The text of a manual · part 11 of 14
Guard I/O EtherNet/IP Safety Modules User Manual, pages 101 to 110
Pages 101 to 110 of 140
The original document is the PDF (7.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1791ES
Page 101
Get Diagnostic Status from Modules by Using Explicit Messaging
Appendix A
The first 32 bits of the instance are in IB16MSGdata[0].0…31, and the final 24 bits are in IB16MSGdata[1].0…23. Map these 56 bits according to Instance 869. An easy method to do this mapping is to create a userdefined tag (UDT) for Instance 869. Once you complete this, it appears as follows.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
101
Page 102
Appendix A
Get Diagnostic Status from Modules by Using Explicit Messaging
Get Status Messages from 1732ES Modules
Follow these steps to get status messages from 1732ES modules. TIP
The process is identical for the 1732ES-IB12XOBV2 and 1732ES-IB12XOB4 modules. Where necessary, the 1732ES-IB12XOBV2 module is used as the module reference name in tags.
1. In the Module Definition dialog box, from the Input Status pull-down menu, choose Combined Status.
This creates a three-byte input assembly, as shown, for the 1732ES modules.
102
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 103
Get Diagnostic Status from Modules by Using Explicit Messaging
Appendix A
2. Use the CombinedInputStatus and CombinedOutputStatus bits to detect if one or more of the I/O points on the module have a fault. • If any input or output status bits go to a value of 0 (0 = bad; 1 = good), use the CombinedInputStatus and CombinedOutputStatus bits to condition your MSG rungs as follows. Note that only use of the CombinedInputStatus bit is shown. Similar rungs should be created by using the CombinedOutputStatus bit instead of the CombinedInputStatus bit. • Note that the second rung can be used to read the status on mode transition and once a fault is detected, continue reading until the fault is corrected. • Place these rungs in the standard task.
See the figures that show the MSG instruction parameters for reading Instance 860 from the 1732ES module. See Appendix C of this manual for a layout of possible instances.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
103
Page 104
Appendix A
Get Diagnostic Status from Modules by Using Explicit Messaging
Instance 860 (35C hex) is 5 bytes in length, so the destination tag IB12XOBV2MSGdata must be at least 5 bytes in length to hold this data. The size is DINT[2] or 8 bytes (see Table 41). Table 42 - Layout of Instance 860 (35C hex) – 1732ES Modules Instance Hex (decimal)
35C (860)
Connection Type
Safety and standard
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
Safety Input 11
Safety Input 10
Safety Input 9
Safety Input 8
2
Safety Input 11 Status
Safety Input 10 Status
Safety Input 9 Status
Safety Input 8 Status
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
3
Safety Output 3 Monitor
Safety Output 2 Monitor
Safety Output 1 Monitor
Safety Output 0 Monitor
Safety Output 3 Status
Safety Output 2 Status
Safety Output 1 Status
Safety Output 0 Status
4
Reserved
Reserved
Input Power Error(1)
Output Power Error(1)
Reserved
Muting Lamp 11
Muting Lamp 7
Muting Lamp 3
(1) This data is only diagnostic data. This data does not have safety integrity.
From the top of the Message Configuration dialog box, choose the Communication tab. This dialog box requires the path to the module. Click Browse to go to the module that the MSG will read.
104
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 105
Get Diagnostic Status from Modules by Using Explicit Messaging
Appendix A
From the top of the Message Configuration dialog box, click Tag to see this dialog box.
When the explicit message reads the data from the 1732ES modules, the data appears in the MSGdata tags as shown.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
105
Page 106
Appendix A
Get Diagnostic Status from Modules by Using Explicit Messaging
The first 32 bits of the instance are in IB12XOBV2MSGdata[0].0…31, and the final 8 bits are in IB12XOBV2MSGdata[1].0…7. Map these 40 bits according to Instance 860. An easy method to do this mapping is to create a user-defined tag (UDT) for Instance 860. Once you complete this, it appears as follows.
I/O Data Supported by Each Module
Table 43 shows a summary of default I/O data by module. Table 43 - Default I/O Data Module Cat. No.
