FLEX I/O PROFIBUS Adapter (Cat. No. 1794-APB) User Manual, pages 68 to 71

Pages 68 to 71 of 90: 5 - Troubleshooting; A - Specifications

The original document is the PDF (924 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 1794-IB16

Page 68

Chapter

5

Troubleshooting What this Chapter Contains

In this chapter, we describe how to use the adapter’s indicators for troubleshooting.

Troubleshooting with the Indicators

Locate the two bi-color indicators on the front panel of the adapter. They show both normal operation and fault conditions in your Flex I/O PROFIBUS system. The indicators are:

• STATUS – this indicator provides device status • PROFIBUS – this indicator provides communication link status Use the following table to determine the indicator conditions and status.

STATUS Indicator Indication

STATUS indicator (green/red)

PROFIBUS indicator (green/red)

OFF Solid Green Flashing Red/OFF

Solid Red

Status No power Normal operation Recoverable fault – Flex I/O module bad – Incorrect Flex I/O module installed – Node address changed since power up Unrecoverable fault

PROFIBUS Indicator Indication OFF Solid Green Flashing Red/OFF

Solid Red

Status No power or no communication Data is being transmitted and recieved Recoverable fault – Invalid Send Parameter data – Invalid Check Configuration data Unrecoverable fault – Unable to communicate

Publication 1794-6.5.6 – April 1996

Page 69

5–2

Troubleshooting

Viewing Status from the Master’s Configuration Software

You can use read diagnostics to view status using the master’s configuration software. The adapter returns identification in response to the Read DP–Slave Diagnostic Information message. Read DP–Slave Diagnostics Information Message Ext_Diag_Data field (Length 9 bytes) Octet

Description

7 8 9 10

Device Related diagnostic header byte (05h) Revision – Minor Revision – Major Adapter Status Bit 0 – Node Address Changed Bits 1-7 – Reserved Node Address switch setting Identifier Related diagnostic header byte (44h) Identifier diagnostic bits1

11 12 13–15

1 One identifier bit for each logical module (adapter and each slot use two identifier bits). The bits set indicate a module fault.

Publication 1794-6.5.6 – April 1996

Page 70

Appendix

A

Specifications 1794-APB Flex I/O PROFIBUS Adapter Specifications I/O Capacity

8 modules

Input Voltage Rating

24V dc nominal

Input Voltage Range

19.2V to 31.2V dc (includes 5% ac ripple)

Communication Rate

All rates up to 1.5Mbit/s

Indicators

STATUS LED – red/grn PROFIBUS LED – red/grn

Flexbus Output Current

640mA maximum @ 5V dc

Isolation Voltage

100% tested at 850V dc for 1s between user power and flexbus

Power Consumption

400mA maximum from external 24V dc supply

Power Dissipation

7.68W maximum @ 19.2V dc

Thermal Dissipation

26 BTU/hr @ 19.2V dc

Environmental Conditions Operational Temperature Storage Temperature Relative Humidity Shock Operating Non-operating Vibration

0 to 55oC (32 to 131oF) –40 to 85oC (–40 to 185oF) 5 to 95% noncondensing 30 g peak acceleration, 11(+1)ms pulse width 50 g peak acceleration, 11(+1)ms pulse width Tested 5 g @ 10–500Hz per IEC 68-2-6

PROFIBUS Connector

9-pin D-shell

PROFIBUS Drop Cable

Standard Drop Cable

Power Conductors Wire Size Category Agency Certification (when product or packaging is marked)

12 gauge (4mm2) stranded maximum 3/64 inch (1.2mm) insulation max. 21 • UL listed • CSA certified • CSA Class I, Division 2 • IEC • JIS • FCC • PNO • CE marked for all applicable directives

1 Use this conductor category information for planning conductor routing. Refer to publication 1770-4.1,

“Industrial Automation Wiring and Grounding Guidelines.”

Publication 1794-6.5.6 – April 1996

Page 71

A–2

Device Data Base File

Publication 1785-6.5.15 – November 1995