Page 79

4–10

Configuring Your DeviceNet Adapter Online

Configure Slot 1 and 2 Slots 1 and 2 are empty. No selection is necessary.

Configure Slot 3 Slot 3 is a 1794-OE4 analog output module. This module has the following selections: When you are on line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file. If you do a "load from device," the sizes are the current sizes stored in the adapter. 1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection. Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more or less output/configuration words from the process. 2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen. 3. If desired, enter a value that the module outputs go to in the event of a communication failure if safe state is the action chosen in the fault or idle action. You can select the radix to use for data entry by clicking on the desired radio button. 4. Select the voltage/current for each analog output using the list box for selection of each output. 5. The to I/O only" button returns all settings to real time settings for this type of module. These settings are optimal, and not necessarily the settings.

6. You can apply your configuration now by clicking on the to Flex I/O" button. Or you can wait until you have configured all slots and apply the configuration using the to Flex I/O" button on the 1794-ADN configuration screen. 7. If you change the settings, when all selections are complete, click on the OK button.

Publication 1794-6.5.5 - October 1996

6

1

7

5 2 3

4

3a

2a

Page 80

Configuring Your DeviceNet Adapter Online

4–11

Configure Slot 4 The fifth module (slot 4) in the example is a 1794-IE8 analog input module. This module has the following selections: When you are on line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file. If you do a "load from device," the sizes are the current sizes stored in the adapter. 1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection. Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more or less output/configuration words from the process. 2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen.

5 1

6

4 2

3

2a

3. Select the voltage/current for each analog output using the list box for selection of each output. 4. The to I/O only" button returns all settings to real time settings for this type of module. These settings are optimal, and not necessarily the settings.

5. You can apply your configuration now by clicking on the to Flex I/O" button. Or you can wait until you have configured all slots and apply the configuration using the to Flex I/O" button on the 1794-ADN configuration screen. 6. If you change the settings, when all selections are complete, click on the OK button.

Configure Slots 5 and 6 Slots 5 and 6 are empty.

Publication 1794-6.5.5 - October 1996

Page 81

4–12

Configuring Your DeviceNet Adapter Online

Configure Slot 7 The eighth module (slot 7) is a 1794-OB16 input module. This module has the following selections: When you are on line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file. If you do a "load from device," the sizes are the current sizes stored in the adapter. 1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection. Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more or less output/configuration words from the process. 2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen. 3. If desired, enter a value that the module outputs would go to in the event of a communication failure if safe state is the action chosen in the fault or idle action. You can select the radix to use for data entry by clicking on the desired radio button. 4. The to I/O only" button returns all settings to real time settings for this type of module. These settings are optimal, and not necessarily the settings.

5. You can apply your configuration now by clicking on the to Flex I/O" button. Or you can wait until you have configured all slots and apply the configuration using the to Flex I/O" button on the 1794-ADN configuration screen. 6. If you change the settings, when all selections are complete, click on the OK button.

Publication 1794-6.5.5 - October 1996

6 1

5 4 2

3

2a

Page 82

Configuring Your DeviceNet Adapter Online

4–13

Applying Configuration Information to the Adapter In order to actually configure the adapter, you must do the following:

1. Click on to Flex I/O." 2. After clicking on the to Flex I/O" button you are automatically returned to the adapter configuration screen.

1

2

Note that the status line will show status when the configuration tool is communicating with the adapter.

!

ATTENTION: Your settings will be lost if you cycle power without doing a “Save to File” or a “Save to Flex I/O.”

If you attempt to close, the system will prompt you to save either to a file or to Flex I/O.

Publication 1794-6.5.5 - October 1996

Page 83

4–14

Configuring Your DeviceNet Adapter Online

Viewing the Mapping Summaries Click on the I/O summary button to see a summary of input and output image mapping for your adapter. This summary corresponds to whatever is on your configuration screen when launched. Your screen will look similar to the following:

This screen shows the mapping for the input data as configured. Each slot, the selected module, and individual channel data is identified.

By clicking on the radio button for output data, the following screen appears: This screen shows the mapping for the output data as configured. Each slot, the selected module, and individual channel data is identified.

Publication 1794-6.5.5 - October 1996

Page 84

Configuring Your DeviceNet Adapter Online

4–15

A complete module summary can be viewed by clicking on the button at the bottom of the I/O summary screen. Your module summary screen will look similar to the following:

The total words indicated are used in configuring the scan list table in your 1771-SDN scanner module.

Publication 1794-6.5.5 - October 1996

Page 85

4–16

Configuring Your DeviceNet Adapter Online

Using Mini Who and Network Who

You have a pulldown menu called “Who.” You can use the Who’s to see what devices are on the network, and information about them. You also have direct access to configuration screens for these devices. This includes your DeviceNet adapter.

Using Mini Who Mini Who shows you the devices on the network by node number, and indicates the total number of devices found. An “X” appears in the box at the address where a device is located. You access Mini Who directly though the Who menu.

The who" displays a matrix of possible node addresses and merely indicates which ones are in use. For a detailed description of what each node consists of, you must use a who."

Publication 1794-6.5.5 - October 1996

Page 86

Configuring Your DeviceNet Adapter Online

4–17

Using Network Who Network Who shows you the node address, the vendor ID, the device type, and device name for each device on the network, plus the total number of devices found. You access Network Who directly though the Who menu.

1. When you do a "network who", the network is examined for all devices connected to it. They are listed on the screen by node address. 2. To go to the online configure screen, select the device and click on the device" button to bring up the configuration screen. 3. To display details about each device, by click on the details" button. 4. When the build is complete, or the stop button is used, the button becomes active.

You can go directly to the “configure adapter” screen from the “network who” screen.

Using a "network who" to configure a device. 1 1. Highlight the device on the list. 2. Click on the device" button. 3. The configuration screen for that device appears.

2 3

Publication 1794-6.5.5 - October 1996

Page 87

4–18

Configuring Your DeviceNet Adapter Online

You can display device details from the network who screen.

Using a network who to display device details. 1. Highlight the device on the network screen. 2. Click on the details" button.

Publication 1794-6.5.5 - October 1996