For the Allen-Bradley 1794-ADN

Page 38

How Communication Takes Place and I/O Image Table Mapping

Word

Dec. Bits (Octal Bits)

Write word 1

00-01

2–21

Description Module Data Type Bit

01

00

0

0 oC (default)

0

1 oF

1

0

Bipolar counts scaled between -32768 and +32767

1

1

Unipolar counts scaled between 0 and 65535

02

Ehanced mode select - measures voltage drop across a precision resistor in the module to compare with the unknown input.

03-05

A/D Filter First Notch Frequency Bit

05

04

03

Definition

0

0

0

10Hz (default)

0

0

1

25Hz

0

1

0

50Hz

0

1

1

60Hz

1

0

0

100Hz

1

0

1

250Hz

1

1

0

500Hz

1

1

1

1000hZ

06

Calibration High/Low bit - This bit is set during gain calibration; reset during offset calibration.

07

Calibration clock - this bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to initiate calibration.

08-15

Calibration mask - The channel, or channels, to be calibrated will have the correct mask bit set. Bit 0 corresponds to channel 0, bit 1 to channel 1, and so on.

Publication 1794-6.5.5 - October 1996

Page 39

2–22

How Communication Takes Place and I/O Image Table Mapping

Word

Dec. Bits (Octal Bits)

Write Word 2

00-03

Description Channel 0 RTD Type Bit

03

02

01

00

RTD Type - Range

0

0

0

0

Resistance (default)

0

0

0

1

No sensor connected - do not scan

0

0

1

0

100 ohm Pt α = 0.00385 Euro (-200 to +870oC)

0

0

1

1

100 ohm Pt α = 0.003916 U.S. (-200 to +630oC)

0

1

0

0

200 ohm Pt α = 0.00385 (-200 to +630oC)

0

1

0

1

500 ohm Pt α = 0.00385 (-200 to +630oC)

0

1

1

0

Reserved

0

1

1

1

10 ohm Copper (-200 to +260oC)

1

0

0

0

120 ohm Nickel (-60 to +250oC)

1

0

0

1

100 ohm Nickel (-60 to +250oC)

1

0

1

0

200 ohm Nickel (-60 to +250oC)

1

0

1

1

500 ohm Nickel (-60 to +250oC)

1

1

0

0

Module data time stamp

1101 to 1111 - Reserved

Write Word 3

04-07

Channel 1 RTD Type (see bits 00-03)

08-11

Channel 2 RTD Type (see bits 00-03)

12-15

Channel 3 RTD Type (see bits 00-03)

00-03

Channel 4 RTD Type (see write word 2, bits 00-03)

04-07

Channel 5 RTD Type (see write word 2, bits 00-03)

08-11

Channel 6 RTD Type (see write word 2, bits 00-03)

12-15

Channel 7 RTD Type (see write word 2, bits 00-03)

Publication 1794-6.5.5 - October 1996

Page 40

How Communication Takes Place and I/O Image Table Mapping

2–23

Thermocouple Input Module (1794-IT8) Image Table Mapping Module Image Reserved Input Data Channel 0 Input Data Channel 1

I/O Image

Input Data Channel 2

Input Size

Input Data Channel 3

1 to 11 Words

Input Data Channel 4 Input Data Channel 5 Input Data Channel 6 Input Data Channel 7 Overrange

Underrange Calibration Status

Output Size

Configuration

Calibration Mask

0 to 3 Words

Thermocouple Type Thermocouple Type

Thermocouple Input Module (1794-IT8) Read Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

CJC over

CJC Under

Read Word 1

Reserved

Read Word 2

Channel 0 Input Data

Read Word 3

Channel 1 Input Data

Read Word 4

Channel 2 Input Data

Read Word 5

Channel 3 Input Data

Read Word 6

Channel 4 Input Data

Read Word 7

Channel 5 Input Data

Read Word 8

Channel 6 Input Data

Read Word 9

Channel 7 Input Data

Read Word 10 Read Word 11

Overrange Bits 0

0

0

0

0

Bad Cal

Underrange Bits Cal Done

Cal Range

0

Diagnostics

Pwr Up

Bad Structure

Publication 1794-6.5.5 - October 1996

Page 41

2–24

How Communication Takes Place and I/O Image Table Mapping

Thermocouple Input Module (1794-IT8) Write Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Cal Clk

Cal hi Cal lo

FDF

Data Type

Write Word 1

8-Bit Calibration Mask

Filter Cutoff

Write Word 2

Thermocouple 3 Type

Thermocouple 2 Type

Thermocouple 1 Type

Thermocouple 0 Type

Write Word 3

Thermocouple 7 Type

Thermocouple 6 Type

Thermocouple 5 Type

Thermocouple 4 Type

Where:

FDF = fixed digital filter bit

Word/Bit Descriptions for the 1794-IT8 Thermocouple Input Module Word

Decimal Bit (Octal Bit)

Read Word 1

00-15 (00-17)

Reserved

Read Word 2

00-15 (00-17)

Channel 0 Input data

Read Word 3

00-15 (00-17)

Channel 1 Input data

Read Word 4

00-15 (00-17)

Channel 2 Input data

Read Word 5

00-15 (00-17)

Channel 3 Input data

Read Word 6

00-15 (00-17)

Channel 4 Input data

Read Word 7

00-15 (00-17)

Channel 5 Input data

Read Word 8

00-15 (00-17)

Channel 6 Input data

Read Word 9

00-15 (00-17)

Channel 7 Input data

Read Word 10

00-07 (00-07)

Underrange bits - these bits are set if the input signal is below the input channel's minimum range.

