For the Allen-Bradley 1794-ADN

Page 18

Chapter

2

How Communication Takes Place and I/O Image Table Mapping Chapter Objectives

In this chapter, you will learn about:

• communication over the Flex I/O backplane (between the DeviceNet adapter and the I/O modules) • how data is mapped into the I/O image table

Communication Over the Flex I/O Backplane

One 1794-ADN DeviceNet adapter can interface with up to eight terminal base units with installed Flex I/O modules, forming a Flex I/O system of up to eight slots. The adapter communicates to other network system components (typically one or more controllers or scanners, and/or programming terminals) over the DeviceNet network. The adapter communicates with its I/O modules over the backplane. I/O Module Inputs

Network

DeviceNet Adapter

Read

Write

0

Read Words

Status Outputs Configuration Slot 0

Write Words 15

I/O Module

I/O Module

Inputs

Inputs

Status

Status

Outputs

Outputs

Configuration

Configuration

Slot 1

Slot 7

The I/O map for a module is divided into read words and write words. Read words consist of input and status words, and write words consist of output and configuration words. The number of read words or write words can be 0 or more. The length of each I/O module’s read words and write words vary in size depending on module complexity. Each I/O module will support at least 1 input word or 1 output word. Status and configuration are optional, depending on the module.

Publication 1794-6.5.5 - October 1996

Page 19

2–2

How Communication Takes Place and I/O Image Table Mapping

For example, a 16 point discrete input module will have up to 2 read words and 1 write word.

16-point Discrete Input Module

I/O Image

Module Image

Input Size 1 or 2 Words

Inputs

Output Size 0 or 1 Word

Not used Not used

Delay Time

Delay Time

Check the I/O map for each module for the exact mapping.

I/O Structure

Output data is received by the adapter in the order of the installed I/O modules. The Output data for Slot 0 is received first, followed by the Output data for Slot 1, and so on up to slot 7. The first word of input data sent by the adapter is the Adapter Status Word. This is followed by the input data from each slot, in the order of the installed I/O modules. The Input data from Slot 0 is first after the status word, followed by Input data from Slot 2, and so on up to slot 7. DeviceNet Adapter Read Data Adapter Status Slot 0 Input Data

Network READ

Slot 1 Input Data

...

...

Slot 7 Input Data

Read

Write Data

Write

Slot 0 Output Data Slot 1 Output Data

...

...

Network WRITE

Slot 7 Output Data

Publication 1794-6.5.5 - October 1996

I/O Module I/O Module Slot 0 Slot 1

...

I/O Module Slot 7

Page 20

How Communication Takes Place and I/O Image Table Mapping

2–3

Adapter Input Status Word The input status word consists of:

• I/O module fault bits – 1 status bit for each slot • node address changed – 1 bit • I/O status – 1 bit I/O Module Fault Bits Slot 0

1 0 Slot 1

Slot 2

Not Used

Slot 3

9 8 7 6 5 4 3 2 Slot 5 Slot 4

10 through 15

Slot 6

15

Slot 7

Bit:

I/O State Bit Node Address Changed Bit

The adapter input status word bit descriptions are shown in the following table. Bit Description

Bit

Explanation

0

This bit is set (1) when an error is detected in slot position 0.

1

This bit is set (1) when an error is detected in slot position 1.

2

This bit is set (1) when an error is detected in slot position 2.

3

This bit is set (1) when an error is detected in slot position 3.

4

This bit is set (1) when an error is detected in slot position 4.

5

This bit is set (1) when an error is detected in slot position 5.

6

This bit is set (1) when an error is detected in slot position 6.

7

This bit is set (1) when an error is detected in slot position 7.

Node Address Changed

8

This bit is set (1) when the node address switch setting has been changed since power up.

I/O State

9

Bit = 0 - idle Bit = 1 - run

I/O Module Fault

10 thru 15

Not used - sent as zeroes.

Possible causes for an I/O Module Fault are:

• • • • • transmission errors on the Flex I/O backplane a failed module a module removed from its terminal base incorrect module inserted in a slot position the slot is empty The node address changed bit is set when the node address switch setting has been changed since power up. The new node address does not take affect until the adapter has been powered down and then powered back up.

Publication 1794-6.5.5 - October 1996

Page 21

2–4

How Communication Takes Place and I/O Image Table Mapping

Communication Choices

The FLEX I/O DeviceNet adapter module supports multiple communication choices. These choices all use the default I/O structure previously described. The adapter master makes the actual communication choice. The choices are: Polled – data is sent by the adapter in response to received data Strobe – data is sent by the adapter in response to the strobe command. The single bit allocated to the adapter in the strobe message is not used. If the configured size of the input data (sent from the adapter) is greater than 8 bytes, the strobe connection establishment will fail. In this case, the input size must be reconfigured to 8 bytes or less. Change of State – data is sent by the adapter based on detection of any changed value within the input data. Data is independently received based on change of state from the sender. Data in both directions can be acknowledged or unacknowledged depending on the run time configuration of the system. Cyclic – data is sent cyclically by the adapter based on a configured time value. Data is independently received cyclically from the sender. Data in both directions can be acknowledged or unacknowledged depending on the run time configuration of the system.

