Configure the I/O Modules by Using the Logix Designer Application

Chapter 5

Follow these steps to configure the module inputs. 1. Click the Input Configuration tab.

2. For Point Operation Type, choose one of these values and a value for Discrepancy Time if set to Equivalent or Complementary: • Single Inputs are treated as single channels. Note that in many cases, dualchannel safety inputs are configured as two individual single channels. This does not affect pulse testing because it is handled on an individual channel basis. • Equivalent(1) Inputs are treated as a dual-channel pair. The channels must match within the discrepancy time or an error is generated. • Complementary(1) Inputs are treated as a dual-channel pair. They must be in opposite states within the discrepancy time or an error is generated. 3. For Point Mode, choose one of these values for each point, referring to the Safety Input Parameters table for additional information: • Not Used - Safety input channel is disabled • Safety Pulse Test - Safety input is configured for pulse test operation • Safety - The safety input is used with a safety field device • Standard - Safety input has a standard field device wired to it

(1) Be aware that configuring discrepancy time on safety I/O modules masks input inconsistent faults from the GuardLogix safety instructions. Status can be read by GuardLogix to obtain this fault information.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

81

Page 82

Chapter 5

Configure the I/O Modules by Using the Logix Designer Application

4. Complete entries, noting the following: • For each safety input on the module, you can define if the input will be pulse tested. If the inputs are pulse tested, select which test source to use. • Off -> On and On -> Off delay times can be configured per channel with each channel specifically tuned to match the characteristics of the field device for maximum performance. • Input Error Latch Time is the time the module holds an error to make sure the controller can detect it. This provides you more reliable diagnostics and enhances the chances that a nuisance error is detected. 5. Click OK at the bottom of the dialog box or a tab at the top of the dialog box.

Configure the Test Outputs

Table 23 provides information for configuring the test outputs.

Table 23 - Configuring Test Outputs Parameter Name

Test Output Mode

Value

Description

Not Used

The test output is disabled.

Standard

The output point is enabled for use by the GuardLogix controller.

Pulse Test

The test output is being used as a pulse test source.

Power Supply

A constant 24V is placed on the output terminal. It can be used to provide power to a field device.

Muting Lamp Output (1)

An indicator lamp is connected to the output. When this lamp is energized, a burned-out bulb, broken wire, or short to GND error condition can be detected. Typically, the lamp is an indicator used in light curtain applications.

Default

Not Used

(1) Terminal T3/T7 for 1791ES-IB8XOBV4 modules, terminal T3/T7/T11/T15 for 1791ES-IB16 modules, and terminal T3/T7/T11 for 1732ES modules.

Follow these steps to configure the test outputs. 1. Click the Test Outputs tab.

2. From the Port Mode pull-down menus, select the desired configuration option for each point. 82

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 83

Configure the I/O Modules by Using the Logix Designer Application

Configure the Module Outputs

Chapter 5

Table 24 provides information for configuring the test outputs.

Table 24 - Guidelines for Configuring Safety Outputs Parameter Name

Value

Default

Single

The 1791ES modules and the 1732ES-IB12XOBV2 module treat the outputs as a pair. It always sets them HI to LO as a matched pair. Safety logic must set both of these outputs ON or OFF at the same time or the module will declare a channel fault. Dual-channel The 1732ES-IB12XOB4 module can be configured with the outputs treated as single channels. Both channels of an output pair are set to either Single or Dual.(1)

Not Used

The output is disabled.

Safety

The output point is enabled, and it does not perform a pulse test on the output.

Safety Pulse Test

The output point is enabled and performs a pulse test on the output. When the output is energized, the output pulses LO briefly. The pulse test detects if 24V remains on the output terminal during this LO pulse due to a short to 24V or if the output is shorted to another output terminal.

Dual Point Operation Type

Point Mode

Output Error Latch Time

Description

Not Used

The purpose for latching output errors is to make sure that intermittent faults that can only exist for a few 0…65,530 ms (in are latched long enough to be read by the controller. The amount of time to latch the errors is based 1000 ms increments of 10 ms) milliseconds on the RPI, the safety task watchdog, and other application-specific variables.

(1) Safety outputs configured for single-channel operation must be controlled as pairs for use in functional safety applications.

Follow these steps to configure the module outputs. 1. For Point Operation, all safety outputs must be controlled as pairs for use in functional safety applications(1). .

2. For Point Mode, select Not Used, Safety, or Safety Pulse Test, referring to the Safety Output Parameters table for additional information. 3. Select a value for Output Error Latch Time. Output Error Latch Time is the time the module holds an error to make sure the controller can detect it. This provides you more reliable diagnostics and enhances the changes that a nuisance error is detected. 4. Click Apply from the bottom of the dialog box.