Safety Connection
Assembly Instance (hex)
1791ES-IB16
Safety
225 and 23
1791ES-IB8XOBV4
Safety
204 and 234
1732ES-IB12XOBV2
Safety
20C and 233
1732ES-IB12XOB4
Safety
20C and 233
The tables show the I/O data supported by each module. See I/O Assembly and Reference Data on page 109 for data arrangements. For I/O data, safety connections for up to four items, including one output, can be allocated for the master unit. Also, standard connections for up to two items can be allocated for the master unit.
106
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 107
Get Diagnostic Status from Modules by Using Explicit Messaging
Appendix A
Table 44 - 1791ES-IB8XOBV4 Modules Input Data
Safety
Safety - Readback
Input Status
Assembly Instance
None
204(1)
Point Status - Muting
334
Combined Status - Muting
324
Point Status - Muting
354
Point Status - Muting - Test Output
374
Output Data
Assembly Instance
Safety
234(1)
Test
–
Combined None
22 2C4 C7
(1) The default Assembly Instance.
Table 45 - 1791ES-IB16 Modules Input Data
Safety
Input Status
Assembly Instance
None
205
Point Status - Muting
335
Point Status - Muting - Test Output
365
Combined Status - Muting
315
Point Status
225(1)
Output Data
Assembly Instance
Test
23(1)
–
None
C7
(1) The default Assembly Instance.
Table 46 - 1732ES-IB12XOBV2 Input Data
Safety
Safety - Readback
Input Status
Assembly Instance
None
20C(1)
Point Status - Muting
34C
Combined Status - Muting
32C
Point Status - Muting
35C
Point Status - Muting - Test Output
37C
Output Data
Assembly Instance
Safety
233 (1)
Test Combined
–
None
25 3C4 C8
(1) The default Assembly Instance.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
107
Page 108
Appendix A
Get Diagnostic Status from Modules by Using Explicit Messaging
Table 47 - 1732ES-IB12XOBV2 Input Data
Safety
Safety - Readback
Input Status
Assembly Instance
None
20C(1)
Point Status - Muting
34C
Combined Status - Muting
32C
Point Status - Muting
35C
Point Status - Muting - Test Output
37C
Output Data
Assembly Instance
Safety
233 (1)
Test Combined
–
None (1) The default Assembly Instance.
108
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
25 3C4 C8
Page 109
Get Diagnostic Status from Modules by Using Explicit Messaging
Appendix A
This section provides information for I/O assembly and reference data.
I/O Assembly and Reference Data
1791ES Modules The bits in the tag definitions of the Logix Designer application are different than those shown in the following section. The following defines the name associations for clarification with the programming software. Table 48 - Bit Definitions and Logix Designer Tag Names Bit Definitions
Logix Designer Application Tag Name
Safety Input 0
Pt00Data
Safety Input 15
Pt15Data
Safety Input 0 Status
Pt00InputStatus
Safety Input 15 Status
Pt15InputStatus
Safety In Status
InputStatus
Muting Lamp Status
MutingStatus
Safety Output 0
Pt00Data
Safety Output 7
Pt07Data
Standard Output 0
Test00Data
Standard Output 15
Test15Data
Safety Output 0 Status
Pt00OutputStatus
Safety Output 7 Status
Pt07OutputStatus
Safety Out Status
OutputStatus
Safety Output 0 Monitor
Pt00Readback
Safety Output 7 Monitor
Pt07Readback
Test Output 0 Status
Pt00TestOutputStatus
Test Output 15 Status
Pt15TestOutputStatus
See these tables for reference data concerning input and output data.
