Page 51

Install the Module

Chapter 3

Table 13 - Input +24V DC Power Calculation Value

Module 1

Module 2

Module 3

Module 4

IIPDC

4.875 A

3.250 A

1.625 A

0.000 A

IIPM

0.175 A

0.175 A

0.175 A

0.175 A

ITO0

0.005 A

0.005 A

0.005 A

0.700 A

ITO1

0.005 A

0.005 A

0.005 A

0.700 A

ITO2

0.005 A

0.005 A

0.700 A

0.005 A

ITO3

0.005 A

0.005 A

0.700 A

0.005 A

ITO4

0.005 A

0.700 A

0.005 A

0.005 A

ITO5

0.005 A

0.700 A

0.005 A

0.005 A

ITO6

0.700 A

0.005 A

0.005 A

0.005 A

ITO7

0.700 A

0.005 A

0.005 A

0.005 A

ITO8

0.005 A

0.005 A

0.005 A

0.005 A

ITO9

0.005 A

0.005 A

0.005 A

0.005 A

ITO10

0.005 A

0.005 A

0.005 A

0.005 A

ITO11

0.005 A

0.005 A

0.005 A

0.005 A

IIP

6.500 A

4.875 A

3.250 A

1.625 A

The output +24V DC power current required for a module in the daisy chain can be estimated as described here. IOP ~ IOPM + ISO + ISNSO + IOPDC Where: IOP is the output +24V DC power current through the module’s male power connector. IOPM is the output +24V DC power current required by the module itself (with no safety output load current). ISO is the total safety output load current for safety outputs N (safety outputs 0 and 2 for modules with bipolar safety outputs, or safety outputs 0…3 for modules with sourcing safety outputs). ISNSO is the total sensor output load current for the Output +24V DC power output pins (pin 1 in the output I/O connectors). IOPDC is the total output +24V DC power current through the module’s female power connector (output +24V DC power current for the modules that follow in the daisy chain). IOPM can be approximated by 1.56 W divided by the output +24V DC power voltage for the 1732ES-IB12XOBV2 module, and can be approximated by 1.08W divided by the output +24V DC power voltage. Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

51

Page 52

Chapter 3

Install the Module

The table output +24V DC power calculation shows an example output +24V DC power current calculation for a system of four modules. The output +24V DC power voltage is 24V DC in this example. Module 1 is the first module in the daisy chain. Modules 1 and 3 have bipolar safety outputs, Modules 2 and 4 have sourcing safety outputs. The table should be filled out starting with the last module in the daisy chain, in this example Module 4. Once IOP is calculated for module 4, it transfers as the IOPDC value for Module 3. This process continues for all modules in the daisy chain. As can be seen in the cell with value set in bold, the maximum output +24V DC power current through the male power connectors in the daisy chain is 9.02 A which is less than 10 A, so this system is adequate. If the IOP value for a module in this or any daisy chained system were to exceed 10A, that system would not meet the module requirement that the maximum current that any pin on the power connectors can carry is 10 A. Table 14 - Output +24V DC Power Calculation Value

Module 1

Module 2

Module 3

Module 4

Iopdc

6.755 A

4.600 A

2.245 A

0.000 A

Iopm

0.065 A

0.045 A

0.065 A

0.045 A

Iso0

1.000 A

0.500 A

1.000 A

0.500 A

Iso1

–

0.500 A

–

0.500 A

Iso2

1.000 A

0.500 A

1.000 A

0.500 A

Iso3

–

0.500 A

–

0.500 A

ISNSO

0.200 A

0.200 A

0.200 A

0.200 A

Iop

9.020 A

6.755 A

4.600 A

2.245 A

ATTENTION: To comply with the CE Low Voltage Directive (LVD), this equipment and all connected I/O must be powered from a source compliant with Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

EtherNet/IP Connections This section describes the EtherNet/IP connector and sample cables. Table 15 - EtherNet/IP Connector Pin Description

52

Pin No.

Signal

1

Tx+

2

Rx+

3

Tx-

4

Rx-

5

Shell/Shield

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 53

Install the Module

Chapter 3

Table 16 - Sample EtherNet/IP Cables Description

Cat. No.

