The text of a manual · part 12 of 14
Guard I/O EtherNet/IP Safety Modules User Manual, pages 111 to 120
Pages 111 to 120 of 140
The original document is the PDF (7.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1791ES
Page 111
Get Diagnostic Status from Modules by Using Explicit Messaging
Appendix A
Bit 4
Bit 0
Table 50 - Input Data – 1791ES-IB16 Modules Instance Hex (decimal)
Connection Type
Byte
Bit 7
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
205 (517)
1
Safety Input 15
Safety Input 14
Safety Input 13
0
Safety Input 7
Safety Input 6
Safety Input 5
1
Safety Input 15
Safety Input 14
2
Safety Input 7 Status
3
225 (549)
300 (768)
315 (789)
335 (821)
365 (869)
385 (901)
Safety and standard
Only standard
Safety and standard
Safety and standard
Safety and standard
Only standard
Bit 6
Bit 5
Bit 3
Bit 2
Bit 1
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
Safety Input 12
Safety Input 11 Safety Input 10
Safety Input 9
Safety Input 8
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
Safety Input 13
Safety Input 12
Safety Input 11 Safety Input 10
Safety Input 9
Safety Input 8
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
Safety Input 15 Status
Safety Input 14 Status
Safety Input 13 Status
Safety Input 12 Status
Safety Input 11 Status
Safety Input 10 Status
Safety Input 9 Status
Safety Input 8 Status
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Input Power Error
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 15 Status
Safety Input 14 Status
Safety Input 13 Status
Safety Input 12 Status
Safety Input 11 Status
Safety Input 10 Status
Safety Input 9 Status
Safety Input 8 Status
2
Combined Safety In Status
Reserved
Input Power Error (1)
Reserved
Muting Lamp 15 Status
Muting Lamp 11 Status
Muting Lamp 7 Status
Muting Lamp 3 Status
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 15
Safety Input 14
Safety Input 13
Safety Input 12
Safety Input 11 Safety Input 10
Safety Input 9
Safety Input 8
2
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
3
Safety Input 15 Status
Safety Input 14 Status
Safety Input 13 Status
Safety Input 12 Status
Safety Input 11 Status
Safety Input 10 Status
Safety Input 9 Status
Safety Input 8 Status
4
Reserved
Reserved
Input Power Error (1)
Reserved
Muting Lamp 15 Status
Muting Lamp 11 Status
Muting Lamp 7 Status
Muting Lamp 3 Status
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 15
Safety Input 14
Safety Input 13
Safety Input 12
Safety Input 11 Safety Input 10
Safety Input 9
Safety Input 8
2
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
3
Safety Input 15 Status
Safety Input 14 Status
Safety Input 13 Status
Safety Input 12 Status
Safety Input 11 Status
Safety Input 10 Status
Safety Input 9 Status
Safety Input 8 Status
4
Test Output 7 Status
Test Output 6 Status
Test Output 5 Status
Test Output 4 Status
Test Output 3 Status
Test Output 2 Status
Test Output 1 Status
Test Output 0 Status
5
Test Output 15 Status
Test Output 14 Status
Test Output 13 Status
Test Output 12 Status
Test Output 11 Status
Test Output 10 Status
Test Output 9 Status
Test Output 8 Status
6
Reserved
Reserved
Input Power Error (1)
Output Power Error (1)
Muting Lamp 15 Status
Muting Lamp 11 Status
Muting Lamp 7 Status
Muting Lamp 3 Status
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Input Power Error
1
Test Output 7 Status
Test Output 6 Status
Test Output 5 Status
Test Output 4 Status
Test Output 3 Status
Test Output 2 Status
Test Output 1 Status
Test Output 0 Status
2
Test Output 15 Status
Test Output 14 Status
Test Output 13 Status
Test Output 12 Status
Test Output 11 Status
Test Output 10 Status
Test Output 9 Status
Test Output 8 Status
(1) This data is only diagnostic data. This data does not have safety integrity.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
111
Page 112
Appendix A
Get Diagnostic Status from Modules by Using Explicit Messaging
Table 51 - Output Data – 1791ES-IB8XOBV4 Modules Instance Hex (decimal)
Connection Type
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
22 (34)
Safety and standard
0
Standard Output 7(1)
Standard Output 6
Standard Output 5
Standard Output 4
Standard Output 3
Standard Output 2
Standard Output 1
Standard Output 0
234 (564)
Only safety
0
Safety Output 7
Safety Output 6
Safety Output 5
Safety Output 4
Safety Output 3
Safety Output 2
Safety Output 1
Safety Output 0
0
Safety Output 7
Safety Output 6
Safety Output 5
Safety Output 4
Safety Output 3
Safety Output 2
Safety Output 1
Safety Output 0
1
Standard Output 7
Standard Output 6
Standard Output 5
Standard Output 4
Standard Output 3
Standard Output 2
Standard Output 1
Standard Output 0
2C4 (708)
Only safety
(1) Standard output signifies a test output configured as a standard output.
