where: IIP is the input +24V DC power current through the module’s male power connector. IIPM is the input +24V DC power current required by the module itself (with no test output load current). ITO is the total test output load current for test outputs N (0…11). IIPDC is the total input +24V DC power current through the module’s female power connector (input +24V DC power current for the modules that follow in the daisy chain). IIPM can be approximated by 4.2 W divided by the input +24V DC power voltage. The table input +24V DC power calculation shows an example input +24V DC power current calculation for a system of four modules. The input +24V DC power voltage is 24V DC in this example. Module 1 is the first module in the daisy chain. The table should be filled out starting with the last module in the daisy chain, in this example Module 4. Once IIP is calculated for module 4, it transfers as the IIPDC value for Module 3. This process continues for all modules in the daisy chain. As can be seen in the cell with value set in bold, the maximum input +24V DC power current through the male power connectors in the daisy chain is 6.5A which is less than 10 A, so this system is adequate. If the IIP value for a module in this or any daisy chained system were to exceed 10 A that system would not meet the module requirement that the maximum current that any pin on the power connectors can carry is 10 A.

50

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015