M12 D-Coded straight to RJ45 patchcord

1585D-M4UBJM-2(1)

M12 D-Coded straight to flying leads cordset

1585D-M4UB-2(1)

M12 D-Coded straight to M12 straight patchcord

1585D-M4UBDM-2(1)

M12 D-Coded right angle to M12 right angle patchcord

1585D-E4UBDE-2(1)

(1) Replace -2 (2 m [6.6 ft]) with -1 (1 m [3.3 ft]), -5 (5 m [16.4 ft]) or -10 (10 m [32.8 ft]) for additional standard cable lengths.

See http://www.ab.com/en/epub/catalogs/6005557/6005561/10514505/ 10515166/Introduction.html for additional information.

I/O Connections This section describes the I/O connectors and recommended cables. Table 17 - I/O Connector Pin Description Pin No.

Input Signal

1

I/O Connector

Bipolar Output Signal

Sourcing Output Signal

Test out n+1

Output +24V DC power

Output +24V DC power

2

Input n+1

Output n+1 (N) (sinking)

Output n+1

3

Input common

Output power common

Output power common

4

Input n

Output n (P) (sourcing)

Output n

5

Test out n

Output power common

Output power common

Case

No connect

No connect

No connect

Figure 22 - I/O Connector Positions D

C

B

A

H

G

F

E

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

53

Page 54

Chapter 3

Install the Module

Table 18 - I/O Connector Pinouts Safety Input Signals

Safety Output Signals

Terminal

1732ES-IB12XOBV2 and 1732ES-IB12XOB4 Modules

Terminal

1732ES-IB12XOBV2 and 1732ES-IB12XOB4 Modules

Terminal

Only 1732ES-IB12XOBV2 Module

Only 1732ES-IB12XOB4 Module

A-1

Test out 1

D-1

Test out 7

G-1

Output +24V DC power

Output +24V DC power

A-2

Safety input 1

D-2

Safety input 7

G-2

Safety output 1 (N) (sinking)

Safety output 1(3) (sourcing)

A-3

Input common

D-3

Input common

G-3

Output power common

Output power common

A-4

Safety input 0

D-4

Safety input 6

G-4

Safety output 0(1) (P) (sourcing)

Safety output 0(3) (sourcing)

A-5

Test out 0

D-5

Test out 6

G-5

Output power common

Output power common

B-1

Test out 3

E-1

Test out 9

H-1

Output +24V DC power

Output +24V DC power

B-2

Safety input 3

E-2

Safety input 9

H-2

Safety output 3(2) (N) (sinking)

Safety output 3(4) (sourcing)

B-3

Input common

E-3

Input common

H-3

Output power common

Output power common

B-4

Safety input 2

E-4

Safety input 8

H-4

Safety output 2(2) (P) (sourcing)

Safety output 2(4) (sourcing)

B-5

Test out 2

E-5

Test out 8

H-5

Output power common

Output power common

C-1

Test out 5

F-1

Test out 11

C-2

Safety input 5

F-2

Safety input 11

C-3

Input common

F-3

Input common

C-4

Safety input 4

F-4

Safety input 10

C-5

Test out 4

F-5

Test out 10

(1) (2) (3) (4)

(1)

Safety outputs 0/1 must be controlled as a pair. Safety outputs 2/3 must be controlled as a pair. Safety outputs 0/1 may be controlled individually or as a pair. Safety outputs 0/1 may be controlled individually or as a pair.

Table 19 - Recommended I/O Connector Cables Description

Cat. No.

M12 right-angle male to flying leads cordset

889D-E5AC-2(1)

M12 straight-male to flying leads cordset

889D-M5AC-2(1)

M12 right-angle male to straight female patchcord

889D-F5ACDE-2(2)

M12 straight male to straight female patchcord

889D-F5ACDM-2(2)

(1) Replace -2 (2 m [6.6 ft]) with -5 (5 m [16.4 ft]) or -10 (10 m [32.8 ft]) for additional standard cable lengths. (2) Replace -2 (2m [6.6 ft]) with -OM3 (0.3 m [1.0 f t]), -1 (1 m [3.3 ft]), -5 (5 m [16.4 ft]), or -10 (10 m [32.8 ft]) for additional standard cable lengths.

