The text of a manual · part 13 of 14
Guard I/O EtherNet/IP Safety Modules User Manual, pages 121 to 130
Pages 121 to 130 of 140
The original document is the PDF (7.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1791ES
Page 121
Appendix
C
Configuration Reference Information
The modules have these parameter groups: general parameters, safety input, test output, safety output.
See the tables for the settings in each parameter group. All parameters are set by using the Logix Designer application.
Parameter Groups Table 62 - General Parameters Parameter Name
Value
Description
Default
Safety Output Error Latch Time
0…65,530 ms (in increments of 10 ms)
Safety output errors are latched for this time.
1000 ms
Safety Input Error Latch Time
0…65,530 ms (in increments of 10 ms)
Safety input or test output errors are latched for this time.
1000 ms
Table 63 - Safety Input Parameters Parameter Name Input Point Operation Type
Value
Description
Single Channel
Use as single channel.
Dual-channel Equivalent
Use as dual-channel. Normal when both channels are ON or OFF.
Dual-channel Complementary
Use as dual-channel. Normal when one channel is ON and the other channel is OFF.
Not Used
External input device is not connected.
Safety Test Pulse
Use with a contact output device and in combination with a test output. By using this setting, short-circuits between input signal lines and the power supply (positive side) and short-circuits between input signal lines can be detected.
Safety
A solid-state output safety sensor is connected.
Standard
A standard device, such as a reset switch, is connected.
Not Used Test Output 0 to n
The test output that is used with the input. n is dependent on the module catalog number.
Input Delay Time Off -> On
0…126 ms (in increments of 6 ms)
Filter time for OFF to ON transition
Input Delay Time On -> Off
0…126 ms (in increments of 6 ms)
Filter time for ON to OFF transition
Input Point Mode
Safety Input Test Source
IMPORTANT
When configuring a test output for Pulse Test mode, verify the corresponding safety input is configured for safety pulse test.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
121
Page 122
Appendix C
Configuration Reference Information
Table 64 - Test Output Parameters Parameter Name
Test Output Mode
Value
Description
Not Used
An external device is not connected.
Standard
The output is connected to a standard device.
Default
Pulse Test
A contact output device is connected. Use in combination with a safety input.
Power Supply
The power supply of a Safety Sensor is connected. The voltage supplied to I/O Not Used power (V, G) is output from the test output terminal.
Muting Lamp Output 1791ES-IB8XOBV4 module = T3 and T7 1791ES-IB16 module = T3, T7, T11, and T15 1732ES modules = T3, T7, and T11
An indicator is connected and turned ON to detect broken lines in an external indicator.
Table 65 - Safety Output Parameters Parameter Name
Value
Description
Not Used
An external output device is not connected.
Safety
When the output is ON, the test pulse is not output (remains ON).
Safety Pulse Test
By using this function, short-circuits between output signal lines and the power supply (positive side) and short-circuits between output signal lines can be detected.
Single Channel(1)
Use as single channel.
Dual-channel
Use as dual-channel. When both channels are normal, outputs can be turned ON.
Output Point Mode
Output Point Operation Type
(1) Safety outputs configured for single-channel operation must be controlled as pairs for use in functional safety applications.
122
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Default
Not Used
Dual-channel
Page 123
Appendix
D
Specifications
Technical Specifications
Topic
Page
Technical Specifications
123
Environmental Specifications
127
Certifications
130
Legislation and Standards
130
EC Directives
131
This section provides technical specifications for the modules.
1791ES Modules For 1791ES modules, see Table 66 and Table 67. Table 66 - 1791ES Modules – Technical Specifications Attribute
Value
Safety input Inputs type
Current sinking
Voltage, on-state input, min
11V DC
Current, on-state input, min
3.3 mA
Voltage, off-state input, max
5V DC
Current, off-state, max
1.3 mA
IEC 61131-2 (input type)
Type 3
Pulse test output Output type
Current sourcing
Pulse test output current
0.7 A per output 8 A total module at 40 °C (104 °F) 6 A total module at 60 °C (140 °F) for 1791ES-IB8XOBV4 (see temperature versus current derating) 8 A total module at 60 °C (140 °F) for 1791ES-IB16
Residual voltage, max
1.2V
Output leakage current, max
0.1 mA
Short circuit protection
Yes
Current, max
25 mA – current, max (to avoid fault when used as a muted lamp output)
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
123
Page 124
Appendix D
Specifications
Table 66 - 1791ES Modules – Technical Specifications (continued) Attribute
Value
Current, min
5 mA – current, min (at which fault indication is generated when used as a muted lamp output)
Safety output Output types
Current sourcing/current sinking – bipolar pair
Output current rating
2 A max per point 8 A total module at 40 °C (104 °F) (see temperature versus current derating) 6 A total module at 60 °C (140 °F)
On-state voltage drop
+/- 0.6V
Leakage current
+/- 1.0 mA(1)
Internal resistance from P to M terminal
3.25 kΩ
Short circuit detection
Yes (short high and low and cross-circuit fault detection)
Short circuit protection
Electronic
Aggregate current of module
8 A at 40 °C (104 °F), 6 A at 60 °C (140 °F) (see product temperature versus current derating)
Pilot duty rating
2.5 A inrush for 1791ES-IB8XOBV4 module
Number of outputs
4, dual-channel
(1) Includes the presence of a single P stuck-high or M stuck-low short.
