For the Allen-Bradley 1794-ADN
Page 38
How Communication Takes Place and I/O Image Table Mapping
Word
Dec. Bits (Octal Bits)
Write word 1
00-01
2–21
Description Module Data Type Bit
01
00
0
0 oC (default)
0
1 oF
1
0
Bipolar counts scaled between -32768 and +32767
1
1
Unipolar counts scaled between 0 and 65535
02
Ehanced mode select - measures voltage drop across a precision resistor in the module to compare with the unknown input.
03-05
A/D Filter First Notch Frequency Bit
05
04
03
Definition
0
0
0
10Hz (default)
0
0
1
25Hz
0
1
0
50Hz
0
1
1
60Hz
1
0
0
100Hz
1
0
1
250Hz
1
1
0
500Hz
1
1
1
1000hZ
06
Calibration High/Low bit - This bit is set during gain calibration; reset during offset calibration.
07
Calibration clock - this bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to initiate calibration.
08-15
Calibration mask - The channel, or channels, to be calibrated will have the correct mask bit set. Bit 0 corresponds to channel 0, bit 1 to channel 1, and so on.
Publication 1794-6.5.5 - October 1996
Page 39
2–22
How Communication Takes Place and I/O Image Table Mapping
Word
Dec. Bits (Octal Bits)
Write Word 2
00-03
Description Channel 0 RTD Type Bit
03
02
01
00
RTD Type - Range
0
0
0
0
Resistance (default)
0
0
0
1
No sensor connected - do not scan
0
0
1
0
100 ohm Pt α = 0.00385 Euro (-200 to +870oC)
0
0
1
1
100 ohm Pt α = 0.003916 U.S. (-200 to +630oC)
0
1
0
0
200 ohm Pt α = 0.00385 (-200 to +630oC)
0
1
0
1
500 ohm Pt α = 0.00385 (-200 to +630oC)
0
1
1
0
Reserved
0
1
1
1
10 ohm Copper (-200 to +260oC)
1
0
0
0
120 ohm Nickel (-60 to +250oC)
1
0
0
1
100 ohm Nickel (-60 to +250oC)
1
0
1
0
200 ohm Nickel (-60 to +250oC)
1
0
1
1
500 ohm Nickel (-60 to +250oC)
1
1
0
0
Module data time stamp
1101 to 1111 - Reserved
Write Word 3
04-07
Channel 1 RTD Type (see bits 00-03)
08-11
Channel 2 RTD Type (see bits 00-03)
12-15
Channel 3 RTD Type (see bits 00-03)
00-03
Channel 4 RTD Type (see write word 2, bits 00-03)
04-07
Channel 5 RTD Type (see write word 2, bits 00-03)
08-11
Channel 6 RTD Type (see write word 2, bits 00-03)
12-15
Channel 7 RTD Type (see write word 2, bits 00-03)
Publication 1794-6.5.5 - October 1996
Page 40
How Communication Takes Place and I/O Image Table Mapping
2–23
Thermocouple Input Module (1794-IT8) Image Table Mapping Module Image Reserved Input Data Channel 0 Input Data Channel 1
I/O Image
Input Data Channel 2
Input Size
Input Data Channel 3
1 to 11 Words
Input Data Channel 4 Input Data Channel 5 Input Data Channel 6 Input Data Channel 7 Overrange
Underrange Calibration Status
Output Size
Configuration
Calibration Mask
0 to 3 Words
Thermocouple Type Thermocouple Type
Thermocouple Input Module (1794-IT8) Read Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
CJC over
CJC Under
Read Word 1
Reserved
Read Word 2
Channel 0 Input Data
Read Word 3
Channel 1 Input Data
Read Word 4
Channel 2 Input Data
Read Word 5
Channel 3 Input Data
Read Word 6
Channel 4 Input Data
Read Word 7
Channel 5 Input Data
Read Word 8
Channel 6 Input Data
Read Word 9
Channel 7 Input Data
Read Word 10 Read Word 11
Overrange Bits 0
0
0
0
0
Bad Cal
Underrange Bits Cal Done
Cal Range
0
Diagnostics
Pwr Up
Bad Structure
Publication 1794-6.5.5 - October 1996
Page 41
2–24
How Communication Takes Place and I/O Image Table Mapping
Thermocouple Input Module (1794-IT8) Write Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Cal Clk
Cal hi Cal lo
FDF
Data Type
Write Word 1
8-Bit Calibration Mask
Filter Cutoff
Write Word 2
Thermocouple 3 Type
Thermocouple 2 Type
Thermocouple 1 Type
Thermocouple 0 Type
Write Word 3
Thermocouple 7 Type
Thermocouple 6 Type
Thermocouple 5 Type
Thermocouple 4 Type
Where:
FDF = fixed digital filter bit
Word/Bit Descriptions for the 1794-IT8 Thermocouple Input Module Word
Decimal Bit (Octal Bit)
Read Word 1
00-15 (00-17)
Reserved
Read Word 2
00-15 (00-17)
Channel 0 Input data
Read Word 3
00-15 (00-17)
Channel 1 Input data
Read Word 4
00-15 (00-17)
Channel 2 Input data
Read Word 5
00-15 (00-17)
Channel 3 Input data
Read Word 6
00-15 (00-17)
Channel 4 Input data
Read Word 7
00-15 (00-17)
Channel 5 Input data
Read Word 8
00-15 (00-17)
Channel 6 Input data
Read Word 9
00-15 (00-17)
Channel 7 Input data
Read Word 10
00-07 (00-07)
Underrange bits - these bits are set if the input signal is below the input channel's minimum range.
