Page 91

Appendix

A

Get Diagnostic Status from Modules by Using Explicit Messaging

Topic

Page

Get Status Messages from 1791ES-IB8XOBV4 Modules

92

Get Status Messages from 1791ES-IB16 Modules

97

Get Status Messages from 1732ES Modules

102

I/O Data Supported by Each Module

106

I/O Assembly and Reference Data

109

Explicit Messages

115

This appendix provides information about how to use CIP Generic Message instructions (sometimes called Explicit Messaging) to get diagnostic status information from the modules. You can implicitly obtain individual point status of the Guard I/O module from the Module Definition dialog box by choosing Pt. Status from the Input Status pull-down menu.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

91

Page 92

Appendix A

Get Diagnostic Status from Modules by Using Explicit Messaging

Another choice is to obtain overall status implicitly from the Module Definition dialog box by choosing Combined Status from the Input Status pull-down menu.

If the Combined Status changes, use Explicit Messaging to obtain the point level status.

Get Status Messages from 1791ES-IB8XOBV4 Modules

92

Follow these steps to get status messages from 1791ES-IB8XOBV4 modules. 1. In the Module Definition dialog box, from the Input Status pull-down menu, choose Combined Status.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 93

Get Diagnostic Status from Modules by Using Explicit Messaging

Appendix A

This creates a two-byte input assembly, as shown for the 1791ESIB8XOBV4 module.

2. Use the CombinedInputStatus and CombinedOutputStatus bits to detect if one or more of the I/O points on the module have a fault. • If any input or output status bit goes to a value of 0 (0=error, 1=no error), use the CombinedInputStatus and CombinedOutputStatus bits to condition your MSG rungs as follows. • Note that the second rung can be used to read the status on mode transition and once a fault is detected, continue reading until the fault is corrected. • Place these rungs in the standard task.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

93

Page 94

Appendix A

Get Diagnostic Status from Modules by Using Explicit Messaging

Reference the figures below that show the MSG instruction parameters for reading Instance 852 from the 1791ES-IB8XOBV4 module.

Instance 852 (354 hex) is 5 bytes in length, so the destination tag MSGdata must be at least 5 bytes in length to hold this data. The size is DINT[2] or 8 bytes (see Table 40). Table 40 - Layout of Instance 852 (354 hex) – 1791ES- IB8XOBV4 Module Instance Hex (decimal)

354 (852)

Connection Type

Safety and standard

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Safety Input 7

Safety Input 6

Safety Input 5

Safety Input 4

Safety Input 3

Safety Input 2

Safety Input 1

Safety Input 0

1

Safety Input 7 Status

Safety Input 6 Status

Safety Input 5 Status

Safety Input 4 Status

Safety Input 3 Status

Safety Input 2 Status

Safety Input 1 Status

Safety Input 0 Status

2

Safety Output 7 Status

Safety Output 6 Status

Safety Output 5 Status

Safety Output 4 Status

Safety Output 3 Status

Safety Output 2 Status

Safety Output 1 Status

Safety Output 0 Status

3

Safety Output 7 Monitor

Safety Output 6 Monitor

Safety Output 5 Monitor

Safety Output 4 Monitor

Safety Output 3 Monitor

Safety Output 2 Monitor

Safety Output 1 Monitor

Safety Output 0 Monitor

4

Reserved

Reserved

Input Power Error (1)

Output Power Error (1)

Reserved

Reserved

Muting Lamp 7 Status

Muting Lamp 3 Status

(1) This data is only diagnostic data. This data does not have safety integrity.

94

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 95

Get Diagnostic Status from Modules by Using Explicit Messaging

Appendix A

Click the Communication tab. This dialog box requires the path to the module. Click Browse to select the module that the MSG will read.

From the top of the Message Configuration dialog box, choose Tag to see this dialog box.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

95

Page 96

Appendix A

Get Diagnostic Status from Modules by Using Explicit Messaging

When the explicit message reads the data from the 1791ES-IB8XOBV4 module, the data appears in the MSGdata tags as shown.

The first 32 bits of the instance are in MSGdata[0].0…31, and the final 8 bits are in MSGdata[1].0…7. These 40 bits must be mapped according to Instance 852. An easy method to do this mapping is to create a user-defined tag (UDT) for Instance 852. Once complete, it appears as follows.

96

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 97

Get Diagnostic Status from Modules by Using Explicit Messaging

Get Status Messages from 1791ES-IB16 Modules

Appendix A

Follow these steps to get status messages from 1791ES-IB16 modules. 1. In the Module Definition dialog box, from the Input Status pull-down menu, choose Combined Status.

This creates a three-byte input assembly, as shown, for the 1791ES-IB16 module.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

97

Page 98

Appendix A

Get Diagnostic Status from Modules by Using Explicit Messaging

2. Use the CombinedInputStatus bit to detect if one or more of the I/O points on the module have a fault. • If any input status bits go to a value of 0 (0 = bad; 1 = good), use an explicit message to determine which individual data points have faulted. • Note that you can use the second rung to read the status on mode transition and once a fault is detected, continue reading until the fault is corrected. • Place these rungs in the standard task.

See the figures that show the MSG instruction parameters for reading Instance 869 from the 1791ES-IB16 module. See Appendix C of this manual for a layout of possible instances.

98

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 99

Get Diagnostic Status from Modules by Using Explicit Messaging

Appendix A

Instance 869 (365 hex) is 7 bytes in length, so the destination tag IB16MSGdata must be at least 7 bytes in length to hold this data. The size is DINT[2] or 8 bytes (see Table 41). Table 41 - Layout of Instance 869 (365 hex) – 1791ES-IB16 Module Instance Hex (decimal)

365 (869)

Connection Type

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Safety Input 7

Safety Input 6

Safety Input 5

Safety Input 4

Safety Input 3

Safety Input 2

Safety Input 1

Safety Input 0

1

Safety Input 15

Safety Input 14

Safety Input 13

Safety Input 12

Safety Input 11

Safety Input 10

Safety Input 9

Safety Input 8

2

Safety Input 7 Status

Safety Input 6 Status

Safety Input 5 Status

Safety Input 4 Status

Safety Input 3 Status

Safety Input 2 Status

Safety Input 1 Status

Safety Input 0 Status

3

Safety Input 15 Status

Safety Input 14 Status

Safety Input 13 Status

Safety Input 12 Status

Safety Input 11 Status

Safety Input 10 Status

Safety Input 9 Status

Safety Input 8 Status

4

Test Output 7 Status

Test Output 6 Status

Test Output 5 Status

Test Output 4 Status

Test Output 3 Status

Test Output 2 Status

Test Output 1 Status

Test Output 0 Status

5

Test Output 15 Status

Test Output 14 Status

Test Output 13 Status

Test Output 12 Status

Test Output 11 Status

Test Output 10 Status

Test Output 9 Status

Test Output 8 Status

6

Reserved

Reserved

Input Power Error (1)

Output Power Error (1)

Muting Lamp 15 Status

Muting Lamp 11 Status

Muting Lamp 7 Status

Muting Lamp 3 Status

Safety and standard

(1) This data is only diagnostic data. This data does not have safety integrity.

From the top of the Message Configuration dialog box, choose the Communication tab. This dialog box requires the path to the module. Click Browse to go to the module that the MSG will read.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

99

Page 100

Appendix A

Get Diagnostic Status from Modules by Using Explicit Messaging

From the top of the Message Configuration dialog box, click Tag to see this dialog box.

When the explicit message reads the data from the 1791ES-IB16 module, the data appears in the MSGdata tags as shown.

100

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015