Page 121

Appendix

C

Configuration Reference Information

The modules have these parameter groups: general parameters, safety input, test output, safety output.

See the tables for the settings in each parameter group. All parameters are set by using the Logix Designer application.

Parameter Groups Table 62 - General Parameters Parameter Name

Value

Description

Default

Safety Output Error Latch Time

0…65,530 ms (in increments of 10 ms)

Safety output errors are latched for this time.

1000 ms

Safety Input Error Latch Time

0…65,530 ms (in increments of 10 ms)

Safety input or test output errors are latched for this time.

1000 ms

Table 63 - Safety Input Parameters Parameter Name Input Point Operation Type

Value

Description

Single Channel

Use as single channel.

Dual-channel Equivalent

Use as dual-channel. Normal when both channels are ON or OFF.

Dual-channel Complementary

Use as dual-channel. Normal when one channel is ON and the other channel is OFF.

Not Used

External input device is not connected.

Safety Test Pulse

Use with a contact output device and in combination with a test output. By using this setting, short-circuits between input signal lines and the power supply (positive side) and short-circuits between input signal lines can be detected.

Safety

A solid-state output safety sensor is connected.

Standard

A standard device, such as a reset switch, is connected.

Not Used Test Output 0 to n

The test output that is used with the input. n is dependent on the module catalog number.

Input Delay Time Off -> On

0…126 ms (in increments of 6 ms)

Filter time for OFF to ON transition

Input Delay Time On -> Off

0…126 ms (in increments of 6 ms)

Filter time for ON to OFF transition

Input Point Mode

Safety Input Test Source

IMPORTANT

When configuring a test output for Pulse Test mode, verify the corresponding safety input is configured for safety pulse test.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

121

Page 122

Appendix C

Configuration Reference Information

Table 64 - Test Output Parameters Parameter Name

Test Output Mode

Value

Description

Not Used

An external device is not connected.

Standard

The output is connected to a standard device.

Default

Pulse Test

A contact output device is connected. Use in combination with a safety input.

Power Supply

The power supply of a Safety Sensor is connected. The voltage supplied to I/O Not Used power (V, G) is output from the test output terminal.

Muting Lamp Output 1791ES-IB8XOBV4 module = T3 and T7 1791ES-IB16 module = T3, T7, T11, and T15 1732ES modules = T3, T7, and T11

An indicator is connected and turned ON to detect broken lines in an external indicator.

Table 65 - Safety Output Parameters Parameter Name

Value

Description

Not Used

An external output device is not connected.

Safety

When the output is ON, the test pulse is not output (remains ON).

Safety Pulse Test

By using this function, short-circuits between output signal lines and the power supply (positive side) and short-circuits between output signal lines can be detected.

Single Channel(1)

Use as single channel.

Dual-channel

Use as dual-channel. When both channels are normal, outputs can be turned ON.

Output Point Mode

Output Point Operation Type

(1) Safety outputs configured for single-channel operation must be controlled as pairs for use in functional safety applications.

122

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Default

Not Used

Dual-channel

Page 123

Appendix

D

Specifications

Technical Specifications

Topic

Page

Technical Specifications

123

Environmental Specifications

127

Certifications

130

Legislation and Standards

130

EC Directives

131

This section provides technical specifications for the modules.

1791ES Modules For 1791ES modules, see Table 66 and Table 67. Table 66 - 1791ES Modules – Technical Specifications Attribute

Value

Safety input Inputs type

Current sinking

Voltage, on-state input, min

11V DC

Current, on-state input, min

3.3 mA

Voltage, off-state input, max

5V DC

Current, off-state, max

1.3 mA

IEC 61131-2 (input type)

Type 3

Pulse test output Output type

Current sourcing

Pulse test output current

0.7 A per output 8 A total module at 40 °C (104 °F) 6 A total module at 60 °C (140 °F) for 1791ES-IB8XOBV4 (see temperature versus current derating) 8 A total module at 60 °C (140 °F) for 1791ES-IB16

Residual voltage, max

1.2V

Output leakage current, max

0.1 mA

Short circuit protection

Yes

Current, max

25 mA – current, max (to avoid fault when used as a muted lamp output)

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

123

Page 124

Appendix D

Specifications

Table 66 - 1791ES Modules – Technical Specifications (continued) Attribute

Value

Current, min

5 mA – current, min (at which fault indication is generated when used as a muted lamp output)

Safety output Output types

Current sourcing/current sinking – bipolar pair

Output current rating

2 A max per point 8 A total module at 40 °C (104 °F) (see temperature versus current derating) 6 A total module at 60 °C (140 °F)

On-state voltage drop

+/- 0.6V

Leakage current

+/- 1.0 mA(1)

Internal resistance from P to M terminal

3.25 kΩ

Short circuit detection

Yes (short high and low and cross-circuit fault detection)

Short circuit protection

Electronic

Aggregate current of module

8 A at 40 °C (104 °F), 6 A at 60 °C (140 °F) (see product temperature versus current derating)

Pilot duty rating

2.5 A inrush for 1791ES-IB8XOBV4 module

Number of outputs

4, dual-channel

(1) Includes the presence of a single P stuck-high or M stuck-low short.