Mapping Data into the Image Table

All Flex I/O modules are supported by the DeviceNet adapter. At present, these consist of: Catalog Number:

For image table mapping refer to:

16 Sink Input Module

1794-IB16 page 2-5

16 Source Output Module

1794-OB16 page 2-6

10 Input/6 Output Module

1794-IB10XOB6 page 2-6

8 Electronically Fused Source Output Module

1794-OB8EP page 2-7

8 Sensor Input Module

1794-IB8S page 2-8

8 Input Module

1794-IA8 page 2-9

8 Output Module

1794-OA8 page 2-10

8 Relay Output Module

1794-OW8 page 2-10

8 Input Analog Module

1794-IE8 page 2-11

4 Output Analog Module

1794-OE4 page 2-13

4 in/2 out Analog Combo Module

1794-IE4XOE2 page 2-16

8 RTD Input Analog Module

1794-IR8 page 2-19

8 Thermocouple Input Module

1794-IT8 page 2-23

2 Channel SCANport Module

1203-FM1 page 2-27

Module Description

Publication 1794-6.5.5 - October 1996

Page 22

How Communication Takes Place and I/O Image Table Mapping

2–5

16-point Discrete Input Module (1794-IB16) Image Table Mapping I/O Image

Module Image

Input Size Read

Inputs

1 or 2 Words

Not used Output Size Write

Delay Time

Not used

0 or 1 Word

Delay Time

Memory Map of 16-Point Discrete Input Module Image Table – 1794-IB16 Decimal Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

D15

D14

D13

D12

D11

D10

D9

D8

D7

D6

D5

D4

D3

D2

D1

D0

Not used

Size Read Word 1 Read Word 2

Not used

DT 12-15

DT 00-11

Write Word 1

Where D = Input Data (D0 corresponds to input 0, D1 corresponds to input 1, etc. DT = Input Delay Time (DT 00-11 corresponds to inputs 0 thru 11; DT 12-15 corresponds to inputs 12 thru 15)

Input Delay Times for the 1794-IB16 Input Module Bits

Description Selected Delay Time

02

01

00

Delay Time for Inputs 00-11

05

04

03

Delay Time for Inputs 12-15

0

0

0

Delay Time 0 (default)

512µs

0

0

1

Delay Time 1

1ms

0

1

0

Delay Time 2

2ms

0

1

1

Delay Time 3

4ms

1

0

0

Delay Time 4

8ms

1

0

1

Delay Time 5

16ms

1

1

0

Delay Time 6

32ms

1

1

1

Delay Time 7

64ms

Publication 1794-6.5.5 - October 1996

Page 23

2–6

How Communication Takes Place and I/O Image Table Mapping

16-point Discrete Output Module (1794-OB16) Image Table Mapping

Read

I/O Image Input Size

Module Image

0 or 1 Word

Not used

Output Size

Outputs

1 or 2 Words

Write

Not used

Memory Map of 16-Point Discrete Output Module Image Table – 1794-OB16 Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Oct. Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Size

Not used O15

O14

O13

O12

O11

O10

O9

O8

Read Word 1

O7

O6

O5

O4

O3

O2

O1

O0

Write Word 1

Not used

Write Word 2

Where O = Output value (O0 corresponds to output 0, O1 corresponds to output 1, etc.)

16-point Discrete Input/Output Module Image Table Mapping 1794-IB10XOB6 I/O Image Input Size Read

Module Image

0 to 1 Word

Not used

Inputs

Not used

Outputs

Output Size Write

0 to 2 Words

Not used

Memory Map of 16-Point Discrete Input/Output Module Image Table – 1794-IB10XOB6 Decimal Bits

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

(Octal Bits)

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

I9

I8

I7

I6

I5

I4

I3

I2

I1

I0

Read Word 1

O5

O4

O3

O2

O1

O0

Write Word 1

Not used Not used

Not used Where

I = Input Channel O = Output Channel

Publication 1794-6.5.5 - October 1996

Size

Write Word 2

Page 24

How Communication Takes Place and I/O Image Table Mapping

2–7

8-point Discrete Electronically Fused Output Module (1794-OB8EP) Image Table Mapping I/O Image Input Size Read

Module Image

0 or 1 Word

Fault Bits

Output Size

Reserved

Not used

FR

Outputs

1 or 2 Words

Write

Reserved

Memory Map of 8-Point Discrete Electronically Fused Output Module Image Table – 1794-OB8EP Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Oct. Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

F7

F6

F5

F4

F3

F2

F1

F0

Not used

FR

Reserved O7

O6

O5

O4

O3

Size Read Word 1

O2

O1

O0

Reserved

Write Word 1 Write Word 2

Where O = Output value (O0 corresponds to output 0, O1 corresponds to output 1, etc.) FV = overload fault bit (1 = fault present; 0 = no fault). F0 corresponds to output 0, F1 corresponds to output 1, and so on. FR = fault reset bit (1 = reset word; 0 = no change)