Table 49 - Input Data – 1791ES- IB8XOBV4 Modules Instance Hex (decimal)
Connection Type
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
204 (516)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
224 (548)
Safety and standard
1
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
301 (769)
Only standard
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Output Power Error (1)
Input Power Error
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
324 (804)
Safety and standard
Combined Safety In Status
Combined Safety Out Status
Input Power Error (1)
Output Power Error (1)
Reserved
Reserved
Muting Lamp 7 Status
Muting Lamp 3 Status
1
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
109
Page 110
Appendix A
Get Diagnostic Status from Modules by Using Explicit Messaging
Table 49 - Input Data – 1791ES- IB8XOBV4 Modules (Continued) Instance Hex (decimal)
334 (820)
344 (836)
354 (852)
364 (868)
374 (884)
394 (916)
3A4 (932)
Connection Type
Safety and standard
Safety and standard
Safety and standard
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
2
Reserved
Reserved
Input Power Error (1)
Output Power Error (1)
Reserved
Reserved
Muting Lamp 7 Status
Muting Lamp 3 Status
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
2
Safety Output 7 Status
Safety Output 6 Status
Safety Output 5 Status
Safety Output 4 Status
Safety Output 3 Status
Safety Output 2 Status
Safety Output 1 Status
Safety Output 0 Status
3
Reserved
Reserved
Input Power Error (1)
Output Power Error (1)
Reserved
Reserved
Muting Lamp 7 Status
Muting Lamp 3 Status
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
2
Safety Output 7 Status
Safety Output 6 Status
Safety Output 5 Status
Safety Output 4 Status
Safety Output 3 Status
Safety Output 2 Status
Safety Output 1 Status
Safety Output 0 Status
3
Safety Output 7 Monitor
Safety Output 6 Monitor
Safety Output 5 Monitor
Safety Output 4 Monitor
Safety Output 3 Monitor
Safety Output 2 Monitor
Safety Output 1 Monitor
Safety Output 0 Monitor
4
Reserved
Reserved
Input Power Error (1)
Output Power Error (1)
Reserved
Reserved
Muting Lamp 7 Status
Muting Lamp 3 Status
0
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
1
Safety Output 7 Status
Safety Output 6 Status
Safety Output 5 Status
Safety Output 4 Status
Safety Output 3 Status
Safety Output 2 Status
Safety Output 1 Status
Safety Output 0 Status
2
Test Output 7 Status
Test Output 6 Status
Test Output 5 Status
Test Output 4 Status
Test Output 3 Status
Test Output 2 Status
Test Output 1 Status
Test Output 0 Status
3
Reserved
Reserved
Input Power Error (1)
Output Power Error (1)
Reserved
Reserved
Muting Lamp 7 Status
Muting Lamp 3 Status
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
2
Safety Output 7 Status
Safety Output 6 Status
Safety Output 5 Status
Safety Output 4 Status
Safety Output 3 Status
Safety Output 2 Status
Safety Output 1 Status
Safety Output 0 Status
3
Safety Output 7 Monitor
Safety Output 6 Monitor
Safety Output 5 Monitor
Safety Output 4 Monitor
Safety Output 3 Monitor
Safety Output 2 Monitor
Safety Output 1 Monitor
Safety Output 0 Monitor
4
Test Output 7 Status
Test Output 6 Status
Test Output 5 Status
Test Output 4 Status
Test Output 3 Status
Test Output 2 Status
Test Output 1 Status
Test Output 0 Status
5
Reserved
Reserved
Input Power Error (1)
Output Power Error (1)
Reserved
Reserved
Muting Lamp 7 Status
Muting Lamp 3 Status
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Output Power Error
Input Power Error
1
Test Output 7 Status
Test Output 6 Status
Test Output 5 Status
Test Output 4 Status
Test Output 3 Status
Test Output 2 Status
Test Output 1 Status
Test Output 0 Status
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Output Power Error
Input Power Error
1
Safety Output 7 Monitor
Safety Output 6 Monitor
Safety Output 5 Monitor
Safety Output 4 Monitor
Safety Output 3 Monitor
Safety Output 2 Monitor
Safety Output 1 Monitor
Safety Output 0 Monitor
2
Test Output 7 Status
Test Output 6 Status
Test Output 5 Status
Test Output 4 Status
Test Output 3 Status
Test Output 2 Status
Test Output 1 Status
Test Output 0 Status
Safety and standard
Safety and standard
Only standard
Only standard
(1) This data is only diagnostic data. This data does not have safety integrity.
110
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015