See http://www.ab.com/en/epub/catalogs/6005557/6005561/6125318/ 8613745/8613769/8613771/Introduction.html for additional information.

54

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 55

Install the Module

Chapter 3

Label the IP Address and Device Connections The 1732ES module ships with 12 white labels that you can use to identify the IP address of the module, and the input and output connections. There are six areas on the module to place the labels, with six additional labels that can be used if the IP address or device connections change. Use a pen or indelible marker with a fine tip to write on the labels. You can also use a printing device to print the data onto the label. Contact a Brady representative at http://www.bradyid.com and ask about printer compatibility for part number PTLEP-171-593.

Apply two labels here to identify the IP address of the module.

IMPORTANT: Be sure that the surface of the module is clean and dry before you apply the labels to the module.

Apply one label between each pair of I/O connectors. On the left side of the label, identify the signal assignment to the I/O connection on the left side of the module. On the right side of the label, identify the signal assignment to the I/O connection on the right side of the module.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

55

Page 56

Chapter 3

Install the Module

Notes:

56

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 57

Chapter

4

Wiring Examples

Topic

Page

Wiring Examples for Safety Categories

57

Wiring by Application

61

Read this chapter for information about wiring and safety categories. See the tables that show input device connection methods and their safety categories.

Wiring Examples for Safety Categories

Table 20 - Input Device Connection Methods and Safety Categories Connected Device

Test Pulse from Test Output

Connection

Reset switch

No

Connect the switch between I0 and T0. T0 must be configured as 24V power supply.

Schematic Diagram

Safety Category N/A

1791ES Modules

I0

I1

T0

T1

1732ES Modules

Connect the switch between 24V DC and I0.

2

1

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

5 4

3

N/A

1791ES Modules

I0

I1

T0

T1

24V DC 1732ES Modules 2

1

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

5 4

3

24V DC

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

57

Page 58

Chapter 4

Wiring Examples

Table 20 - Input Device Connection Methods and Safety Categories (continued) Connected Device

Test Pulse from Test Output

Connection

Single-channel safety device

Yes

Connect the switch between I0 and T0

Schematic Diagram

Safety Category 2

Only 1732ES Modules

Emergency stop switch Door monitor

Yes

Connect the switches between I0 and T0, and I1 and T1

2

1

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

5 4

3

4

1791ES Modules

I0

I1

T0

T1

1732ES Modules 1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

58

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

2

1 5 4

3

Page 59

Wiring Examples

Chapter 4

Table 20 - Input Device Connection Methods and Safety Categories (continued) Connected Device

Test Pulse from Test Output

Connection

Emergency stop switch Door monitor

No

Connect the switches between T0 and I0 and I1, noting that T0 is configured for 24V power supply.

Schematic Diagram

Safety Category 3

1791ES Modules

I0

I1

T0

T1

1732ES Modules

Connect the switches between 24V DC and I0 and I1.

2

1

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

5 4

3

1791ES Modules

I0

I1

T0

T1

24V DC 1732ES Modules 1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

2

1 5 4

3

24V DC

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

59

Page 60

Chapter 4

Wiring Examples

Table 20 - Input Device Connection Methods and Safety Categories (continued) Connection

Schematic Diagram

Safety Category

Light curtain

Yes

Connect the OSSD1 and OSSD2 to I0 and I1, respectively. Connect the 24V power supply commons.

1791ES Modules

3 or 4 based on light curtain being used

OSSD2

Test Pulse from Test Output

OSSD1

Connected Device

PS1

In +

In -

I1

24V DC COM

OSSD1

T1

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

1732ES Modules PS1

1 - Output Power 2 - Input Power 3 - Input Common 4 - Output Common

T0

OSSD2

I0

4

2

3

1

2

1 5

3

4

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

OSSD2

60

OSSD1