(1) Safety outputs on the 1732ES-IB12XOBV4 module can be set to single channel operation mode but then must be controlled as pairs to be used in functional safety applications. Use of safety outputs on 1791ES-IB8XOBV4 and 1732ES-IB12XOBV2 modules in functional safety applications requires the channel operation mode be set to Dual and the safety outputs be matched as pairs in software (always set high or low as a pair) in those applications.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

83

Page 84

Chapter 5

Configure the I/O Modules by Using the Logix Designer Application

Save and Download the Module Configuration

We recommend that after a module is configured you save your work. If after downloading the program the MS and NS indicators on the Guard I/O module are not both solid green, this can be due to loss of ownership. The ownership is based on the following items: • Guard I/O EtherNet/IP address • Guard I/O safety network number • GuardLogix slot number • GuardLogix safety network number • Path from GuardLogix controller to Guard I/O module • Configuration signature If any of these items change, the connection between the GuardLogix controller and the Guard I/O module is lost, and the yellow yield in the project tree appears. Reset ownership to re-establish the connection by using this procedure. 1. Open the safety I/O module properties. 2. Choose the Safety tab. 3. From the dialog box, choose Reset ownership.

84

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 85

Chapter

6

Interpret the Module Status Indicators

Topic

Page

1791ES Module Status Indicators

85

1732ES Module Status Indicators

87

See Figure 23 and Table 25…Table 32 for information on the 1791ES module indicators.

1791ES Module Status Indicators

Figure 23 - 179ES1 Module Status Indicators 24V DC Input Power Indicator

24V DC Output Power Indicator (only 1791ES-IB8XOBV4 modules) Module Status Indicator

Network Activity Indicator

Configuration Lock Indicator Network Status Indicator

I0…I15 - Safety Input Status Indicator T0…T15 - Test Output Status Indicator 00…07 - Safety Output Status Indicator (only 1791ES-IB8XOBV4 module)

Table 25 - 24V DC Input Power Indicator State Off Solid green Solid yellow

Status No power Normal operation Input power out of specification

Description No power is applied. The applied voltage is within specifications. The input power is out of specification.

Recommended Action Apply power to this section. None. Check your connectors, wiring, and voltages.

Description No power is applied. The applied voltage is within specifications. The output power is out of specification.

Recommended Action Apply power to this section. None. Check your connectors, wiring, and voltages.

Table 26 - 24V DC Output Power Indicator State Off Solid green Solid yellow

Status No power Normal operation Output power out of specification

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

85

Page 86

Chapter 6

Interpret the Module Status Indicators

Table 27 - Module Status Indicator State Off Solid green

Status No power Normal operation

Description No power is applied to the power connector. The module is operating normally.

Solid red

Unrecoverable fault

The module detected an unrecoverable fault.

Module is unconfigured

Module needs commissioning due to missing, incomplete, or incorrect configuration.

Device in self-test

The module is performing its power-cycle diagnostic tests.

Flashing red and green

Flashing green Idle Recoverable fault Flashing red User-initiated firmware update in progress

Idle, waiting for connection from scanner. The module has detected a recoverable fault. User-initiated firmware update is in progress.

Recommended Action Apply power to this connector. None. Cycle power to the module. If problem persists, replace the module. Reconfigure the module. For additional information, inspect Network Status indicator. Wait for the module to complete its power-cycle diagnostics. Establish connection. Cycle power to the module or reset the module. Wait for firmware update to complete.

Table 28 - Network Status Indicator State Off

Status Module not online online with no connections in Flashing green Module established state Module online with connections in Solid green established state One or more I/O connections in timed-out Flashing red state User-initiated firmware update Solid red

Critical link failure

Flashing red and green

Self-test

Description The module does not have an IP address.

Recommended Action Verify your network is working properly. your network and module The module has acquired an IP address, but no connections are established. Verify configuration. The module is operating normally.

None.

Verify your network and module configuration. User-initiated firmware update is in progress. Wait for firmware update to complete. The module detected an error that prevents it from communicating on the Cycle power to the module. Check network network, such as duplicate IP address has been detected. IP addressing. Wait for the module to complete its The module is performing its power-cycle diagnostic test. power-cycle diagnostics. The module detected a recoverable network fault.

Table 29 - Network Activity Indicator State Off Flashing Green Steady Green

Status No link is established. Transmit or receive activity. Link is established

Recommended Action Establish link. None. None.

Table 30 - Safety Input Status Indicator State

Status

Description

Off

Safety input off

The safety input is off or the channel is configured for not used.

Solid yellow

Safety input on

The safety input is on.

Solid red

Fault detected

A fault in the external wiring or input circuit detected.

Flashing red

Partner fault detected

A fault in the partner input circuit of a dual-input configuration detected.

86

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Recommended Action Turn the safety input on or reconfigure the channel, if desired. None. Check configuration, field wiring, and devices. If no problem found, replace module. Check the field wiring and verify your configuration for the partner circuit. If no problem found, replace module.

Page 87

Interpret the Module Status Indicators

Chapter 6

Table 31 - Test Output Status Indicator State

Status

Description

Off

Test output off

The test output is off or the channel is configured for not used.

Solid yellow

Output on

Output is on.

Solid red

Fault detected

A fault in the external wiring or input circuit detected.

Recommended Action Turn the test output on or reconfigure the channel, if desired. None. Check field wiring. If no problem found, replace module. For outputs configured for muting could indicate undercurrent or burned-out lamp.

