Page 71

Configure the I/O Modules by Using the Logix Designer Application

Configure the Module Properties

Chapter 5

Follow these steps to configure the general properties of the module. 1. From the I/O configuration tree, double-click the module, such as the 1791ES-IB8XOBV4 module, to see the Module Properties dialog box.

2. Type a unique name for the module. 3. If desired, type a description. Note the safety network number (SNN). In most cases you can use the default provided by the Logix Designer application. For a detailed explanation of the safety network number (SNN), see the GuardLogix Controller Systems Safety Reference Manual listed in the Additional Resources on page 9.

Set the IP Address in the Logix Designer Application If you are not using network address translation (NAT), type the IP address of the module in the IP Address field. If you are using NAT, follow these steps: 1. In the IP Address field, type the IP address that the controller will use. 2. Click Advanced to open the Advanced Ethernet Settings dialog box.

3. Check the checkbox to indicate that this module and the controller communicate through NAT devices.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

71

Page 72

Chapter 5

Configure the I/O Modules by Using the Logix Designer Application

4. Type the actual module address. If you configured the IP Address using the rotary switches, this is the address you set on the module. 5. Click OK. IMPORTANT

When NAT is used in a safety application with a GuardLogix controller, the module does not accept a safety connection unless the actual module address is provided.

Change the Module Definition Click Change to open the Module Definition dialog box, where you can select values to configure what data and status tags to generate implicitly for the safety module. See these sections for settings explanations: • Input Data Options on page 72 • Input Status Options on page 74 • Output Data Options on page 76 • Values and States of Tags on page 77

Input Data Options Choose from these options: • Safety - Selecting Safety creates these tags for the target module: – RunMode: Module mode – ConnectionFaulted: Communication status

72

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 73

Configure the I/O Modules by Using the Logix Designer Application

Chapter 5

– Safety Data: Safety inputs from module

• Safety-Readback - This selection is not available for input-only safety modules. Selecting Safety-Readback creates both safety and readback tags, with readback indicating the presence of 24V on the output terminal.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

73

Page 74

Chapter 5

Configure the I/O Modules by Using the Logix Designer Application

Input Status Options Choose from these options. IMPORTANT

Status data is not SIL 3 data. Do not use status data to directly control a SIL 3 safety output.

• None - No status tags, only data for the inputs • Point Status-Muting - A muting status tag for test output with muting output capability with point status for each input and output point

74

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 75

Configure the I/O Modules by Using the Logix Designer Application

Chapter 5

• Combined Status-Muting – A single BOOL tag represents an AND of the status bits for all the input points. For example, if any input channel has a fault, this bit goes LO.(1) – A single BOOL tag represents an AND of the status bits for all the output points.(1) – A muting status tag for test output T3/T7 (for 1791ES-IB8XOBV4 modules) T3/T7/T11/T15 (for 1791ES-IB16 modules), and T3/T7/T11 (for 1732ES modules). .

(1) When using combined status, use Explicit Messaging to read individual point status for diagnostic purposes.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

75

Page 76

Chapter 5

Configure the I/O Modules by Using the Logix Designer Application

Output Data Options Choose from these options. IMPORTANT

The standard outputs on the module must not be used for safety purposes.

• None - Selecting None results in an input only connection to the module. Inputs and status are read, but no outputs are written. • Safety - Selecting Safety creates the safety tags shown here and enables the safety outputs for use in the safety task.

• Test - Selecting Test creates these tags and enables the test outputs on the module. These outputs are standard outputs and must not be used for safety purposes.

• Combined - Selecting Combined creates these tags and enables all module outputs - safety and test.

76

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 77

Configure the I/O Modules by Using the Logix Designer Application

Chapter 5

Values and States of Tags This table shows the values and states of the tags. Table 21 - Values and States of Tags Data

Input data

Output data

Description Run Mode STANDARD

Indicates whether consumed data is actively being updated by a device that is in one of these states. • Run mode: 1 • Idle State: 0

Connection Faulted STANDARD

Indicates the validity of the safety connection between the safety producer and the safety consumer. • Valid: 0 • Faulted: 1

Safety Input Data SAFETY

Indicates the ON/OFF status of each input circuit. • ON: 1 • OFF: 0

Combined Safety Input Status SAFETY

An AND of the status of all input circuits. • All circuits are normal: 1 • An error was detected in one or more input circuits: 0

Individual Safety Input Status SAFETY

Indicates the status of each input circuit. • Normal: 1 • Fault (Alarm): 0

Combined Safety Output Status SAFETY

An AND of the status of all safety output circuits. • All circuits are normal: 1 • An error has been detected in one or more output circuits: 0

Individual Safety Output Status SAFETY

Indicates the status of each safety output circuit. • Normal: 1 • Fault (Alarm): 0

Muting Lamp Status SAFETY

Indicates the status when a test output is configured as a muting lamp output. • Normal: 1 • Fault (Alarm): 0

Safety Output Monitor STANDARD

Monitors the outputs of the safety output circuits. • ON: 1 • OFF: 0

Individual Test Output Status STANDARD

Indicates the status of each of the test output circuits. • Normal: 1 • Fault (Alarm): 0

Input Power Error Bit STANDARD

Indicates if the field power supplied is within specification. • Power error: 1 • Power OK: 0

Output Power Error Bit STANDARD

Indicates if the field power supplied is within specification. • Power error: 1 • Power OK: 0

Safety Output Data SAFETY

Controls the safety output. • ON: 1 • OFF: 0

Standard Output Data STANDARD

Controls the test output when test output mode is set to a standard output. • ON: 1 • OFF: 0

IMPORTANT

Safety denotes information the controller can use in safety-related functions. Standard denotes additional information that must not be relied on for safety functions.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

77

Page 78

Chapter 5

Configure the I/O Modules by Using the Logix Designer Application

Configure the Safety Connections

Follow these steps to complete entries when you choose the Safety tab. 1. From the Module Properties dialog box, choose the Safety tab to see the Safety dialog box.

