Page 61

Wiring Examples

Chapter 4

Read this section for examples of wiring by application. See catalog number details for appropriate module.

Wiring by Application

Figure 23 - Emergency Stop Switch Dual-channel Inputs with Manual Reset 1791ES Modules PS1

In +

In -

FE

I0

I1

T0

T1

I2

I3

T2

T3M

S2 S1

PS1: User 24V DC Power Supply S1: Emergency Stop Switch (positive opening mechanism) S2: Reset Switch

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

1732ES Modules PS1

1 - Output Power 2 - Input Power 3 - Input Common 4 - Output Common

4

2

3

1

2

1

1 - Test Output 3 2 - Input 3 3 - Input Common 4 - Input 2 5 - Test Output 2

4

2

1

5

5 3

S1

4

3

S2

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Dual-channel Equivalent

Dual-channel Safety Input 0/1 Discrepancy Time

100 ms (application dependent)

Safety Input 1 Channel Mode

Test Pulse from Test Output

Safety Input 1 Test Source

Test Output 1

Safety Input 1 Safety Input 2

Test Output 0

Safety Input 2 Channel Mode

Used as standard input

Safety Input 2 Test Source

Not Used

Dual-channel Safety Input 2/3 Mode

Single Channel

Test Output 0 Mode

Pulse Test Output

Test Output 1

Test Output 1 Mode

Pulse Test Output

Test Output 2

Test Output 2 Mode

Power Supply Output

This example shows wiring and controller configuration when using the Guard I/O module. If used in combination with the programs in a safety controller, this wiring is Safety Category 4 in accordance with ISO 13849-1:2008 wiring requirements. Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

61

Page 62

Chapter 4

Wiring Examples

Figure 24 - Two-hand Monitor 1791ES Modules E1

In +

In -

FE

1732ES Modules 1 - Output Power 2 - Input Power 3 - Input Common 4 - Output Common

I0

I1

T0

T1

I2

S11

S12

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

1 - Test Output 3 2 - Input 3 3 - Input Common 4 - Input 2 5 - Test Output 2

4

2

3

1

2

1

Safety Input 1 Safety Input 2

Safety Input 3

T3M

2

1

5

5 3

S11

Safety Input 0

T2

E1

4

Controller Configuration

I3

3

4

S12

Parameter Name

Configuration Setting

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual Channel Safety Input 0/1 Mode

Dual Channel Complementary

Dual Channel Safety Input 0/1 Discrepancy Time

100 ms (application dependent)

Safety Input 1 Channel Mode

Test Pulse from Test Output

Safety Input 1 Test Source

Test Output 1

Safety Input 2 Channel Mode

Test Pulse from Test Output

Safety Input 2 Test Source

Test Output 0

Dual Channel Safety Input 2/3 Mode

Dual Channel Complementary

Dual Channel Safety Input 2/3 Discrepancy Time

100 ms (application dependent)

Safety Input 3 Channel Mode

Test Pulse from Test Output

Safety Input 3 Test Source

Test Output 1

Test Output 0

Test Output 0 Mode

Pulse Test Output

Test Output 1

Test Output 1 Mode

Pulse Test Output

This example shows wiring and controller configuration when using the Guard I/O module. If used in combination with the programs of a safety controller, the wiring is Category 4 in accordance with ISO 13849-1:2008 wiring requirements. 62