08-15 (10-17)
Overrange bits - these bits are set if 1), the input signal is above the input channel's maximum range, or 2), an open detector is detected.
Read Word 11
Description
00 (00)
Cold Junction sensor underrange bit. - this bit is set if the cold junction temperature is below 0oC.
01 (01)
Cold Junction sensor overrange bit. - this bit is set if the cold junction temperature is above 70oC.
02 (02)
Bad Structure - this bit is set if there is an invalid thermocouple type selected.
03 (03)
Powerup bit - this bit is set (1) until configuration data is received by the module.
04-06 (04-06)
Critical Fault bits - If these bits are anything other than zero, return the module to the factory for repair.
07 (07)
Unused - set to 0
08 (10)
Calibration Range bit - set to 1 if a reference signal is out of range during calibration
09 (11)
Calibration Done bit - set to 1 after an initiated calibration cycle is complete.
10 (12)
Calibration Bad bit - set to 1 if the channel has not had a valid calibration.
11-15 (13-17)
Publication 1794-6.5.5 - October 1996
Unused - set to 0
Page 42
How Communication Takes Place and I/O Image Table Mapping
Word
Decimal Bit (Octal Bit)
Write Word 1
00-01 (00-01)
Description Module Data Type Bit
Bit 02 (02) 03-05 (03-05)
2–25
01
00
Definition
0
0 oC (default)
0
1 oF
1
0
Bipolar counts scaled between -32768 and +32767
1
1
Unipolar counts scaled between 0 and 65535
Fixed Digital Filter - When this bit is set (1), a software digital filter is enabled. This filter settles to 100% of a Full Scale step input in 60 scans. A/D Filter First Notch Frequency Bit
05
04
03
Definition
0
0
0
10Hz (default)
0
0
1
25Hz
0
1
0
50Hz
0
1
1
60Hz
1
0
0
100Hz
1
0
1
250Hz
1
1
0
500Hz
1
1
1
1000hZ
06 (06)
Calibration High/Low bit - This bit is set during gain calibration; reset during offset calibration.
07 (07)
Calibration clock - this bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to initiate calibration.
08-15 (10-17)
Calibration mask - The channel, or channels, to be calibrated will have the correct mask bit set. Bit 8 corresponds to channel 0, bit 9 to channel 1, and so on.
Publication 1794-6.5.5 - October 1996
Page 43
2–26
How Communication Takes Place and I/O Image Table Mapping
Word
Decimal Bit (Octal Bit)
Write Word 2
00-03 (00-03)
Description Channel 0 Thermocouple Type Bit
Write Word 3
03
02
01
00
Thermocouple Type - Range
0
0
0
0
Millivolts (default)
0
0
0
1
B
300 to 1800oC
0
0
1
0
E
-270 to 1000oC (-454 to 1832oF)
0
0
1
1
J
-210 to 1200oC (-346 to 2192oF)
0
1
0
0
K
-71 to 1372oC
(-95 to 2502oF)
0
1
0
1
R
-50 to 1768oC
(-58 to 3214oF)
0
1
1
0
S
-50 to 1768oC
(-58 to 3214oF)
0
1
1
1
T
-73 to 400oC
(-99 to 752oF)
1
0
0
0
C
0 to 2315oC
(32 to 4199oF)
1
0
0
1
N
-270 to 1300oC (-450 to 2372oF)
1
0
1
0
Reserved
1
0
1
1
Reserved
1
1
0
0
Module reports cold junction temperature for channels 00-03
1
1
0
1
Module reports cold junction temperature for channels 04-07
1
1
1
0
Reserved
1
1
1
1
No sensor connected (do not scan)
04-07 (04-07)
Channel 1 Thermocouple Type (see bits 00-03)
08-11 (10-13)
Channel 2 Thermocouple Type (see bits 00-03)
12-15 (14-17)
Channel 3 Thermocouple Type (see bits 00-03)
00-03 (00-03)
Channel 4 Thermocouple Type (see write word 2, bits 00-03)
04-07 (04-07)
Channel 5 Thermocouple Type (see write word 2, bits 00-03)
08-11 (10-13)
Channel 6 Thermocouple Type (see write word 2, bits 00-03)
12-15 (14-17)
Channel 7 Thermocouple Type (see write word 2, bits 00-03)
Publication 1794-6.5.5 - October 1996
(572 to 3272oF)
Page 44
How Communication Takes Place and I/O Image Table Mapping
2–27
SCANport Module (1203-FM) Image Table Mapping Module Image
I/O Image
Reserved
Input Size
Connection Status Channel 2
6 Words
Read
Connection Status Channel 1
Logic Status Channel 1 Analog Feedback Channel 1 Logic Status Channel 2 Analog Feedback Channel 2 Connection Enable Channel 2
Connection Enable Channel 1
Logic Command Channel 1 Write
Output Size
Analog Reference Channel 1
5 Words
Logic Command Channel 2 Analog Reference Channel 2 Not used Not used Not used Not used