Table 67 - 1791ES Modules – General Attribute

Value

North American temp code

T4A

Enclosure type rating

Meets IP20

Communication current consumption

250 mA at 24V DC

Operating voltage range

19.2…28.8V DC (24V DC, -20…20%)

Isolation voltage

1791ES-IB16 - 50V (continuous), basic insulation - type tested at 800V DC for 60 s between input channels and network 1791ES-IB8XOBV4 - 50V (continuous), basic insulation - type tested at 800V DC for 60 s between input and output channels and between I/O and network

Product temperature versus current derating

8A 7A 6A

-20 °C (-4 °F)

40 °C 50 °C 60 °C (104 °F) (122 °F) (140 °F) Product Temperature Versus Current Derating (combined current from both input and output supplies) Wiring category(1)

124

2 - on signal ports, 2 - on power ports, 2 -on communication ports

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 125

Specifications

Appendix D

Table 67 - 1791ES Modules – General (continued) Attribute

Value

Wire size

Power and I/O wiring: 0.34…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max

Weight, approx.

600 g (1.32 lb)

Dimensions (HxWxD), approx.

80 x 196 x 77 mm (3.2 x 7.7 x 3 in.) with terminal block 77 x 196 x 62 mm (3 x 7.7 x 2.5 in.) without terminal block

(1) Use this Conductor Category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

1732ES Modules For 1732ES modules, see Table 68 and Table 69. Table 68 - 1732ES Modules – Technical Specifications Attribute

Value

Safety input Inputs type

Current sinking

Voltage, on-state input

11…30V DC

Current, on-state input

3.5 mA

Voltage, off-state input, max

5V DC

Current, off-state, max

1 mA

IEC 61131-2 (input type)

Type 3

Pulse test output Output type

Current sourcing

Pulse test output current (each)

0.7 A max per point at 40 °C (104 °F) 0.3 A max per point at 55 °C (131 °F) (see Product temperature versus pulse test output current derating on page 126)

Residual voltage, max

1.2V

Output leakage current, max

0.1 mA

Short circuit protection

Yes

Current, max

25 mA – current, max (to avoid fault when used as a muted lamp output)

Current, min

5 mA – current, min (at which fault indication is generated when used as a muted lamp output)

Safety output Output types

1732ES-IB12XOBV2: Current sourcing/current sinking bipolar pair 1732ES-IB12XOB4: Current sourcing

Output current rating (each)

1732ES-IB12XOBV2: 2 A max per point, bipolar outputs 1732ES-IB12XOB4: 1 A max per point, sourcing outputs

On-state voltage drop, max

1.15V

Leakage current

1732ES-IB12XOB4: +/-0.1 mA 1732ES-IB12XOBV2: +/-1.0 mA(1)

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

125

Page 126

Appendix D

Specifications

Table 68 - 1732ES Modules – Technical Specifications (continued) Attribute

Value

Internal resistance from sourcing to sinking terminal

1732ES-IB12XOBV2: 3.25 kΩ 1732ES-IB12XOB4: N/A

Short circuit detection

Yes (short high and low and cross-circuit fault detection)

Short circuit protection

Electronic

Pilot duty rating

1732ES-IB12XOBV2: 2.5 A inrush 1732ES-IB12XOB4: N/A

Number of outputs

Safety outputs 1732ES-IB12XOB4 module, 4 sourcing outputs 1732ES-IB12XOBV2 module, 4 bipolar outputs, (2 pairs)

Sensor power output current rating (pins 1, 3, and 5 of each output signal I/O connector)

2 A max per point at 40 °C (104 °F) 1 A max per point at 55 °C (131 °F) (see Product temperature versus sensor power current derating (per pin) on page 127)

(1) Includes the presence of a single sourcing output stuck-high or sinking output stuck-low fault.

Table 69 - 1732ES Modules – General Attribute

Value

Enclosure type rating

Meets IP65/IP67 (when marked)

Product current consumption (not including Test output or Safety output load current)

1732ES-IB12XOBV2: • In power (no load): 19.2…28.8V DC, 175 mA at 24V DC • Out power (no load): 19.2…28.8V DC, 65 mA at 24V DC 1732ES-IB12XOB4: • In power (no load): 19.2…28.8V DC, 175 mA at 24V DC • Out power (no load): 19.2…28.8V DC, 45 mA at 24V DC

Operating voltage range

19.2…28.8V DC (24V DC, -20…20%)

Module power connector rating

10 A max per pin

Isolation voltage

50V (continuous), Basic Type, Input Power and I/O to Ethernet, Input Power and I/O to Output Power and IO, and Output Power and IO to Ethernet Tested at 707V DC for 60s