Publication 1794-6.5.5 - October 1996

Page 25

2–8

How Communication Takes Place and I/O Image Table Mapping

8-point Discrete Sensor Input Module (1794-IB8S) Image Table Mapping I/O Image

Module Image

Input Size Read

Status

1 or 2 Words

Inputs Not used

Output Size Write

Delay Time

Not used

0 or 1 Word

Delay Time

Memory Map of 8-Point Discrete Sensor Input Module Image Table – 1794-IB8S Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Oct. Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

S7

S6

S5

S4

S3

S2

S1

S0

D7

D6

D5

D4

D3

D2

D1

D0

Not used

Size Read Word 1 Read Word 2

Not used

DT 12-15

DT 00-11

Write Word 1

Where S = Status of input (where S1 corresponds to the diagnostic bit for input 1, S2 corresponds to the diagnostic bit for input 2, etc.) D = Input Data (where D0 corresponds to input 0, D1 corresponds to input 1, etc. DT = Input Delay Time (where DT 00-11 corresponds to inputs 0 thru 11; DT 12-15 corresponds to inputs 12 thru 15. Make certain that the delay time for 00-11 is the same as the delay time for 12-15. Smart Sensor Bits 08-15

S = Diagnostic data -

1 = Fault present (Smart) 0 = Normal (no errors)

Bits 00-07

D = Input data

1 = Sensor on 0 = Sensor off

1 = Diagnostics not disabled 0 = Normal (Disabled)

Bits 00-07

D = Input data

1 = Sensor on 0 = Sensor off

Standard Sensor Bits 08-15

S = Diagnostic data -

Input Delay Times for the 1794-IB8S Input Module Bits

Publication 1794-6.5.5 - October 1996

Description Selected Delay Time

02

01

00

Delay Time for Inputs 00-11

05

04

03

Delay Time for Inputs 12-15

0

0

0

Delay Time 0 (default)

512µs

0

0

1

Delay Time 1

1ms

0

1

0

Delay Time 2

2ms

0

1

1

Delay Time 3

4ms

1

0

0

Delay Time 4

8ms

1

0

1

Delay Time 5

16ms

1

1

0

Delay Time 6

32ms

1

1

1

Delay Time 7

64ms

Page 26

How Communication Takes Place and I/O Image Table Mapping

2–9

8-point Discrete Input Module (1794-IA8) Image Table Mapping Module Image

I/O Image Input Size Read

Not used

1 or 2 Words

Inputs Not used

Output Size Write

Delay Time

Not used

0 or 1 Word

Memory Map of 8-point Discrete Input Module Image Table – 1794-IA8 Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Oct. Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

D7

D6

D5

D4

D3

D2

D1

D0

Not used

Not used

Size Read Word 1 Read Word 2

Not used

DT 00-07

Write Word 1

Where D = Input Data (where D0 corresponds to input 0, D1 corresponds to input 1, etc. DT = Input Delay Time (where DT 00-07 corresponds to inputs 0 thru 7)

Input Delay Times for the 1794-IA8 Input Module Bits

Description

Maximum Delay Time

02

01

00

Delay Time for Inputs 00-07

Off to On

On to Off

0

0

0

Delay Time 0 (default)

8.6ms

26.6ms

0

0

1

Delay Time 1

9ms

27ms

0

1

0

Delay Time 2

10ms

28ms

0

1

1

Delay Time 3

12ms

30ms

1

0

0

Delay Time 4

17ms

35ms

1

0

1

Delay Time 5

26ms

44ms

1

1

0

Delay Time 6

43ms

61ms

1

1

1

Delay Time 7

78ms

96ms

Publication 1794-6.5.5 - October 1996

Page 27

2–10

How Communication Takes Place and I/O Image Table Mapping

8-point Discrete Output Module (1794-OA8) Image Table Mapping I/O Image Read

Input Size

Module Image

0 or 1 Word

Not used

Output Size Write

Not used

Outputs

1 or 2 Words

Not used

Memory Map of 8-point Discrete Output Module Image Table – 1794-OA8 Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Oct. Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Size

Not used Not used

O7

Read Word 1 O6

O5

O4

O3

O2

O1

O0

Not used

Write Word 1 Write Word 2

Where O = Output value (where O0 corresponds to output 0, O1 corresponds to output 1, etc.)

8-point Discrete Relay Output Module (1794-OW8) Image Table Mapping I/O Image Read

Input Size

Module Image

0 or 1 Word

Not used

Output Size

Not used

1 or 2 Words

Write

Outputs Not used

Memory Map of 8-Point Discrete Relay Output Image Table – 1794-OW8 Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Oct. Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Not used Not used

O7 Not used

Size Read Word 1

O6

O5

O4

O3

O2

O1

O0

Write Word 1 Write Word 2

Where O = Output value: where O0 corresponds to output 0, O1 corresponds to output 1, etc., and when bit = 0, the output is off; when bit = 1, the output is on.