08-15 (10-17)

Overrange bits - these bits are set if 1), the input signal is above the input channel's maximum range, or 2), an open detector is detected.

Read Word 11

Description

00 (00)

Cold Junction sensor underrange bit. - this bit is set if the cold junction temperature is below 0oC.

01 (01)

Cold Junction sensor overrange bit. - this bit is set if the cold junction temperature is above 70oC.

02 (02)

Bad Structure - this bit is set if there is an invalid thermocouple type selected.

03 (03)

Powerup bit - this bit is set (1) until configuration data is received by the module.

04-06 (04-06)

Critical Fault bits - If these bits are anything other than zero, return the module to the factory for repair.

07 (07)

Unused - set to 0

08 (10)

Calibration Range bit - set to 1 if a reference signal is out of range during calibration

09 (11)

Calibration Done bit - set to 1 after an initiated calibration cycle is complete.

10 (12)

Calibration Bad bit - set to 1 if the channel has not had a valid calibration.

11-15 (13-17)

Publication 1794-6.5.5 - October 1996

Unused - set to 0

Page 42

How Communication Takes Place and I/O Image Table Mapping

Word

Decimal Bit (Octal Bit)

Write Word 1

00-01 (00-01)

Description Module Data Type Bit

Bit 02 (02) 03-05 (03-05)

2–25

01

00

Definition

0

0 oC (default)

0

1 oF

1

0

Bipolar counts scaled between -32768 and +32767

1

1

Unipolar counts scaled between 0 and 65535

Fixed Digital Filter - When this bit is set (1), a software digital filter is enabled. This filter settles to 100% of a Full Scale step input in 60 scans. A/D Filter First Notch Frequency Bit

05

04

03

Definition

0

0

0

10Hz (default)

0

0

1

25Hz

0

1

0

50Hz

0

1

1

60Hz

1

0

0

100Hz

1

0

1

250Hz

1

1

0

500Hz

1

1

1

1000hZ

06 (06)

Calibration High/Low bit - This bit is set during gain calibration; reset during offset calibration.

07 (07)

Calibration clock - this bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to initiate calibration.

08-15 (10-17)

Calibration mask - The channel, or channels, to be calibrated will have the correct mask bit set. Bit 8 corresponds to channel 0, bit 9 to channel 1, and so on.

Publication 1794-6.5.5 - October 1996

Page 43

2–26

How Communication Takes Place and I/O Image Table Mapping

Word

Decimal Bit (Octal Bit)

Write Word 2

00-03 (00-03)

Description Channel 0 Thermocouple Type Bit

Write Word 3

03

02

01

00

Thermocouple Type - Range

0

0

0

0

Millivolts (default)

0

0

0

1

B

300 to 1800oC

0

0

1

0

E

-270 to 1000oC (-454 to 1832oF)

0

0

1

1

J

-210 to 1200oC (-346 to 2192oF)

0

1

0

0

K

-71 to 1372oC

(-95 to 2502oF)

0

1

0

1

R

-50 to 1768oC

(-58 to 3214oF)

0

1

1

0

S

-50 to 1768oC

(-58 to 3214oF)

0

1

1

1

T

-73 to 400oC

(-99 to 752oF)

1

0

0

0

C

0 to 2315oC

(32 to 4199oF)

1

0

0

1

N

-270 to 1300oC (-450 to 2372oF)

1

0

1

0

Reserved

1

0

1

1

Reserved

1

1

0

0

Module reports cold junction temperature for channels 00-03

1

1

0

1

Module reports cold junction temperature for channels 04-07

1

1

1

0

Reserved

1

1

1

1

No sensor connected (do not scan)

04-07 (04-07)

Channel 1 Thermocouple Type (see bits 00-03)

08-11 (10-13)

Channel 2 Thermocouple Type (see bits 00-03)

12-15 (14-17)

Channel 3 Thermocouple Type (see bits 00-03)

00-03 (00-03)

Channel 4 Thermocouple Type (see write word 2, bits 00-03)

04-07 (04-07)

Channel 5 Thermocouple Type (see write word 2, bits 00-03)

08-11 (10-13)

Channel 6 Thermocouple Type (see write word 2, bits 00-03)

12-15 (14-17)

Channel 7 Thermocouple Type (see write word 2, bits 00-03)

Publication 1794-6.5.5 - October 1996

(572 to 3272oF)