Memory Map of SCANport Module Image Table – 1203-FM Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read Word 1
Reserved
Read Word 2
Connection Status Channel 2
Connection Status Channel 1
Read Word 3
Logic Status Channel 1
Read Word 4
Analog Feedback Channel 1
Read Word 5
Logic Status Channel 2
Read Word 6
Analog Feedback Channel 2
Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Oct. Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Write Word 1
Connection Enable Channel 2
Connection Enable Channel 2
Write Word 2
Logic Command Channel 1
Write Word 3
Analog Reference Channel 1
Write Word 4
Logic Command Channel 2
Write Word 5
Analog Reference Channel 2
Publication 1794-6.5.5 - October 1996
Page 45
2–28
How Communication Takes Place and I/O Image Table Mapping
Defaults
Each I/O module has default values associated with it. At default, each module will generate inputs/status and expect outputs/configuration. Module Defaults for:
Factory Defaults
Real Time Sizes
Input Default
Output Default
Input Default
Output Default
Catalog Number
Description
1794-IB16
16-pt 24V dc Sink Input
1
1
1
0
1794-OB16
16-pt 24V dc Source Output
1
1
0
1
1794-IB10XOB6
10 Input/6 Output
1
1
1
1
1794-IA8
8-pt 120V ac Input
1
1
1
0
1794-OA8
8-pt 120V ac Output
1
1
0
1
1794-IB8S
8-pt 24V dc Sensor Input
1
1
1
0
1794-OW8
8-pt Relay Output
1
1
0
1
1794-IE8
8-pt Analog Input
9
6
8
0
1794-OE4
4-pt Analog Output
1
14
0
4
1794-IE4XOE2
4 in/2 out Analog Combo
5
10
4
2
1794-IR8
8-pt RTD Analog Input
11
4
10
0
1794-IT8
8-pt Thermocouple Input
11
4
10
0
1794-OB8EP
8-pt 24V dc Electrically Fused Source Output
1
1
0
1
1203-FM1
SCANport Module
6
5
6
5
Factory defaults are the values assigned by the adapter when you:
• first power up the system, and • no previous stored settings have been applied. For discrete modules, these “automatic” default sizes are 1 input word/1 output word. These values are used for defaults instead of the maximum of 2 read/1 write or and 1 read/2 write. For analog modules, the defaults reflect the maximum number of read words/write words. For example, for the 8 input analog module, you have 9 input words and 6 output words, which is a combination of inputs/status and outputs/configuration. You can change the I/O data size for a module by reducing the number of words mapped into the adapter module, as shown in real time sizes. Real time sizes are the settings that provide optimal real time data to and from the I/O module. You need a software configuration tool to change the size.
Publication 1794-6.5.5 - October 1996
Page 46
How Communication Takes Place and I/O Image Table Mapping
2–29
The real time settings provide the fastest network time by only mapping input data and output data for the I/O modules. If you reduce your data sizes to only include real time data, you can only change your configuration data with a software tool. If you need to change configuration information on a real time basis, your data size must be large enough to include the necessary words. For information on using DeviceNetManager software to configure your adapter, refer to chapter 3, “Configuring Your DeviceNet Adapter Offline,” and chapter 4, “Configuring Your DeviceNet Adapter Online.”
More
For additional information on FLEX I/O modules, refer to the following publications. Module Description
Catalog Number
For Additional Information: Installation User Manual
16 Sink Input Module
1794-IB16
1794-5.4
16 Source Output Module
1794-OB16
1794-5.3
10 Input/6 Output Module
1794-IB10XOB6
1794-5.24
8 Electronically Fused Output Module
1794-OB8EP
1794-5.20
8 Sensor Input Module
1794-IB8S
1794-5.7
8 Input Module
1794-IA8
1794-5.9
8 Output Module
1794-OA8
1794-5.10
8 Relay Output Module
1794-OW8
1794-5.19
8 Input Analog Module
1794-IE8
1794-5.6
4 Output Analog Module
1794-OE4
1794-5.5
4 in/2 out Analog Combo Module
1794-IE4XOE2
1794-5.15
8 RTD Input Analog Module
1794-IR8
1794-5.22
1794-6.5.4
8 Thermocouople Input Module
1794-IT8
1794-5.21
1794-6.5.7
SCANport Module
1203-FM1
1203-5.8
1794-6.5.2
Publication 1794-6.5.5 - October 1996