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 63

Wiring Examples

Chapter 4

Figure 25 - Mode Select Switch 1791ES Modules PS1

In +

In -

FE

I0

I1

T0

T1

S2

S1

PS1: User 24V DC Power Supply S1…S5: Switches

I2

S3

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

1732ES Modules

I3

T2

T3M

I4

S4

I5

T4

T5

I6

I7

T6

T7M

S5

1 - Test Output 3 2 - Input 3 3 - Input Common 4 - Input 2 5 - Test Output 2

1 - Test Output 5 2 - Input 5 3 - Input Common 4 - Input 4 5 - Test Output 4

PS1

1 - Output Power 2 - Input Power 3 - Input Common 4 - Output Common

4

2

3

1

2

1

4

S1

5

5 3

4

S2

S3

2

1

2

1

5

3

4

S4

S5

Controller Configuration

Parameter Name

Safety Input 0

Safety Input 0 Channel Mode

Safety Input

Safety Input 0 Test Source

None

Configuration Setting

Dual Channel Safety Input 0/1 Mode

Single Channel

Safety Input 1

Safety Input 1 Channel Mode

Safety Input

Safety Input 1 Test Source

None

Safety Input 2

Safety Input 2 Channel Mode

Safety Input

Safety Input 2 Test Source

None

Dual Channel Safety Input 2/3 Mode

Single Channel

Safety Input 3 Safety Input 4

Test Output 0

Safety Input 3 Channel Mode

Safety Input

Safety Input 3 Test Source

None

Safety Input 4 Channel Mode

Safety Input

Safety Input 4 Test Source

None

Dual Channel Safety Input 4/5 Mode

Single Channel

Test Output 0 Mode

Power Supply

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

3

63

Page 64

Chapter 4

Wiring Examples

Figure 26 - Muting Lamp Output 1791ES Modules PS1

In +

In -

FE

I0

I1

T0

T1

I2

I3

T2

L1

PS1: User 24V DC Power Supply L1: External Muting Lamp

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

1732ES Modules PS1

1 - Output Power 2 - Input Power 3 - Input Common 4 - Output Common

4

2

3

1

1

1 - Test Output 3 2 - Input 3 3 - Input Common 4 - Input 2 5 - Test Output 2

2

1

3

4

5 4

2 5

L1

Controller Configuration

Parameter Name

Configuration Setting

Test Output 3

Test Output 3 Mode

Muting Lamp Output

64

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

3

T3M

Page 65

Wiring Examples

Chapter 4

Figure 27 - Limit Switch Dual-channel Inputs and a Manual Reset 1791ES Modules PS1

In +

In -

FE

I0

I1

T0

T1

I2

I3

T2

T3M

S1 (N.C.)

Safety Guard

Close

PS1: User 24V DC Power Supply S1: Safety Limit Switch (positive opening mechanism) S2: Safety Limited Switch S3: Reset Switch

S3

S2 (N.O.)

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

1732ES Modules E1

1 - Output Power 2 - Input Power 3 - Input Common 4 - Output Common

4

2

3

1

2

1

1 - Test Output 3 2 - Input 3 3 - Input Common 4 - Input 2 5 - Test Output 2

4

2

1

5

5 3

3

4

S1 (N.C.)

Close

Safety Guard S2 (N.O.)

S3

Controller Configuration

Parameter Name

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Dual-channel Equivalent

Dual-channel Safety Input 0/1 Discrepancy Time

1000 ms (application dependent)

Safety Input 1 Safety Input 2

Configuration Setting

Safety Input 1 Channel Mode

Test Pulse from Test Output

Safety Input 1 Test Source

Test Output 1

Safety Input 2 Channel Mode

Used as Standard Input

Safety Input 2 Test Source

Not Used

Dual-channel Safety Input 2/3 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Test Output 1

Test Output 1 Mode

Pulse Test Output

Test Output 2

Test Output 2 Mode

Power Supply Output

This example shows wiring and controller configuration when using the Guard I/O module with limit switch dual-channel inputs and a manual reset. If used in combination with the programs of a safety controller, the wiring is Category 4 in accordance with ISO 13849-1:2008 wiring requirements. Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

65

Page 66

Chapter 4

Wiring Examples

Figure 28 - Guard I/O Module with Limit Switch Dual-channel Inputs and a Manual Reset 1791ES Modules

S1 L1

PS1

In +

In -

FE

I0

I1

T0

T1

I2

I3

T2

PS1: User 24V DC Power Supply L1: Lamp S1: Switch 1732ES Modules 1 - Output Power 2 - Input Power 3 - Input Common 4 - Output Common

S1 PS1

4 3

2 1

2

1 5 4

3

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

L1

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 1

Safety Input 1 Channel Mode

Standard Input

Safety Input 1 Test Source

None

Dual-channel Safety Input 0/1 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Standard Output

Test Output 1

Test Output 1 Mode

Power Supply

66

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

T3M

Page 67

Wiring Examples

Chapter 4

Figure 29 - Dual-load Bipolar Outputs

For the bipolar safety outputs to work as intended, you must connect the devices that are being controlled as shown in this figure. Connection of devices directly to 24V DC, 0V DC, or ground is strictly prohibited.