Table 52 - Output Data – 1791ES-IB16 Modules Instance Hex (decimal)
23 (35)
Connection Type
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Standard Output 7
Standard Output 6
Standard Output 5
Standard Output 4
Standard Output 3
Standard Output 2
Standard Output 1
Standard Output 0
1
Standard Output 15
Standard Output 14
Standard Output 13
Standard Output 12
Standard Output 11
Standard Output 10
Standard Output 9
Standard Output 8
Safety and standard
1732ES Modules The bits in the tag definitions of the Logix Designer application are different than those shown in the following section. The following defines the name associations for clarification with the programming software. Table 53 - Bit Definitions and Logix Designer Tag Names
112
Bit Definitions
Logix Designer Application Tag Name
Safety Input 0…11
ModuleName:I.Pt00Data - Pt11Data
Safety Input 0…11 Status
ModuleName:I.Pt00InputStatus - Pt11InputStatus
Combined Safety In Status
ModuleName:I.InputStatus
Muting Lamp Status
ModuleName:I.MutingStatusXX where XX = 03, 07, 11
Safety Output 0…3
ModuleName:O.Pt00Data - Pt03Data
Safety Output 0…3 Status
ModuleName:I.Pt00OutputStatus - Pt03OutputStatus
Combined Safety Out Status
ModuleName:I.OutputStatus
Safety Output 0…3 Monitor
ModuleName:I.Pt00Readback - Pt03Readback
Test Output 0…11 Data
ModuleName:O.Test00Data - Test11Data
Test Output 0…11 Status
ModuleName:I.Pt00TestOutputStatus - Pt11TestOutputStatus
Input Power Status
ModuleName:I.InputPowerStatus
Output Power Status
ModuleName:I.OutputPowerStatus
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 113
Get Diagnostic Status from Modules by Using Explicit Messaging
Appendix A
See these tables for reference data concerning input and output data. Table 54 - Input Data – 1732ES-IB12XOBV2 and 1732ES-IB12XOB4 Modules Instance Hex (decimal)
Connection Type
20C (524)
Safety and standard
22C (556)
301 (769)
32C (812)
33C (828)
34C (844)
35C (860)
Safety and standard
Only standard
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Reserved
Reserved
Reserved
Reserved
Safety Input 11
Safety Input 10
Safety Input 9
Safety Input 8
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
Safety Input 11
Safety Input 10
Safety Input 9
Safety Input 8
2
Safety Input 11 Status
Safety Input 10 Status
Safety Input 9 Status
Safety Input 8 Status
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Output Power Error
Input Power Error
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
Safety Input 10
Safety Input 9
Safety Input 8
1
Reserved
Reserved
Reserved
Reserved
Safety Input 11
2
Combined Safety In Status
Combined Safety Out Status
Input Power Error (1)
Output Power Error (1)
Reserved
Muting Lamp 11 Status
Muting Lamp 7 Status
Muting Lamp 3 Status
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
Safety Input 11
Safety Input 10
Safety Input 9
Safety Input 8
2
Safety Input 11 Status
Safety Input 10 Status
Safety Input 9 Status
Safety Input 8 Status
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
3
Reserved
Reserved
Input Power Error (1)
Output Power Error (1)
Reserved
Muting Lamp 11 Status
Muting Lamp 7 Status
Muting Lamp 3 Status
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
Safety Input 11
Safety Input 10
Safety Input 9
Safety Input 8
2
Safety Input 11 Status
Safety Input 10 Status
Safety Input 9 Status
Safety Input 8 Status
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
3
Reserved
Reserved
Reserved
Reserved
Safety Output 3 Status
Safety Output 2 Status
Safety Output 1 Status
Safety Output 0 Status
4
Reserved
Reserved
Input Power Error (1)
Output Power Error (1)
Reserved
Muting Lamp 11 Status
Muting Lamp 7 Status
