Page 47

Chapter

3

Configuring Your DeviceNet Adapter Offline Chapter Objectives

In this chapter you will learn:

• how to use the DeviceNet Manager software to configure the adapter offline

About DeviceNet Manager

More

DeviceNet Manager is the software tool used to configure your Flex I/O DeviceNet adapter and its related modules. This software tool can be connected to the adapter via the DeviceNet network. You must know and understand how DeviceNet Manager works in order to add a device to the network. Refer to the DeviceNet Manager Software User Manual, publication 1787-6.5.3. In this chapter, we assume that you have established a network, and are adding a Flex I/O Adapter to your network.

Adding Your Flex I/O DeviceNet Adapter to the Network

To add the DeviceNet adapter to the network:

1. At the Network Screen, click on the device" button. 2. At the Device to Network" screen, click on adapter," and then click on the 1794-ADN in the product area (2a).

1 4

3. Select the device node address. 4. Click on the Device" button when you have selected your device. Add more devices as necessary.

3 2

2a

When you click on the “Add Device” button, you are given the opportunity to add additional devices to the network.

Publication 1794-6.5.5 - October 1996

Page 48

3–2

Configuring Your DeviceNet Adapter Offline

2 2 1. To add more devices to the network at this time, select a device and click on Device." You can also add devices lby highlighting the device and double-clicking on it. This will automatically increment the node number for each device added.

1

2. To return to the network screen, click on the cancel button, or click in the upper left corner of the screen.

After adding the adapter to the network, you must configure it. Return to the network screen. You have 2 choices:

• highlight the device, and click on the “Configure Device”button, or • double-click on the highlighted adapter to bring up the adapter configuration screen. If a configuration file exists, the screen will be populated with the selections in that file.

The 1794-ADN adapter configuration begins and ends on the configuration screen. This “home base” is the access point for each Flex I/O module directly connected to the adapter. This is also where you configure adapter actions, and select process configuration information.

Publication 1794-6.5.5 - October 1996

Page 49

Configuring Your DeviceNet Adapter Offline

Configuring Your Flex I/O Adapter and System Offline

3–3

You can determine the adapter configuration and system configuration for an adapter at a specific node address. The node address is assigned at the adapter using the thumbwheel switch.

1. Verify the node address for your adapter. You can't change the address on this screen.

1

2. You configure each module in your Flex I/O system here.

4

3. You configure the adapter run idle action, run fault action, idle fault action and module fault action. These settings determine how your adapter will respond to these conditions.

2

5

4. Use this button to load adapter configuration data from a file (a previously saved configuration).

3

5. The "save to file" dialog defaults to storing the information in the project/network directory and using the user defined filename or a default name of (node address).prf." From the Configuration screen, you can:

To:

set run fault action for the adapter

Reset outputs to zero, Hold outputs in last state, Use safe state output values set run idle action

Reset outputs to zero, Hold outputs in last state, Use safe state output values set idle fault action

Outputs remain in idle, Outputs go to fault state set module fault action

Zero inputs, Hold last value determine what module resides in each slot select from the list provided configure each module safe state data current/voltage for inputs/outputs delay times I/O data sizes load settings from a file click on from file" button save settings to a file click on to file" button view a summary of modules and read/write spaces configured click on summary" button clear all changes made to the screen and revert to original settings click on memory" button

Publication 1794-6.5.5 - October 1996

Page 50

3–4

Configuring Your DeviceNet Adapter Offline

Select your adapter options as shown in the following:

1. Select from the list box for each configuration option: a. run idle b. run fault c. idle fault d. module fault Use the button to show the settings for each option. 1

1a

1b

1c

1d

Publication 1794-6.5.5 - October 1996

Page 51

Configuring Your DeviceNet Adapter Offline

3–5

Configuring Your Adapter's Flex I/O System Configure your Flex I/O system by specifying the Flex I/O module that will reside in each slot. Remember, slot 0 is the closest slot to the adapter, and slot 7 is the furthest or last slot. 1. Click on the or on the list box for slot 0. A list of modules is displayed. Use the up/dwn arrows to view the entire list of modules. 1a 2. Use the up/down arrows to page thru the possible module selections. Select the desired module by clicking on that selection.

1

1a

2

Select the modules you want inserted into each slot in your Flex I/O system. In the example, the following selections were made:

1

2

Example This adapter example has all 8 slots filled with modules.

1. Click on the slot number in the column called Configure to select the module for that slot.

2. Note that you can click on the radio button to display the module selections by catalog number.

Publication 1794-6.5.5 - October 1996

Page 52

3–6

Configuring Your DeviceNet Adapter Offline

You can configure each module as you enter it, or fill the slots and go back and configure them one at a time. To configure a module, click on the slot number for that module.

Configure Slot 0 To configure the module in slot 0 of our example, you have the following selections: When you are off line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file. 1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection. Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more or less output/configuration words from the process.

4 1 5 2

3

2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen. 3. Set the delay time constant for each set of inputs by clicking on the text box and scrolling thru the settings. Delay settings range from 0.5ms to 64ms. 4. Click on the OK button to save your edits. 5. The for I/O only" button returns all I/O data size settings to the optimal I/O settings for this module.

Publication 1794-6.5.5 - October 1996

2a

Page 53

Configuring Your DeviceNet Adapter Offline

3–7

Configure Slot 1 The second module (slot 1) in the example is a 1794-IB16 input module. This module has the following selections: When you are off line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file. 1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection.

5 1 4

Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more or less output/configuration words from the process.

2 3

2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen. 3. Set the delay time constant for each set of inputs by clicking on the text box and scrolling thru the settings. Delay settings range from 0.5ms to 64ms. 4. The for I/O only" button returns all I/O data size settings to the optimal I/O settings for this module.

2a

5. Click on the OK button to save your edits.

Publication 1794-6.5.5 - October 1996

Page 54

3–8

Configuring Your DeviceNet Adapter Offline

Configure Slot 2 The third module (slot 2) in the example is a 1794-IB8S sensor input module. This module has the following selections: When you are off line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file. 1. To specify the number of input and output words, place the cursor in the box and backspace to delete and then enter the desired selection.

5 1

Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more or less output/configuration words from the process.

4 2 3

2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen. 3. Set the delay time constant for the inputs by clicking on the text box and scrolling thru the settings. Delay settings range from 0.5ms to 64ms. 4. The for I/O only" button returns all I/O data size settings to the optimal I/O settings for this module. 5. Click on the OK button to save your edits.

Publication 1794-6.5.5 - October 1996

2a