Preface
About This Manual Purpose
Use this manual to install and configure your Flex I/O DeviceNetTM Adapter, cat. no. 1794-ADN Series B.
Audience
We assume that you have previously used an Allen-Bradley programmable controller, that you are familiar with its features, and that you are familiar with the terminology we use. If not, read the user manual for your processor before reading this manual. In addition, you must be familiar with:
• DeviceNet Manager Software, cat. no. 1787-MGR • Microsoft WindowsTM • Flex I/O system components
Vocabulary
In this manual, we refer to:
• the individual DeviceNet adapter module as the “adapter.” • the programmable controller as the “controller” or the “processor.”
What This Manual Contains
The contents of this manual are as follows: Chapter
Title
What's Covered
1
Overview of Flex I/O and Your DeviceNet Adapter
Describes features, capabilities, and hardware components.
2
How Communication Takes Place and I/O Mapping
Describes communication over the I/O backplane between the modules and the adapter, and how data is mapped into the image table.
3
Configuring Your DeviceNet Adapter Offline
Describes how to configure the adapter when in the offline mode.
4
Configuring Your DeviceNet Adapter Online
Describes how to configure the adapter when in the online mode.
5
Troubleshooting
Explains how to use the indicators for troubleshooting.
Specifications
Adapter specifications
Appendix A
1794-6.5.5 - October 1996
Page 9
SP–2
About This Manual
Conventions
We use these conventions in this manual: In this manual, we show:
Like this:
that there is more information about a topic in another chapter in this manual that there is more information about the topic in another manual
Related Publications
1794-6.5.5 - October 1996
More
For additional information on planning and installing your DeviceNet system, and Flex I/O modules, see the following publications: Publication
Publication Number
DeviceNet Manager Software User Manual
1787-6.5.3
Scanner Configuration Manual (cat. no. 1771-SDN)
1771-6.5.118
Industrial Automation Wiring and Grounding Guidelines
1770-4.1
Flex I/O Product Data
1794-2.1
16 Source Output Module, Cat. No. 1794-OB16
1794-5.3
16 Sink Input Module, Cat. No. 1794-IB16
1794-5.4
4 Output Analog Module, Cat. No. 1794-OE4
1794-5.5
8 Input Analog Module, Cat. No. 1794-IE8
1794-5.6
8 Sensor Input Module, Cat. No. 1794-IB8S
1794-5.7
8 Input Module, Cat. No. 1794-IA8
1794-5.9
8 Output Module, Cat. No. 1794-OA8
1794-5.10
4 in/2 out Analog Combo Module, Cat. No. 1794-IE4XOE2
1794-5.15
8 Relay Output Module, Cat. No. 1794-OW8
1794-5.19
Thermocouple/mV Input Module, Cat. No. 1794-IT8
1794-5.21
10 Input/6 Output Module, Cat. No. 1794-IB10XOB6
1794-5.24
RTD 8 Input Analog Module, Cat. No. 1794-IR8
1794-5.22
SCANport Module, Cat. No. 1203-FM1
1203-5.8
Page 10
Chapter
1
Installing Your DeviceNet Adapter Module Chapter Objectives
This chapter describes the FLEX I/O system, the DeviceNet Adapter and the procedures for installing your DeviceNet adapter module. These include:
• • • • • •
Compliance to European Union Directives
European Union Directives the FLEX I/O system power requirements mounting the remote I/O adapter setting the module switches connecting the wiring
If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file: • EN 50081-2EMC – Generic Emission Standard, Part 2 – Industrial Environment • EN 50082-2EMC – Generic Immunity Standard, Part 2 – Industrial Environment This product is intended for use in an industrial environment.
Low Voltage Directive This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131–2 Programmable Controllers, Part 2 – Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications: • Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1 • Guidelines for Handling Lithium Batteries, publication AG-5.4 • Automation Systems Catalog, publication B111
Publication 1794-6.5.5 - October 1996
Page 11
1–2
Installing Your DeviceNet Adapter Module
The FLEX I/O System
FLEX I/O is a small, modular I/O system for distributed applications that performs all of the functions of rack-based I/O. The FLEX I/O system contains the following components as shown below:
Adapter/Power Supply
Terminal Base
I/O Module
20125
• DeviceNet adapter/power supply – powers the internal logic for as many as eight I/O modules • terminal base – contains a terminal strip to terminate wiring for two- or three-wire devices • I/O module – contains the bus interface and circuitry needed to perform specific functions related to your application For information on how communication occurs on the Flex I/O system backplane, refer to Chapter 2.
DeviceNet Adapter Components
The adapter module consists of the following major components:
• • • • diagnostic indicators DeviceNet wiring connections 24V dc power wiring connections Node address switch
Power Indicator I/O Status Indicator Mod/Net Status Indicator
DeviceNet Wiring Diagram DeviceNet Connector
Publication 1794-6.5.5 - October 1996
Node Address Thumbwheel Switch 24V dc Common Wiring Connections +24V dc Wiring Connections
Page 12
Installing Your DeviceNet Adapter Module
1–3
Diagnostic Indicators Diagnostic indicators are located on the front panel of the adapter module. They show both normal operation and error conditions in your remote I/O system. The indicators are: Mod/Net status I/O status A complete description of the diagnostic indicators and how to use them for troubleshooting is explained in Chapter 5.