Table 67 - 1791ES Modules – General Attribute
Value
North American temp code
T4A
Enclosure type rating
Meets IP20
Communication current consumption
250 mA at 24V DC
Operating voltage range
19.2…28.8V DC (24V DC, -20…20%)
Isolation voltage
1791ES-IB16 - 50V (continuous), basic insulation - type tested at 800V DC for 60 s between input channels and network 1791ES-IB8XOBV4 - 50V (continuous), basic insulation - type tested at 800V DC for 60 s between input and output channels and between I/O and network
Product temperature versus current derating
8A 7A 6A
-20 °C (-4 °F)
40 °C 50 °C 60 °C (104 °F) (122 °F) (140 °F) Product Temperature Versus Current Derating (combined current from both input and output supplies) Wiring category(1)
124
2 - on signal ports, 2 - on power ports, 2 -on communication ports
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 125
Specifications
Appendix D
Table 67 - 1791ES Modules – General (continued) Attribute
Value
Wire size
Power and I/O wiring: 0.34…1.5 mm2 (22…16 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max
Weight, approx.
600 g (1.32 lb)
Dimensions (HxWxD), approx.
80 x 196 x 77 mm (3.2 x 7.7 x 3 in.) with terminal block 77 x 196 x 62 mm (3 x 7.7 x 2.5 in.) without terminal block
(1) Use this Conductor Category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
1732ES Modules For 1732ES modules, see Table 68 and Table 69. Table 68 - 1732ES Modules – Technical Specifications Attribute
Value
Safety input Inputs type
Current sinking
Voltage, on-state input
11…30V DC
Current, on-state input
3.5 mA
Voltage, off-state input, max
5V DC
Current, off-state, max
1 mA
IEC 61131-2 (input type)
Type 3
Pulse test output Output type
Current sourcing
Pulse test output current (each)
0.7 A max per point at 40 °C (104 °F) 0.3 A max per point at 55 °C (131 °F) (see Product temperature versus pulse test output current derating on page 126)
Residual voltage, max
1.2V
Output leakage current, max
0.1 mA
Short circuit protection
Yes
Current, max
25 mA – current, max (to avoid fault when used as a muted lamp output)
Current, min
5 mA – current, min (at which fault indication is generated when used as a muted lamp output)
Safety output Output types
1732ES-IB12XOBV2: Current sourcing/current sinking bipolar pair 1732ES-IB12XOB4: Current sourcing
Output current rating (each)
1732ES-IB12XOBV2: 2 A max per point, bipolar outputs 1732ES-IB12XOB4: 1 A max per point, sourcing outputs
On-state voltage drop, max
1.15V
Leakage current
1732ES-IB12XOB4: +/-0.1 mA 1732ES-IB12XOBV2: +/-1.0 mA(1)
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
125
Page 126
Appendix D
Specifications
Table 68 - 1732ES Modules – Technical Specifications (continued) Attribute
Value
Internal resistance from sourcing to sinking terminal
1732ES-IB12XOBV2: 3.25 kΩ 1732ES-IB12XOB4: N/A
Short circuit detection
Yes (short high and low and cross-circuit fault detection)
Short circuit protection
Electronic
Pilot duty rating
1732ES-IB12XOBV2: 2.5 A inrush 1732ES-IB12XOB4: N/A
Number of outputs
Safety outputs 1732ES-IB12XOB4 module, 4 sourcing outputs 1732ES-IB12XOBV2 module, 4 bipolar outputs, (2 pairs)
Sensor power output current rating (pins 1, 3, and 5 of each output signal I/O connector)
2 A max per point at 40 °C (104 °F) 1 A max per point at 55 °C (131 °F) (see Product temperature versus sensor power current derating (per pin) on page 127)
(1) Includes the presence of a single sourcing output stuck-high or sinking output stuck-low fault.
Table 69 - 1732ES Modules – General Attribute
Value
Enclosure type rating
Meets IP65/IP67 (when marked)
Product current consumption (not including Test output or Safety output load current)
1732ES-IB12XOBV2: • In power (no load): 19.2…28.8V DC, 175 mA at 24V DC • Out power (no load): 19.2…28.8V DC, 65 mA at 24V DC 1732ES-IB12XOB4: • In power (no load): 19.2…28.8V DC, 175 mA at 24V DC • Out power (no load): 19.2…28.8V DC, 45 mA at 24V DC
Operating voltage range
19.2…28.8V DC (24V DC, -20…20%)
Module power connector rating
10 A max per pin
Isolation voltage
50V (continuous), Basic Type, Input Power and I/O to Ethernet, Input Power and I/O to Output Power and IO, and Output Power and IO to Ethernet Tested at 707V DC for 60s
Product temperature versus pulse test output current derating
0.7 A
0.3 A
-20 °C (-4 °F)
40 °C (104 °F)
55 °C (131 °F)
Product Temperature Versus Pulse Test Output Current Derating
126
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 127
Specifications
Appendix D
Table 69 - 1732ES Modules – General (continued) Attribute
Value
Product temperature versus sensor power current derating (per pin)
2.0 A
1.0 A
-20 °C (-4 °F)
40 °C (104 °F)
55 °C (131 °F)
Product Temperature Versus Sensor Power Current Derating (per pin) Wiring category(1)
2 - on signal ports 2 - on power ports 2 - on communication ports
Weight, approx.