Page 44

How Communication Takes Place and I/O Image Table Mapping

2–27

SCANport Module (1203-FM) Image Table Mapping Module Image

I/O Image

Reserved

Input Size

Connection Status Channel 2

6 Words

Read

Connection Status Channel 1

Logic Status Channel 1 Analog Feedback Channel 1 Logic Status Channel 2 Analog Feedback Channel 2 Connection Enable Channel 2

Connection Enable Channel 1

Logic Command Channel 1 Write

Output Size

Analog Reference Channel 1

5 Words

Logic Command Channel 2 Analog Reference Channel 2 Not used Not used Not used Not used

Memory Map of SCANport Module Image Table – 1203-FM Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read Word 1

Reserved

Read Word 2

Connection Status Channel 2

Connection Status Channel 1

Read Word 3

Logic Status Channel 1

Read Word 4

Analog Feedback Channel 1

Read Word 5

Logic Status Channel 2

Read Word 6

Analog Feedback Channel 2

Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Oct. Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Write Word 1

Connection Enable Channel 2

Connection Enable Channel 2

Write Word 2

Logic Command Channel 1

Write Word 3

Analog Reference Channel 1

Write Word 4

Logic Command Channel 2

Write Word 5

Analog Reference Channel 2

Publication 1794-6.5.5 - October 1996

Page 45

2–28

How Communication Takes Place and I/O Image Table Mapping

Defaults

Each I/O module has default values associated with it. At default, each module will generate inputs/status and expect outputs/configuration. Module Defaults for:

Factory Defaults

Real Time Sizes

Input Default

Output Default

Input Default

Output Default

Catalog Number

Description

1794-IB16

16-pt 24V dc Sink Input

1

1

1

0

1794-OB16

16-pt 24V dc Source Output

1

1

0

1

1794-IB10XOB6

10 Input/6 Output

1

1

1

1

1794-IA8

8-pt 120V ac Input

1

1

1

0

1794-OA8

8-pt 120V ac Output

1

1

0

1

1794-IB8S

8-pt 24V dc Sensor Input

1

1

1

0

1794-OW8

8-pt Relay Output

1

1

0

1

1794-IE8

8-pt Analog Input

9

6

8

0

1794-OE4

4-pt Analog Output

1

14

0

4

1794-IE4XOE2

4 in/2 out Analog Combo

5

10

4

2

1794-IR8

8-pt RTD Analog Input

11

4

10

0

1794-IT8

8-pt Thermocouple Input

11

4

10

0

1794-OB8EP

8-pt 24V dc Electrically Fused Source Output

1

1

0

1

1203-FM1

SCANport Module

6

5

6

5

Factory defaults are the values assigned by the adapter when you:

• first power up the system, and • no previous stored settings have been applied. For discrete modules, these “automatic” default sizes are 1 input word/1 output word. These values are used for defaults instead of the maximum of 2 read/1 write or and 1 read/2 write. For analog modules, the defaults reflect the maximum number of read words/write words. For example, for the 8 input analog module, you have 9 input words and 6 output words, which is a combination of inputs/status and outputs/configuration. You can change the I/O data size for a module by reducing the number of words mapped into the adapter module, as shown in real time sizes. Real time sizes are the settings that provide optimal real time data to and from the I/O module. You need a software configuration tool to change the size.

Publication 1794-6.5.5 - October 1996

Page 46

How Communication Takes Place and I/O Image Table Mapping

2–29

The real time settings provide the fastest network time by only mapping input data and output data for the I/O modules. If you reduce your data sizes to only include real time data, you can only change your configuration data with a software tool. If you need to change configuration information on a real time basis, your data size must be large enough to include the necessary words. For information on using DeviceNetManager software to configure your adapter, refer to chapter 3, “Configuring Your DeviceNet Adapter Offline,” and chapter 4, “Configuring Your DeviceNet Adapter Online.”

More

For additional information on FLEX I/O modules, refer to the following publications. Module Description

Catalog Number

For Additional Information: Installation User Manual

16 Sink Input Module

1794-IB16

1794-5.4

16 Source Output Module

1794-OB16

1794-5.3

10 Input/6 Output Module

1794-IB10XOB6

1794-5.24

8 Electronically Fused Output Module

1794-OB8EP

1794-5.20

8 Sensor Input Module

1794-IB8S

1794-5.7

8 Input Module

1794-IA8

1794-5.9

8 Output Module

1794-OA8

1794-5.10

8 Relay Output Module

1794-OW8

1794-5.19

8 Input Analog Module

1794-IE8

1794-5.6

4 Output Analog Module

1794-OE4

1794-5.5

4 in/2 out Analog Combo Module

1794-IE4XOE2

1794-5.15

8 RTD Input Analog Module

1794-IR8

1794-5.22

1794-6.5.4

8 Thermocouople Input Module

1794-IT8

1794-5.21

1794-6.5.7

SCANport Module

1203-FM1

1203-5.8

1794-6.5.2

Publication 1794-6.5.5 - October 1996