For the Allen-Bradley 1794-ADN

Page 70

Chapter

4

Configuring Your DeviceNet Adapter Online Chapter Objectives

In this chapter you will learn:

• how to use the DeviceNet Manager software to configure the adapter online

About DeviceNet Manager

More

DeviceNet Manager is the software tool used to configure your Flex I/O DeviceNet adapter and its related modules. This software tool can be connected to the adapter via the DeviceNet network. You must know and understand how DeviceNet Manager works in order to add a device to the network. Refer to the DeviceNet Manager Software User Manual, publication 1787-6.5.3. In this chapter, we assume that you have established a network, and are adding a Flex I/O Adapter to your network.

Configuring Your Flex I/O Adapter and System Online

The procedure for online configuration is similar to the offline configuration procedure previously described. You must:

• add the device to the network from the Add Device to Network screen • address the device • establish the interface to the network • get to the configuration screen You can determine the adapter configuration and system configuration for an adapter at a specific node address. The node address is assigned either at the adapter (using the thumbwheel switch) or from the “add a device to network” screen. Note: If addressing the adapter at the “add a device to network” screen, the address must agree with the physical address selected by thumbwheels on the adapter. Select the “add device to network” from the pop-up menu.

Publication 1794-6.5.5 - October 1996

Page 71

4–2

Configuring Your DeviceNet Adapter Online

4 3

1. Click on communication adapter on the list box to highlight. 1

2. Click on the adapter you wish to add to the network. 3. Enter the assigned node address by clicking in the box, backspace and type the number.

2

4. Click on the OK button to accept your additions.

Check to make sure the interface is correct by clicking on the system icon in the tool bar.

System Icon The following screen appears. You can select the interface adapter you want to use.

Click on appears.

Publication 1794-6.5.5 - October 1996 to continue. The driver configuration screen

Page 72

Configuring Your DeviceNet Adapter Online

4–3

Use this screen to set serial port and DeviceNet setups, such as node address, data rate, communication port, and baud rates. Network Setup 1. To set the node address, click on the list box and make a choice. 2. To set the data rate, click on the list box and click on your selection. Driver Setup 3. Click on the radio button to select the desired communication port.

3

4. To set the baud rate, click on the list box and select the desired rate. 5. Click on to contimue.

1 2

4

5

After clicking on the “OK” button, you automatically return to the project screen. Online appears in the network area.

1. Highlight the device (the adapter) you want to configure. 2. Click twice on the selected adapter, or click on Device" to go to the adapter configuration screen in the online mode.

2 1

Online notification, including driver type, is also given in the status line at the bottom of the screen.

Publication 1794-6.5.5 - October 1996

Page 73

4–4

Configuring Your DeviceNet Adapter Online

The adapter configuration screen appears. From this screen, you can: - load from device - load from file - configure the adapter This screen will be automatically populated with the values residing in the adapter module.

The Configuration Screen At the adapter configuration screen, you can choose from various ways to load your screen with configuration information for your adapter. This does not actually configure your adapter.

• Load from Flex I/O – the adapter populates the screen with its system settings. These settings can be the settings previously setup in the adapter and each individual module, or out-of-box settings. • Load from file – populates screen with settings previously set up in a separate file created offline. The configuration screen will be automatically populated with the settings stored in the adapter when you highlight the adapter and click on “configure device” on the project screen. Or you can manually make your selections for adapter responses, and module placements and attributes.

Load from Device If you use “Load from Flex I/O”, your screen will reflect the information stored in the adapter. This information is not necessarily the physical setup of the actual system.

Publication 1794-6.5.5 - October 1996

Page 74

Configuring Your DeviceNet Adapter Online

4–5

This is what the screen looks when a from device" was used. All information stored in the adapter, including module setups, is used to populate the screen. 1. To apply changes to the adapter, you must do a to Flex I/O." 2. Any changes you do here are done the same as offline changes until a configuration button is activated.

Load from a File If you choose to load from a previously saved file, a selection screen will appear. When you load from file the screen will look like this.

If you load from a file, the file can contain settings that differ from the actual physical system setup.

Publication 1794-6.5.5 - October 1996

Page 75

4–6

Configuring Your DeviceNet Adapter Online

When you attempt to configure a slot, if the configured module type does not match the configuration information, you will be prompted with an error message. Your manually entered configuration

Actual configuration

If you make changes to the individual module placement, when you attempt to configure each slot, you will be prompted with a message similar to this:

!

Publication 1794-6.5.5 - October 1996

ATTENTION: Your settings will be lost if you cycle power without doing a “Save to File” or a “Save to Flex I/O.”

Page 76

Configuring Your DeviceNet Adapter Online

4–7

Entering Configuration Information into the Configuration Screen Select your adapter options as shown in the following:

1. Select from the list box for each configuration option: a. run idle b. run fault c. idle fault d. module fault. Use the button to show the settings for each option.

1

1a

1b

1c

1d

Publication 1794-6.5.5 - October 1996

Page 77

4–8

Configuring Your DeviceNet Adapter Online

Configuring Your Adapter's Flex I/O System Configure your Flex I/O system by specifying the Flex I/O module that will reside in each slot. Remember, slot 0 is the closest slot to the adapter, and slot 7 is the furthest or last slot. 1. Click on the or on the list box for slot 0. A list of modules is displayed. Use the up/dwn arrows to view the entire list of modules. 1a 2. Use the up/down arrows to page thru the possible module selections. Select the desired module by clicking on that selection.

1

1a

2

Select the modules you want inserted into each slot in your Flex I/O system. In the example, the following selections were made: Example This adapter example has 4 of 8 slots filled with modules.

1

1. Click in the list box to select the module for that slot.

You can configure each module:

• as you enter it, by clicking on the slot number in the configure column • or fill all the slots with your selections and go back and configure them all at one time using “Save to Flex I/O.”

Publication 1794-6.5.5 - October 1996

Page 78

Configuring Your DeviceNet Adapter Online

4–9

Configure Slot 0 The first module (slot 0) in the example is a 1794-IR8 RTD analog output module. This module has the following selections: When you are off line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file. 1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection. Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more output/configuration words from the process.

7 6 10

1

4

8 2

3

9 5

5a

2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen.

4a 3a

3. Select the module data type by clicking on the list box. A list of types is displayed (3a). Click on the desired module data type to select. 4. Select the desired filter first notch frequency by clicking on the list box. A list of frequencies is displayed (4a). Select the desired frequency by clicking on that selection.

2a

5. Select the type of RTD for each channel using the list box for selection of each type. Click on the desired RTD to select. 6. The to I/O only" button returns all settings to real time settings for this type of module. These settings are optimal, and not necessarily the settings. 7. When all settings are correct, click on to Flex I/O" to save the settings to the adapter. 8. If you change the settings, when all selections are complete, click on the OK button.

10

9. This module has an enhanced mode of operation. In the enhanced mode, inputs are compared against a known, precision resistor to determine the value of the RTD. Since this is performed each scan, module throughput is decreased. 10. Clicking on the calibration button brings up the calibration screen. In order to calibrate the module, you must physically attach reference sources to the module. Refer to the user manual for calibration instructions.

Publication 1794-6.5.5 - October 1996