Product temperature versus pulse test output current derating

0.7 A

0.3 A

-20 °C (-4 °F)

40 °C (104 °F)

55 °C (131 °F)

Product Temperature Versus Pulse Test Output Current Derating

126

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 127

Specifications

Appendix D

Table 69 - 1732ES Modules – General (continued) Attribute

Value

Product temperature versus sensor power current derating (per pin)

2.0 A

1.0 A

-20 °C (-4 °F)

40 °C (104 °F)

55 °C (131 °F)

Product Temperature Versus Sensor Power Current Derating (per pin) Wiring category(1)

2 - on signal ports 2 - on power ports 2 - on communication ports

Weight, approx.

786 g (1.73 lb)

Dimensions (HxWxD), approx.

70 x 259 x 69 mm (2.8 x 10.2 x 2.7 in.) without cables

(1) Use this Conductor Category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Environmental Specifications This section provides environmental specifications for the modules. • For 1791ES modules, see Table 70 on page 127. • For 1732ES modules, see Table 71 on page 128. Table 70 - 1791ES Modules – Environmental Specifications Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20…60 °C (-4…140 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating): 5 g at 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g

Emissions

CISPR 11: Group 1, Class A

ESD immunity

IEC 61000-4-2: 8 kV contact discharges 10 kV air discharges

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

127

Page 128

Appendix D

Specifications

Table 70 - 1791ES Modules – Environmental Specifications (continued) Attribute

Value

Radiated RF immunity

IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

Conducted RF immunity

IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

EFT/B immunity

IEC 61000-4-4: ±4 kV at 5 kHz on power ports ±3 kV at 5 kHz on signal ports ±2 kV at 5 kHz on communication ports

Surge transient immunity

IEC 61000-4-5: ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports ±2 kV line-earth (CM) on communication ports

Reaction time Input reaction time, max

16.2 ms + set values of ON/OFF delays

Output reaction time, max

6.2 ms + (20 ms) relay response time

Signal sequence Typ. 600 ms

Typ. 700 µs While safety outputs are in an on state, the signal sequence shown in the figure is output continuously for fault diagnosis. Confirm response time of device connected to safety outputs so the device does not malfunction due to off pulse.

Table 71 - 1732ES Modules – Environmental Specifications

128

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20…55 °C (-4…131 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating): 5 g at 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g

Emissions

IEC 61000-6-4

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

Page 129

Specifications

Appendix D

Table 71 - 1732ES Modules – Environmental Specifications (continued) Attribute

Value

ESD immunity

IEC 61000-4-2: 4 kV contact discharges 10 kV air discharges

Radiated RF immunity

IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz 3V/m with 1 kHz sine-wave 80% AM from 2700…6000 MHz

Conducted RF immunity

IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

EFT/B immunity

IEC 61000-4-4: ±2 kV at 5 kHz on power ports ±1 kV at 5 kHz on signal ports ±1 kV at 5 kHz on communication ports

Surge transient immunity

IEC 61000-4-5: ±2 kV line-earth (CM) on power ports ±2 kV line-earth (CM) on signal ports ±2 kV line-earth (CM) on communication ports

Reaction time Input reaction time, max

16.2 ms + set values of ON/OFF delays

Output reaction time, max

6.2 ms + (20 ms) relay response time

Signal sequence Typ. 600 ms

Typ. 700 µs While safety outputs are in an on state, the signal sequence shown in the figure is output continuously for fault diagnosis. Confirm response time of device connected to safety outputs so the device does not malfunction due to off pulse.

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015

129

Page 130

Appendix D

Specifications

Certifications

This section provides certification information for the 1791ES and 1732ES modules. Table 72 - 1791ES and 1732ES Modules – Certifications Certification

Value

Certifications (when product is marked)(1)

CE

European Union 2004/108/EC EMC Directive, compliant with these norms: EN 61326-1; Meas./Control/Lab, Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

RCM

Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions

Ethernet/IP

ODVA conformance tested to CIP Safety on EtherNet/IP specifications

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with Article 58-2 of Radio Waves Act, Clause 3

TÜV

Capable of Cat. 4/PL e according to EN ISO 13849-1 and SIL 3 according to EN 62061/IEC 61508(2)

(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. (2) When used with specified firmware revisions, and as described in the Safety Reference Manual, publication 1756RM-099, and the Guard I/O EtherNet/IP Safety Modules, publication 1791ES-UM001.

Legislation and Standards

Read this section to familiarize yourself with related legislation and standards information. Relevant international standards include the following: • IEC 61508:2010 Edition 2 (SIL 1…3) • IEC 61131-2 • IEC 60204-1 • IEC 61000-6-2 • IEC 61000-6-4 The modules received the following certification from ODVA, when product is marked. • EtherNet/IP Conformance • EtherNet/IP Safety Conformance

130

Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015