786 g (1.73 lb)
Dimensions (HxWxD), approx.
70 x 259 x 69 mm (2.8 x 10.2 x 2.7 in.) without cables
(1) Use this Conductor Category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Environmental Specifications This section provides environmental specifications for the modules. • For 1791ES modules, see Table 70 on page 127. • For 1732ES modules, see Table 71 on page 128. Table 70 - 1791ES Modules – Environmental Specifications Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20…60 °C (-4…140 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating): 5 g at 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g
Emissions
CISPR 11: Group 1, Class A
ESD immunity
IEC 61000-4-2: 8 kV contact discharges 10 kV air discharges
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
127
Page 128
Appendix D
Specifications
Table 70 - 1791ES Modules – Environmental Specifications (continued) Attribute
Value
Radiated RF immunity
IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
Conducted RF immunity
IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
EFT/B immunity
IEC 61000-4-4: ±4 kV at 5 kHz on power ports ±3 kV at 5 kHz on signal ports ±2 kV at 5 kHz on communication ports
Surge transient immunity
IEC 61000-4-5: ±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports ±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports ±2 kV line-earth (CM) on communication ports
Reaction time Input reaction time, max
16.2 ms + set values of ON/OFF delays
Output reaction time, max
6.2 ms + (20 ms) relay response time
Signal sequence Typ. 600 ms
Typ. 700 µs While safety outputs are in an on state, the signal sequence shown in the figure is output continuously for fault diagnosis. Confirm response time of device connected to safety outputs so the device does not malfunction due to off pulse.
Table 71 - 1732ES Modules – Environmental Specifications
128
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20…55 °C (-4…131 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): -40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat): 5…95% noncondensing
Vibration
IEC 60068-2-6 (Test Fc, Operating): 5 g at 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g
Emissions
IEC 61000-6-4
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
Page 129
Specifications
Appendix D
Table 71 - 1732ES Modules – Environmental Specifications (continued) Attribute
Value
ESD immunity
IEC 61000-4-2: 4 kV contact discharges 10 kV air discharges
Radiated RF immunity
IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz 3V/m with 1 kHz sine-wave 80% AM from 2700…6000 MHz
Conducted RF immunity
IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
EFT/B immunity
IEC 61000-4-4: ±2 kV at 5 kHz on power ports ±1 kV at 5 kHz on signal ports ±1 kV at 5 kHz on communication ports
Surge transient immunity
IEC 61000-4-5: ±2 kV line-earth (CM) on power ports ±2 kV line-earth (CM) on signal ports ±2 kV line-earth (CM) on communication ports
Reaction time Input reaction time, max
16.2 ms + set values of ON/OFF delays
Output reaction time, max
6.2 ms + (20 ms) relay response time
Signal sequence Typ. 600 ms
Typ. 700 µs While safety outputs are in an on state, the signal sequence shown in the figure is output continuously for fault diagnosis. Confirm response time of device connected to safety outputs so the device does not malfunction due to off pulse.
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015
129
Page 130
Appendix D
Specifications
Certifications
This section provides certification information for the 1791ES and 1732ES modules. Table 72 - 1791ES and 1732ES Modules – Certifications Certification
Value
Certifications (when product is marked)(1)
CE
European Union 2004/108/EC EMC Directive, compliant with these norms: EN 61326-1; Meas./Control/Lab, Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
RCM
Australian Radiocommunications Act, compliant with: EN 61000-6-4; Industrial Emissions
Ethernet/IP
ODVA conformance tested to CIP Safety on EtherNet/IP specifications
KC
Korean Registration of Broadcasting and Communications Equipment, compliant with Article 58-2 of Radio Waves Act, Clause 3
TÜV
Capable of Cat. 4/PL e according to EN ISO 13849-1 and SIL 3 according to EN 62061/IEC 61508(2)
(1) See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details. (2) When used with specified firmware revisions, and as described in the Safety Reference Manual, publication 1756RM-099, and the Guard I/O EtherNet/IP Safety Modules, publication 1791ES-UM001.
Legislation and Standards
Read this section to familiarize yourself with related legislation and standards information. Relevant international standards include the following: • IEC 61508:2010 Edition 2 (SIL 1…3) • IEC 61131-2 • IEC 60204-1 • IEC 61000-6-2 • IEC 61000-6-4 The modules received the following certification from ODVA, when product is marked. • EtherNet/IP Conformance • EtherNet/IP Safety Conformance
130
Rockwell Automation Publication 1791ES-UM001E-EN-P - April 2015