Muting Lamp 3 Status
Safety and standard
Safety and standard
Safety and standard
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
Safety Input 11
Safety Input 10
Safety Input 9
Safety Input 8
2
Safety Input 11 Status
Safety Input 10 Status
Safety Input 9 Status
Safety Input 8 Status
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
3
Safety Output 3 Monitor
Safety Output 2 Monitor
Safety Output 1 Monitor
Safety Output 0 Monitor
Safety Output 3 Status
Safety Output 2 Status
Safety Output 1 Status
Safety Output 0 Status
4
Reserved
Reserved
Input Power Error (1)
Output Power Error (1)
Reserved
Muting Lamp 11 Status
Muting Lamp 7 Status
Muting Lamp 3 Status
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
113
Page 114
Appendix A
Get Diagnostic Status from Modules by Using Explicit Messaging
Table 54 - Input Data – 1732ES-IB12XOBV2 and 1732ES-IB12XOB4 Modules (Continued) Instance Hex (decimal)
36C (876)
37C (892)
39C (924)
3AC (940)
Connection Type
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
Safety Input 11
Safety Input 10
Safety Input 9
Safety Input 8
2
Safety Input 11 Status
Safety Input 10 Status
Safety Input 9 Status
Safety Input 8 Status
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
3
Test Output 7 Status
Test Output 6 Status
Test Output 5 Status
Test Output 4 Status
Test Output 3 Status
Test Output 2 Status
Test Output 1 Status
Test Output O Status
4
Reserved
Reserved
Reserved
Reserved
Test Output 11 Status
Test Output 10 Status
Test Output 9 Status
Test Output 8 Status
5
Reserved
Reserved
Input Power Error (1)
Output Power Error (1)
Reserved
Muting Lamp 11 Status
Muting Lamp 7 Status
Muting Lamp 3 Status
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 3 Status
Safety Input 2 Status
Safety Input 1 Status
Safety Input 0 Status
Safety Input 11
Safety Input 10
Safety Input 9
Safety Input 8
2
Safety Input 11 Status
Safety Input 10 Status
Safety Input 9 Status
Safety Input 8 Status
Safety Input 7 Status
Safety Input 6 Status
Safety Input 5 Status
Safety Input 4 Status
3
Safety Output 3 Monitor
Safety Output 2 Monitor
Safety Output 1 Monitor
Safety Output 0 Monitor
Safety Output 3 Status
Safety Output 2 Status
Safety Output 1 Status
Safety Output 0 Status
4
Test Output 7 Status
Test Output 6 Status
Test Output 5 Status
Test Output 4 Status
Test Output 3 Status
Test Output 2 Status
Test Output 1 Status
Test Output 0 Status
5
Reserved
Reserved
Reserved
Reserved
Test Output 11 Status
Test Output 10 Status
Test Output 9 Status
Test Output 8 Status
6
Reserved
Reserved
Input Power Error (1)
Output Power Error (1)
Reserved
Muting Lamp 11 Status
Muting Lamp 7 Status
Muting Lamp 3 Status
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Output Power Error
Input Power Error
1
Test Output 7 Status
Test Output 6 Status
Test Output 5 Status
Test Output 4 Status
Test Output 3 Status
Test Output 2 Status
Test Output 1 Status
Test Output 0 Status
2
Reserved
Reserved
Reserved
Reserved
Test Output 11 Status
Test Output 10 Status
Test Output 9 Status
Test Output 8 Status
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Output Power Error
Input Power Error
1
Test Output 3 Status
Test Output 2 Status
Test Output 1 Status
Test Output 0 Status
Safety Output 3 Monitor
Safety Output 2 Monitor
Safety Output 1 Monitor
Safety Output 0 Monitor
2
Test Output 11 Status
Test Output 10 Status
Test Output 9 Status
Test Output 8 Status
Test Output 7 Status
Test Output 6 Status
Test Output 5 Status
Test Output 4 Status
Safety and standard
Safety and standard
Only standard
Only standard
(1) This data is only diagnostic data. This data does not have safety integrity.