Power Requirements
Mounting the DeviceNet Adapter
The DeviceNet adapter module requires a current of 400mA at 24V dc from an external power supply for Flex bus operation This is sufficient to support one logical rack (8 modules). Remember to add this amount to current requirements for other modules using the same 24V supply.
The DeviceNet adapter module can be DIN rail or wall/panel mounted. Refer to the specific method of mounting below.
Mounting on the DIN Rail A B
C 1. Position the adapter module A on a 35 x 7.5mm DIN rail B (A-B pt. no. 199-DR1; 46277-3; EN 50022) at a slight angle. 2. Rotate the adapter module onto the DIN rail with the top of the rail hooked under the lip on the rear of the adapter module.
Publication 1794-6.5.5 - October 1996
Page 13
1–4
Installing Your DeviceNet Adapter Module
3. Press the adapter module down onto the DIN rail until flush. Locking tab (C) will snap into position and lock the adapter module to the DIN rail. 4. If the adapter module does not lock in place, use a screwdriver or similar device to move the locking tab down while pressing the adapter module flush onto the DIN rail and release the locking tab to lock the adapter module in place. If necessary, push up on the locking tab to lock. 5. Connect the adapter wiring as shown under “Wiring” later in this document. Important:
More
Make certain that the DIN rail is properly grounded to the panel. Refer to “Industrial Automation Wiring and Grounding Guidelines,” publication 1770-4.1.
Mounting on a Wall or Panel To mount the remote I/O adapter module on a wall or panel, you must have the 1794-NM1 mounting kit. The kit contains a special plate and screws necessary for wall/panel mounting. Proceed as follows: Install the mounting plate on a wall or panel as follows: 1. Lay out the required points on the wall/panel as shown in the drilling dimension drawing. Inches (Millimeters)
A 1.4 (35)
1.4 (35)
2.3 (59)
3.7 (94)
0.9 (23)
.83 (21) 2.0 (50)
3.2 (80)
3.7 (94) 3.2 (80)
3.4 (87)
1.2 (30) 2.7 (68) 1794 Adapters 3.4H x 2.7W x 2.7D (87H x 68W x 69D)
Publication 1794-6.5.5 - October 1996
3.7 (94) 1794 Terminal Base Units 3.7H x 3.7W x 2.7D (94H x 94W x 69D)
A = Mounting hole dimensions for optional mounting kit
Page 14
Installing Your DeviceNet Adapter Module
1–5
2. Drill the necessary holes for #6 self-tapping mounting screws. 3. Mount the mounting plate (1) for the adapter module using two #6 self-tapping screws (18 included). Important:
More
Make certain that the mounting plate is properly grounded to the panel. Refer to “Industrial Automation Wiring and Grounding Guidelines,” publication 1770-4.1. 1.4 (35.5)
1 - Adapter Mounting Plate 2 - DeviceNet Adapter Module
Mounting Screws (18) 2 for the mounting plate and 2 each for the 8 possible modules
4. Hold the adapter (2) at an angle and engage the top of the mounting plate in the indention on the rear of the adapter module. 5. Press the module down flush with the panel until the locking lever locks. 6. Position the termination base unit up against the adapter and push the female bus connector into the adapter. 7. Secure to the wall with two #6 self-tapping screws. 8. Repeat for each remaining terminal base unit. Note: The adapter is capable of addressing eight modules. Do not exceed a maximum of eight terminal base units in your system.
Publication 1794-6.5.5 - October 1996
Page 15
1–6
Installing Your DeviceNet Adapter Module
Setting the Network Address Switch
Set the network address using the 2-position thumbwheel switch. Valid settings range from 00 to 63. Press either the + or – buttons to change the number.
Network Address Switches
Note: The baud rate for the adapter is set by way of “baud detection” at power-up. The setting of the network address cannot be changed using the DeviceNet configuration software (DeviceNet Manager).
Publication 1794-6.5.5 - October 1996
Page 16
Installing Your DeviceNet Adapter Module
Wiring
1–7
Connect external wiring to the DeviceNet adapter as shown below.
D
F COM
E
G
24V
DeviceNet Connector
20131
1. Connect the DeviceNet cable to the removable connector as shown. Connect
To
BLK Wire
-V
BLU Wire
CAN* Low
Bare Wire
Drain
WHT Wire
CAN High
RED Wire
+V
CAN = Controller Area Network
NOTE: Cable colors are shown on the wiring label on the front of the module. 2. Insert connector into mating connector on DeviceNet adapter module. 3. Connect +24V dc input to the left side of the lower connector E. 4. Connect 24V common to the left side of the upper connector D. 5. Connections G and F are used to pass 24V dc power (G) and 24V common (F) to the next module in the series (if required). For example:
Daisy-chaining
24V dc
Wiring when total current draw is less than 10A
Publication 1794-6.5.5 - October 1996
Page 17
1–8
Installing Your DeviceNet Adapter Module
Chapter Summary
Publication 1794-6.5.5 - October 1996
In this chapter you learned about the FLEX I/O system, how to install your DeviceNet adapter module and set your switches. Chapter 2 tells you how to communicate with your system.