IMPORTANT

K1

1791ES Modules

K2 K2 K1 PS1

In +

M

PS2 Out +

In -

Out -

FE

O0 P

O1 M

L-

S+

O2 P

O3 M

L-

S+

FE

I0

I1

T0

T1

I2

I3

T2

T3M

PS1, PS2: User 24V DC Power Supply (A single power supply can be used for both input and output power.) K1 k2

Only 1732ES-IB12XOBV2 Module K2

PS2

K1

PS1

1 - Output Power 2 - Input Power 3 - Input Common 4 - Output Common

K1 4

2

3

1

2

1

K2

5 3

4

M

1 - Out 24 V DC 2 - Out 1 3 - Out Common 4 - Out 0 5 - Out Common

2

1

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

5 3

4

K1 k2

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Safety Output 0

Safety Output 0 Channel Mode

Safety Pulse Test

Safety Output 1

Safety Output 1 Channel Mode

Safety Pulse Test

The example shows wiring and configuration when using the Guard I/O module with solid-state outputs in Dual-channel mode. Note that all safety outputs of this Guard I/O module are permanently configured for use as Dual-channel mode only. When used in combination with the programs of the safety controller, this circuit configuration is Safety Category 4 in accordance with ISO 13849-1:2008 wiring requirements. Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

67

Page 68

Chapter 4

Wiring Examples

Figure 30 - Dual-load Sourcing Outputs – Only 1732ES-IB12XOB4 Module Only 1732ES-IB12XOB4 Module PS2

PS1

1 - Output Power 2 - Input Power 3 - Input Common 4 - Output Common

K1 4

2

3

1

2

1 5

K2

K2 K1

4

3

1

2

M

1 - Test Output 1 2 - Input 1 3 - Input Common 4 - Input 0 5 - Test Output 0

5 3

4

PS1, PS2: User 24V DC Power Supply (A single power supply can be used for both input and output power.)

K1

1 - Out 24 V DC 2 - Out 1 3 - Out Common 4 - Out 0 5 - Out Common

K2

Controller Configuration

Parameter Name

Configuration Setting

Safety Input 0

Safety Input 0 Channel Mode

Test Pulse from Test Output

Safety Input 0 Test Source

Test Output 0

Dual-channel Safety Input 0/1 Mode

Single Channel

Test Output 0

Test Output 0 Mode

Pulse Test Output

Safety Output 0/1

Safety Output 0/1 Operation Type

Dual

Safety Output 0

Safety Output 0 Channel Mode

Safety Pulse Test

Safety Output 1

Safety Output 1 Channel Mode

Safety Pulse Test

The example shows wiring and configuration when using the 1732ESIB12XOB4 Guard I/O module with solid-state outputs in Dual-channel mode. When used in combination with the programs of the safety controller, this circuit configuration is Safety Category 4 in accordance with ISO 13849-1:2008 wiring requirements.

68

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 69

Chapter

5

Configure the I/O Modules by Using the Logix Designer Application

Topic

Page

Add Modules to the I/O Configuration Tree

69

Configure the Module Properties

71

Configure the Safety Connections

78

Configure the Module Inputs

80

Configure the Test Outputs

82

Configure the Module Outputs

83

Save and Download the Module Configuration

84

Use the Logix Designer application to configure the modules. At the bottom of a dialog box, choose Help for information about how to complete entries in the dialog box. At the bottom of a warning dialog box, choose Help to get information about that specific error.

Add Modules to the I/O Configuration Tree

To add a module to the I/O configuration tree, follow these guidelines. 1. From the I/O Configuration tree, right-click the Ethernet bridge module, as shown in the figure, and choose New Module.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

69

Page 70

Chapter 5

Configure the I/O Modules by Using the Logix Designer Application

The Select Module dialog box is displayed with a list that includes Safety.

2. From the Select Module dialog box, choose the + next to Safety to see a list of safety modules

A list of safety modules appears here.

3. From the Select Module dialog box, choose the appropriate module, such as 1791ES-IB16, and OK at the bottom of the dialog box.

70

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015