2. Click Advanced to configure Requested Packet Interval (RPI) and Configure Connection Reaction Time Limit (CRTL). We suggest that you keep the Timeout Multiplier and Network Delay Multiplier at their default values of 2 and 200. See GuardLogix Controllers User Manual, listed in the Additional Resources on page 9, for more information about the CRTL.

Make sure that input RPI is set to match the need. The smallest input RPI allowed is 6 ms. Selecting small RPI's consumes network bandwidth and can cause nuisance trips because other devices can't get access to the network.

As an example, a safety input module with only E-stop switches connected to it generally can work well with settings of 50…100 ms. An input module with a light curtain guarding a hazard can need the fastest response that is possible.

78

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 79

Configure the I/O Modules by Using the Logix Designer Application

Chapter 5

Selecting appropriate RPI's will result in a system with maximum (best) performance.

IMPORTANT

Analyze each safety channel to determine what is appropriate. The default timeout multiplier of 2 and network delay multiplier of 200 will create an input connection reaction time limit of four times the RPI and an output connection reaction limit of three times the RPI. Changes to these parameters must be approved by a safety administrator.

A connection status tag exists for every connection. Connection Faulted

If the RPI and CRTL for the network are set appropriately, then this status tag must always remain LO. Monitor all connection status bits to verify that they are not going HI intermittently due to timeouts.

Configuration Ownership – Reset Ownership The connection between the owner and the Guard I/O module is based on the following items: • Guard I/O EtherNet/IP address • Guard I/O safety network number • GuardLogix slot number • GuardLogix safety network number • Path from GuardLogix controller to Guard I/O module • Configuration signature If any of these items change, the connection between the GuardLogix controller and the Guard I/O module is lost, and the yellow yield in the project tree appears. Reset ownership to re-establish the connection by using this procedure. 1. Open the safety I/O module properties. 2. Choose the Safety tab. 3. From the dialog box, choose Reset ownership. Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

79

Page 80

Chapter 5

Configure the I/O Modules by Using the Logix Designer Application

Configuration Signature The configuration signature is created by the Logix Designer application and verified by the safety module. The configuration signature provides SIL 3 integrity of the configuration of a Guard I/O module. • When a GuardLogix controller first connects to an unconfigured Guard I/O module, the complete configuration is downloaded to the I/O module. • Any time the GuardLogix controller attempts to connect to a Guard I/O module, if the configuration signatures are the same, then the configuration does not need to be downloaded, because they already match. • Any time the GuardLogix controller attempts to connect to a Guard I/O module and the signatures do not match, the module checks the IP address and safety network number. If these are all correct, the controller will attempt to configure the module.

Configure the Module Inputs

Table 22 shows the typical safety input parameters available on the Input Configuration tab. See Chapter 2 for related information.

Table 22 - Typical Safety Input Parameters Parameter Name

Input Point Operation Type

Value

Description

Single Channel

Inputs are treated as single channel.

Dual-channel Equivalent

Inputs are treated as a dual-channel pair. The channels must match (be equal) within the discrepancy time or a fault is generated.

Dual-channel Complementary

Inputs are treated as a dual-channel pair. The channels must disagree (be opposite) within the discrepancy time or a fault is generated.

Not Used

The input is disabled. It remains logic 0 if 24V is applied to the input terminal.

Safety Test Pulse

Pulse testing is performed on this input circuit. A test source on the module must be used as the 24V source for this circuit. The test source is configured by using the test source pull-down. The pulse test detects shorts to 24V, and channel-to-channel shorts to other inputs.

Safety

A safety input is connected but there is no requirement for the 1791ES module to perform a pulse test on this circuit. An example is a safety device that performs its own pulse tests on the input wires, such as a light curtain.

Standard

A standard device, such as a reset switch, is connected. This point cannot be used in dual channel operation.

Input Point Mode

None Test Output 0 Safety Input Test Source

If pulse testing is being performed on an input point, then the test source that is sourcing the 24V for the input circuit must be selected. If the incorrect test source is entered, the result is pulse test failures on that input circuit.

Test Output 1 Test Output 2 Test Output 3 Test Output 4…15(1)

Input Delay Time Off -> On

0…126 ms (in increments of 6 ms)

Filter time is for OFF to ON transition. Input must be high after input delay has elapsed before it is set logic 1.

Input Delay Time On -> Off

0…126 ms (in increments of 6 ms)

Filter time is ON to OFF transition. Input must be low after input delay has elapsed before it is set logic 0.

Safety Input Error Latch Time

0…65,530 ms (in increments of 10 ms)

Default is 1000 ms. The purpose for latching input errors is to make sure that intermittent faults that can only exist for a few milliseconds are latched long enough to be read by the controller. The amount of time to latch the error must be based on the RPI, the safety task watchdog, and other application-specific variables.

(1) There are eight test outputs on 1791ES-IB8XOBV4 modules, sixteen test outputs on 1791ES-IB16 modules, and twelve test outputs on 1732ES modules.

80

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015