Table 55 - Output Data – 1732ES-IB12XOBV2 and 1732ES-IB12XOB4 Modules Instance Hex (decimal)
25 (37)
233 (563)
3C4 (964)
114
Connection Type
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Standard Output 7
Standard Output 6
Standard Output 5
Standard Output 4
Standard Output 3
Standard Output 2
Standard Output 1
Standard Output 0
1
Reserved
Reserved
Reserved
Reserved
Standard Output 11
Standard Output 10
Standard Output 9
Standard Output 8
0
Reserved
Reserved
Reserved
Reserved
Safety Output 3
Safety Output 2
Safety Output 1
Safety Output 0
0
Standard Output 3
Standard Output 2
Standard Output 1
Standard Output 0
Safety Output 3
Safety Output 2
Safety Output 1
Safety Output 0
1
Standard Output 11
Standard Output 10
Standard Output 9
Standard Output 8
Standard Output 7
Standard Output 6
Standard Output 5
Standard Output 4
Safety and standard
Only safety
Only safety
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 115
Get Diagnostic Status from Modules by Using Explicit Messaging
Appendix A
Explicit Messaging can also be used to read individual channel status for safety inputs, safety outputs, test outputs, and power status. Communication error settings can also be configured and monitored for test outputs as well.
Explicit Messages
Table 56 - Reading the Cause of the Safety Input Error Explicit Message
Safety input cause of error (fault) information read
Service
Function
Command (hex) Service Code the cause for the status Get attribute Reads bit (1…n), specified by the Single Instance ID, turning OFF.
0E
Class ID
Instance ID
3D
01…n
Response (hex)
Attribute ID
6E
Data Size 0: No error 01: Configuration invalid 02: External test signal error 03: Internal input error 04: Discrepancy error 05: Error in the other dual channel input
-
Table 57 - Reading the Cause of the Safety Output Error Explicit Message
Safety output cause of error (fault) information
Service
Function
Command (hex) Service Code
Get attribute single
Reads the cause for the status bit (1…n), specified by the Instance ID, turning OFF.
0E
Class ID
Instance ID
3B
01…n
Response (hex)
Attribute ID
6E
Data Size 0: No error 01: Configuration invalid 02: Over current detected 03: Short circuit detected 04: Output ON error 05: Error in the other dual channel output 08: Output data error 09: Short circuit detected at safety output
-
Table 58 - Monitoring the Test Output Point Explicit Message
Service
Function
Command (hex) Service Code
Test output cause of error (fault) information
Get attribute single
Reads the cause for the status bit (1…n), specified by the Instance ID, turning OFF.
0E
Class ID
09
Instance ID
01…n
Attribute ID
76
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Response (hex) Data Size
-
0 = No error 01: Configuration invalid 02: Overload detected 05: Output ON error 06: Undercurrent detected for muting lamp
115
Page 116
Appendix A
Get Diagnostic Status from Modules by Using Explicit Messaging
Table 59 - Setting Hold/Clear for Communications Errors (test output) Explicit Message
Setting for output state (hold or clear) after communication error
Setting for output state (hold or clear) after communication error
116
Service
Function
Command (hex)
Response (hex)
Service Code
Class ID
Instance ID
Attribute ID
Data Size
Get attribute single
Reads whether hold or clear is set as the output state after a communication error for a test output specified by the instance ID. The setting can be read for a specified number of points.
