DeviceNet Adapter Module User Manual (Cat. No. 1794-ADN Series B): 3 - Configuring Your DeviceNet Adapter Offline, pages 55 to 62

Pages 55 to 62 of 96, from DeviceNet Adapter Module User Manual (Cat. No. 1794-ADN Series B)

The original document is the PDF (1.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1794-ADN

Page 55

Configuring Your DeviceNet Adapter Offline

3–9

Configure Slot 3 The fourth module (slot 3) in the example is a 1794-IE4XOE2 analog combo module. This module has the following selections: When you are off line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file.

1

6 5

1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection.

2 3

4

3

Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more or less output/configuration words from the process. 2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen.

4

3. Select the voltage/current for each analog input and output using the list box and up/down arrows for selection of each input and output. 4a 4. If desired, enter a value that the module outputs go to in the event of a communication failure if safe state is the action chosen in fault or idle action. You can select the radix (4a) to use for data entry by clicking on the desired radio button.

2a

5. The for I/O only" button returns all I/O data size settings to the optimal I/O settings for this module. 6. If you change the settings, when all selections are complete, click on the OK button.

Publication 1794-6.5.5 - October 1996

Page 56

3–10

Configuring Your DeviceNet Adapter Offline

Configure Slot 4 The fifth module (slot 4) in the example is a 1794-IE8 analog input module. This module has the following selections: When you are off-line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file. 1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection. Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more or less output/configuration words from the process. 2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen. 3. Select the voltage/current for each analog output using the list box for selection of each output. 4. The for I/O only" button returns all I/O data size settings to the optimal I/O settings for this module. 5. If you change the settings, when all selections are complete, click on the OK button.

Publication 1794-6.5.5 - October 1996

5

1

4 2

3

2a

Page 57

Configuring Your DeviceNet Adapter Offline

3–11

Configure Slot 5 The sixth module (slot 5) in the example is a 1794-IR8 RTD analog output module. This module has the following selections: When you are off line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file. 1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection. Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more output/configuration words from the process. 2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen. 3. Select the module data type by clicking on the list box. A list of types is displayed (3a). Click on the desired module data type to select. 4. Select the desired filter first notch frequency by clicking on the list box. A list of frequencies is displayed (4a). Select the desired frequency by clicking on that selection.

7

1 6 2 3 4

8

5

4a 3a

2a

5. Select the type of RTD for each channel using the list box for selection of each type. Click on the desired RTD to select. 6. The for I/O only" button returns all I/O data size settings to the optimal I/O settings for this module. 7. If you change the settings, when all selections are complete, click on the OK button. 8. This module has an enhanced mode of operation. In the enhanced mode, inputs are compared against a known, precision resistor to determine the value of the RTD. Since this is performed each scan, module throughput is decreased.

Publication 1794-6.5.5 - October 1996

Page 58

3–12

Configuring Your DeviceNet Adapter Offline

Configure Slot 6 The seventh module (slot 6) in the example is a 1794-OA8 output module. This module has the following selections: When you are off line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file. 1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection. Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more or less output/configuration words from the process. 2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen. 3. If desired, enter a value that the module outputs would go to in the event of a communication failure if safe state is the action chosen in the fault or idle action. You can select the radix to use for data entry by clicking on the desired radio button. 4. The for I/O only" button returns all I/O data size settings to the optimal I/O settings for this module. 5. If you change the settings, when all selections are complete, click on the OK button.

Publication 1794-6.5.5 - October 1996

5 1 4 2 3

2a

Page 59

Configuring Your DeviceNet Adapter Offline

3–13

Configure Slot 7 The eighth module (slot 7) in the example is a 1794-OB16 output module. This module has the following selections: When you are off line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file.

5

1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection. Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more or less output/configuration words from the process. 2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen. 3. If desired, enter a value that the module outputs would go to in the event of a communication failure if safe state is the action chosen in the fault or idle action. You can select the radix to use for data entry by clicking on the desired radio button.

1 4 2 3

2a

4. The for I/O only" button returns all I/O data size settings to the optimal I/O settings for this module. 5. If you change the settings, when all selections are complete, click on the OK button.

Additional modules not installed in this example, but included in your module selection, are:

• • • • •

1794-OW8 Relay Output module 1794-OE4 Four Output Analog module 1794-IT8 Eight Thermocouple Input module 1794-OB8EP Electronically Fused Eight Output module 1203-FM1 SCANport module Configuration screens for these modules are described below.

Publication 1794-6.5.5 - October 1996

Page 60

3–14

Configuring Your DeviceNet Adapter Offline

Configuration for 1794-OW8 Relay output module The following configuration screens are for the 1794-OW8 relay output module. When you are off-line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file.

5

1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection.

1 4

Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more or less output/configuration words from the process. 2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen. 3. If desired, enter a value that the module outputs would go to in the event of a communication failure if safe state is the action chosen in the fault or idle action. You can select the radix to use for data entry by clicking on the desired radio button. 4. The for I/O only" button returns all I/O data size settings to the optimal I/O settings for this module. 5. If you change the settings, when all selections are complete, click on the OK button.

Publication 1794-6.5.5 - October 1996

2 3

3a 2a

Page 61

Configuring Your DeviceNet Adapter Offline

3–15

Configuration for the 1794-OE4 Analog Output module The following configuration screen is for a 1794-OE4 analog output module. When you are off-line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file. 1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection. Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more or less output/configuration words from the process. 2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen. 3. If desired, enter a value that the module outputs go to in the event of a communication failure if safe state is the action chosen in the fault or idle action. You can select the radix to use for data entry by clicking on the desired radio button.

6

1 5

2 3

4

3a

2a

4. Select the voltage/current for each analog output using the list box for selection of each output. 5. The to I/O only" button returns all I/O data size settings to the optimal I/O settings for this module. 6. If you change the settings, when all selections are complete, click on the OK button.

Publication 1794-6.5.5 - October 1996

Page 62

3–16

Configuring Your DeviceNet Adapter Offline

Configuration for the 1794-IT8 Thermocouple Input module The following configuration screen is for a 1794-IT8 Thermocouple Input module. When you are off line, I/O data size comes up in a default mode.The default sizes are optimal settings. If you do a from file," the sizes are the stored sizes previously sent to file. 1. To specify the number of input and output words, place the cursor in the box and backspace to delete. Enter the desired selection. Changing the number of input (read) words generates the amount of input and status area mapped into adapter memory. Changing the amount of output (write words) causes the adapter to expect more output/configuration words from the process. 2. The Description" button brings up a screen (2a) which shows which input and output words are being used. Clicking on the boxes will automatically select the number of words used. After selection, click on the OK button to return to the module configuration screen. 3. Select the module data type by clicking on the list box. A list of types is displayed (3a). Click on the desired module data type to select.

1

7 6

2

3 8

4 5

5a 3a

4a

4. Select the desired filter first notch frequency by clicking on the list box. A list of frequencies is displayed (4a). Select the desired frequency by clicking on that selection. 5. Select the type of thermocouple for each channel using the list box for selection of each type. Click on the desired type to select. 6. The "set for I/O only" button returns all I/O data size settings to the optimal I/O settings for this module. 7. If you change the settings, when all selections are complete, click on the OK button. 8. This module has a fixed digital filter mode of operation. In this mode, a low pass (lag) digital filter is implemented in addition to the first notch filter.

Publication 1794-6.5.5 - October 1996

2a