Table 32 - Safety Output Status Indicator (only 1791ES-IB8XOBV4 modules) State Off

Status

Solid yellow

Safety output on

Solid red

Fault detected

Flashing red

Partner fault detected

Safety output off

1732ES Module Status Indicators

Description

Recommended Action the safety output on or reconfigure the channel, if The safety output is off or the channel is configured for not used. Turn desired. The safety output is on. None. Check the circuit wiring and end device. If no problem A fault in the output circuit was detected. found, replace module. Make sure logic is driving tag values to the same state (off Both tags in a dual channel circuit do not have the same value. or on). A fault in the partner output circuit of a dual output configuration Check the circuit wiring and end device of the partner. If was detected. no problem found, replace module.

See Figure 31 and Table 33…Table 39 for information on the 1732ES module status indicators. Figure 31 - 1732ES Module Status Indicators 24V DC Input Power Indicator

24V DC Output Power Indicator

Module Status Indicator

Safety Inputs 0…7 Status Indicators

Safety Outputs 0…3 Status Indicators

Safety Inputs 8…11 Status Indicators

Network Status Indicator

Network Link 1 Activity Indicator

Network Link 2 Activity Indicator

Table 33 - 24V DC Input Power Indicator State Off Solid green Solid yellow

Status No power Normal operation Input power out of specification

Description No input power or severe input power overvoltage. The applied voltage is within specifications. The input power is out of specification.

Recommended Action Apply power that is within specifications to this section. None. Check your connectors, wiring, and voltages.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

87

Page 88

Chapter 6

Interpret the Module Status Indicators

Table 34 - 24V DC Output Power Indicator State Off Solid green Solid yellow

Status No power Normal operation Output power out of specification

Description No output power or severe output power overvoltage. The applied voltage is within specifications. The output power is out of specification.

Recommended Action Apply power that is within specifications to this section. None. Check your connectors, wiring, and voltages.

Table 35 - Module Status Indicator State

Status

Off

No power

Solid green

Normal operation

Solid red

Unrecoverable fault

Flashing red and Module is unconfigured green Device in self-test Flashing green Idle Recoverable fault Flashing red User-initiated firmware update in progress

Description Recommended Action No power is applied to the input power connector or severe Apply input power that is within specification to the module. input power overvoltage. The module is operating normally. None. Cycle power to the module. If problem persists, replace the The module detected an unrecoverable fault. module. Module needs commissioning due to missing, incomplete, or Reconfigure the module. For additional information, inspect incorrect configuration. Network Status indicator. The module is performing its power-cycle diagnostic tests. Wait for the module to complete its power-cycle diagnostics. Idle, waiting for connection from scanner. Establish connection. The module has detected a recoverable fault. Cycle power to the module or reset the module. User-initiated firmware update is in progress.

Wait for firmware update to complete.

Table 36 - Network Status Indicator State Off

Status Module not online Module online with no connections in Flashing green established state Module online with connections in Solid green established state One or more I/O connections in timedout state Flashing red User-initiated firmware update Solid red

Critical link failure

Self-test Flashing red and green Waiting for TUNID

Description Recommended Action The module does not have an IP address. Verify your network is working properly. The module has acquired an IP address, but no connections Verify your network and module configuration. are established. The module is operating normally.

None.

The module detected a recoverable network fault.

Verify your network and module configuration.

User-initiated firmware update is in progress. Wait for firmware update to complete. The module detected an error that prevents it from communicating on the network, such as duplicate IP Cycle power to the module. Check network IP addressing. address has been detected. The module is performing its power-cycle diagnostic test. Wait for the module to complete its power-cycle diagnostics. The module has received the proposed UNID and is waiting None. for the TUNID.

Table 37 - Network Activity Indicators (link 1 and link2) State Off Flashing Green Steady Green

88

Status No link is established. Transmit or receive activity. Link is established

Recommended Action Establish link. None. None.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 89

Interpret the Module Status Indicators

Chapter 6

Table 38 - Safety Input Status Indicator State

Status

Description

Off

Safety input off

The safety input is off or the channel is configured for not used.

Solid yellow

Safety input on

The safety input is on.

Solid red

Fault detected

A fault in the external wiring or input circuit detected.

Flashing red

Partner fault detected

A fault in the partner input circuit of a dual-input configuration detected.

Recommended Action Turn the safety input on or reconfigure the channel, if desired. None. Check configuration, field wiring, and devices. If no problem found, replace module. Check the field wiring and verify your configuration for the partner circuit. If no problem found, replace module.

Table 39 - Safety Output Status Indicator State Off

Status

Description

A fault in the partner output circuit of a dual output configuration was detected.

Recommended Action Turn the safety output on or reconfigure the channel, if desired. None. Check the circuit wiring and end device. If no problem found, replace module. Make sure logic is driving tag values to the same state (off or on). Check the circuit wiring and end device of the partner. If no problem found, replace module.

Safety output off

The safety output is off or the channel is configured for not used.

Solid yellow

Safety output on

The safety output is on.

Solid red

Fault detected

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

89

A fault in the output circuit was detected. Both tags in a dual channel circuit do not have the same value. Flashing red

Partner fault detected

Page 90

Chapter 6

Interpret the Module Status Indicators

Notes:

90

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015