OE
09
01…08
05
–
Set attribute single
Sets whether hold or clear as the output status after a communication error for an output specified by the instance ID. Sets whether a test output must hold its state or clear (turn off) after a communication error.
10
09
01…08
05
1 byte 00: Clear 01: Hold
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
1 byte 00: Clear 01: Hold
Page 117
Appendix
B
Safety Data
This appendix lists calculated values for probability of failure on demand (PFD), probability of failure per hour (PFH), and mean time to failure (MTTF). PFD and PFH calculations comply with IEC61508, edition 2, 2010.
Calculated Values
Calculated values of probability of failure on demand and probability of failure per hour appear in the Table 60 and must be calculated for the devices within the system to comply with the SIL level required for application. Users must be responsible for following the requirements of ISO 13849-1:2008, to assess performance levels in their safety system. Within the proof test interval, every I/O module must be functionally tested by individually toggling each input point and verifying that it is detected by the controller. Additionally, each output point must be individually toggled by the controller and user-verified that the output point changes state. For more information, refer to these publications. Resource
Description
GuardLogix 5570 Controller Systems Safety Reference Manual, publication 1756-RM099
Provides information on safety application requirements for GuardLogix 5570 controllers in Studio 5000 Logix Designer projects.
GuardLogix Controller Systems Safety Reference Manual, publication 1756-RM093
Provides information on safety application requirements for GuardLogix 5560 and 5570 controllers in RSLogix 5000 projects.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
117
Page 118
Appendix B
Safety Data
Figure 24 - PFD Versus Proof Test Interval 1791ES-IB16 Module
Figure 25 - PFD Versus Proof Test Interval 1791ES-IB8XOBV4 Module
Figure 26 - PFD Versus Proof Test Interval 1732ES-IB12XOBV2 Module(1)
(1) Data is for both SIL3 dual-channel mode of operation and SIL2 single-channel Safety Inputs mode of operation.
118
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 119
Safety Data
Appendix B
Figure 27 - PFD Versus Proof Test Interval 1732ES-IB12XOB4 Module (1)
Table 60 - Calculated Values for Probability of Failure on Demand (PFD), Probability of Failure per Hour (PFH), and Mean Time To Failure (MTTF) Cat. No.
Proof Test Interval Year
1791ES-IB16
1791ES-IB8XOBV4
1732ES-IB12XOBV2(1)
1732ES-IB12XOB4(1)
Hour
PFD (1/hour)
PFH (1/hour)
Spurious Trip Rate (STR)
MTTFSpurious (years)
3.309E-06
34.48
5.612E-06
20.33
6.73E-06
16.97
6.66E-06
17.14
1
8760
2.06E-06 4.98E-10
2
17520
4.13E-06
5
43800
1.03E-05
10
87600
2.06E-05
1
8760
2.09E-06 5.04E-10
2
17520
4.17E-06
5
43800
1.04E-05
10
87600
2.09E-05
1
8760
5.33E-07 1.31E-10
2
17520
1.07E-06
5
43800
2.70E-06
10
87600
5.46E-06
20
175200
1
8760
5.33E-07 1.31E-10
2
17520
1.07E-06
5
43800
2.70E-06
10
87600
5.46E-06
20
175200
1.12E-05
1.12E-05
(1) Data is for both SIL3 dual-channel mode of operation and SIL2 single-channel Safety Inputs mode of operation.
Table 61 - Product Failure Rates (failures per hour) Cat. No.
λS
λDD
λDU
1791ES-IB16
1.57E-06
1.54E-06
4.98E-10
1791ES-IB8XOBV4
2.71E-06
2.68E-06
5.04E-10
1732ES-IB12XOB4(1)
3.95E-07
3.95E-07
1.31E-10
1732ES-IB12XOBV2(1)
3.95E-07
3.95E-07
1.31E-10
(1) Data is for both SIL3 dual-channel mode of operation and SIL2 single-channel Safety Inputs mode of operation.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
119
Page 120
Appendix B
Safety Data
Notes:
120
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015