What is in it
Allen-Bradley's user manual for the 1794-ADN Series B DeviceNet adapter, which connects a FLEX I/O system to a DeviceNet network. It covers installation (power, DIN rail or panel mounting, node address switch, wiring), how communication over the FLEX I/O backplane works and how each FLEX I/O module maps into the image table, offline and online configuration with DeviceNet Manager software, troubleshooting with the indicators, and specifications.
Its parts
- Installing Your DeviceNet Adapter Module
- How Communication Takes Place and I/O Image Table Mapping
- Configuring Your DeviceNet Adapter Offline
- Configuring Your DeviceNet Adapter Online
- Troubleshooting
From the manual
Key facts from this manual
Each line names its page in the PDF.
The October 1996 user manual for the Flex I/O DeviceNet adapter module 1794-ADN Series B. It explains how to mount and wire the adapter, set its network address, map I/O data for up to eight Flex I/O modules, configure it with DeviceNet Manager software and read its indicators. The 1794-TB3 terminal base is not named in the pages read.
- What it is
- DeviceNet adapter and power supply for a Flex I/O system of up to eight modules p. 11
- I/O capacity
- 8 modules (up to eight terminal base units) p. 89
- Input voltage
- 24V dc nominal; range 19.2V to 31.2V dc (includes 5% ac ripple) p. 89
- Power consumption
- 400mA maximum from an external 24V supply p. 89
- DeviceNet power
- 24V dc (+4%) at 90mA maximum p. 89
- Communication rate
- 125KB, 250KB or 500KB, set by baud detection at power-up p. 15, 89
- Network address
- 00 to 63, set with a 2-position thumbwheel switch p. 15
- Flexbus output current
- 640mA maximum at 5V dc p. 89
- Indicators
- Power, Mod/Net status (red/green) and I/O status (red/green) p. 89
- Operating temperature
- 0 to 55 C (32 to 131 F); storage -40 to 85 C p. 89
- Mounting
- 35 x 7.5mm DIN rail (A-B pt. no. 199-DR1), or wall/panel with the 1794-NM1 mounting kit p. 12, 13
- Dimensions
- 1794 adapters 3.4H x 2.7W x 2.7D in (87H x 68W x 69D mm) p. 13
- Communication choices
- Polled, strobe, change of state and cyclic p. 21
- Configuration software
- DeviceNet Manager Software, cat. no. 1787-MGR p. 8
What this manual walks you through
- Mounting the adapter on a DIN rail or a wall or panel p. 12, 13, 14
- Setting the network address switch p. 15
- Wiring the DeviceNet cable and 24V dc power, including daisy-chaining power p. 16
- How the adapter exchanges read and write words with each module slot p. 18, 19
- Reading the adapter input status word and its slot fault bits p. 20
- Default and real time data sizes for each supported Flex I/O module p. 45, 46
- Adding the adapter to a network in DeviceNet Manager p. 47
- Troubleshooting with the power, Mod/Net and I/O status indicators p. 88
Good to know
- Do not install more than eight terminal base units with one adapter. p. 14
- The network address cannot be changed from DeviceNet Manager, and a new switch setting takes effect only after a power cycle. p. 15, 20
- A strobe connection fails if the configured input size is greater than 8 bytes. p. 21
- The 400mA adapter draw must be added to the needs of other modules on the same 24V supply. p. 12
- The DIN rail and the wall mounting plate must be properly grounded to the panel. p. 13
Questions this manual answers
How many Flex I/O modules can a 1794-ADN handle?
One adapter interfaces with up to eight terminal base units with installed Flex I/O modules, a system of up to eight slots. p. 18
What power does the 1794-ADN need?
It needs 400mA at 24V dc from an external supply, which supports one logical rack of 8 modules; the input range is 19.2V to 31.2V dc. p. 12
What does a solid red Mod/Net light mean on the 1794-ADN?
Solid red on the Mod/Net status indicator means a critical adapter failure; flashing red is a recoverable fault. p. 88
What are the 1794-ADN DeviceNet wire colors?
Black to -V, blue to CAN Low, bare to drain, white to CAN High and red to +V. p. 16
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1794-6.5.5, DeviceNet Adapter Module User Manual1
- Foreword2
- Summary of Changes3
- Preface8
- 1 - Installing Your DeviceNet Adapter Module10
- 2 - How Communication Takes Place and I/O Image Table Mapping18
- 3 - Configuring Your DeviceNet Adapter Offline47
- 4 - Configuring Your DeviceNet Adapter Online70
- 5 - Troubleshooting88
- A - Specifications89
- Index90
- Publication Problem Report93
- Inside Back Cover95
- Back Cover96
The whole text · 13 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 31-3
- Table of Contents4-7
- Pages 8 to 178-17
- 2 - How Communication Takes Place and I/O Image Table Mapping, pages 18 to 2718-27
- 2 - How Communication Takes Place and I/O Image Table Mapping, pages 28 to 3728-37
- 2 - How Communication Takes Place and I/O Image Table Mapping, pages 38 to 4638-46
- 3 - Configuring Your DeviceNet Adapter Offline, pages 47 to 5447-54
- 3 - Configuring Your DeviceNet Adapter Offline, pages 55 to 6255-62
- 3 - Configuring Your DeviceNet Adapter Offline, pages 63 to 6963-69
- 4 - Configuring Your DeviceNet Adapter Online, pages 70 to 7870-78
- 4 - Configuring Your DeviceNet Adapter Online, pages 79 to 8779-87
- Pages 88 to 9288-92
- Pages 93 to 9693-96
The file