Page 1 of FLEX I/O PROFIBUS Adapter (Cat. No. 1794-APB) User Manual

Manual · Allen-Bradley

FLEX I/O PROFIBUS Adapter (Cat. No. 1794-APB) User Manual

Manual90 pagesPDF 924 KB

User manual for the Allen-Bradley 1794-APB FLEX I/O PROFIBUS adapter, including image table mapping for the 1794-IB16 input module.

What this file really is

The old site listed this file as a manual for the Allen-Bradley 1794-IB16. This is the user manual for the 1794-APB FLEX I/O PROFIBUS adapter, not a 1794-IB16 manual; the 1794-IB16 appears only in its image table mapping.

Download the PDF924 KB

Filed under · 1 model

Filed under these models in the old catalog

Summary

What is in it

Allen-Bradley's user manual for installing and configuring the FLEX I/O PROFIBUS adapter, cat. no. 1794-APB. It describes the FLEX I/O system, backplane communication and how data from each FLEX I/O module (including the 1794-IB16 16-point discrete input module) is mapped into the image table, connecting and terminating the PROFIBUS DP network, master/slave configuration, troubleshooting with the indicators, adapter specifications and the device data base (GSD) file.

Its parts

  1. Preface
  2. Overview of FLEX I/O and Your PROFIBUS Adapter Module
  3. How Communication Takes Place and I/O Image Table Mapping
  4. Connect the Adapter to the PROFIBUS DP Network
  5. Configure the Adapter for Master/Slave Communication
  6. Troubleshooting
  7. Specifications
  8. Device Data Base File

From the manual

Key facts from this manual

Each line names its page in the PDF.

Allen-Bradley user manual (publication 1794-6.5.6, April 1996) for the 1794-APB FLEX I/O PROFIBUS adapter, which links up to eight FLEX I/O modules to a PROFIBUS DP master. The manual is about the adapter; it covers the 1794-IB16 16-point 24V dc sink input module only in its image table, delay time, module key and default tables. It explains mounting, network cabling and termination, configuration, troubleshooting and specifications.

Read for this summary: pages 1 to 5, 10 to 16, 21 to 23, 44 to 51, 56 and 68 to 70 of 90.

1794-IB16
1794-IB16: FLEX I/O 16-point 24V dc sink input module p. 21, 44
IB16 delay times
1794-IB16: input delay set for inputs 00-11 and 12-15: 512µs (default), 1, 2, 4, 8, 16, 32 or 64ms p. 23
IB16 image table
1794-IB16: input data D0 to D15 in read word 1; delay time settings in write word 1 p. 21, 22
IB16 module key
1794-IB16: module identification number 0281h (four-word module) p. 56
IB16 data sizes
1794-IB16: default 1 input and 1 output word; optimal 1 input and 0 output words p. 44
Adapter
1794-APB: PROFIBUS DP slave adapter for FLEX I/O, up to 8 modules p. 14, 70
Adapter power
1794-APB: 24V dc nominal, 19.2V to 31.2V dc, 400mA maximum p. 70
Flexbus current
1794-APB: 640mA maximum at 5V dc to the modules p. 70
Baud rates
9.6, 19.2, 93.75, 187.5, 500 Kbit/s and 1.5M bit/s p. 46, 70
Network
RS-485 shielded twisted pair, up to 32 stations, 100 to 1200m line length depending on baud rate and cable p. 46
Network connector
9-pin D-shell: shield pin 1, Signal + pin 3, Signal - pin 8 p. 16, 50
Node address
01 to 99, set with a 2-position thumbwheel switch p. 16
Accessories
1794-CE1 (0.3m) or -CE3 (0.9m) extender cable; 1794-NM1 panel mounting kit p. 11, 12
Configuration software
PROFIBUS Manager Software 1785-PFBMGR, required with a 1785-PFB/B coprocessor master p. 44

What this manual walks you through

  • Mounting a FLEX I/O system on DIN rail or panel p. 11, 12, 13
  • Setting the adapter node address p. 16
  • Mapping 1794-IB16 and other module data into the image table p. 21, 22, 23
  • Choosing line A or line B network cabling p. 46, 47, 48
  • Wiring the drop cable to the adapter p. 50
  • Terminating the PROFIBUS network p. 51
  • Entering module keys in the user parameter data p. 56
  • Troubleshooting with the STATUS and PROFIBUS indicators p. 68
  • Reading adapter diagnostics from the master software p. 69

Good to know

  • The extender cable goes only between I/O modules, never between the adapter and a module, and only one per system. p. 12
  • A changed node address takes effect only after the adapter is powered down and up again. p. 21
  • Allow a 1.0 in (25.4 mm) air gap on all four sides and secure the DIN rail every 200mm. p. 13
  • When line A and line B cable are combined, the maximum lengths are halved. p. 46

Questions this manual answers

What input delay times does the 1794-IB16 support?

512µs by default, or 1, 2, 4, 8, 16, 32 or 64ms, set separately for inputs 00-11 and 12-15. p. 23

What is the module key for the 1794-IB16 on PROFIBUS?

Its module identification number is 0281h. p. 56

How many FLEX I/O modules can the 1794-APB adapter handle?

Up to 8 modules. p. 70

What does a flashing red STATUS light on the 1794-APB mean?

A recoverable fault: a bad or wrong FLEX I/O module, or a node address changed since power up. p. 68

What baud rates does the 1794-APB support?

All PROFIBUS DP rates up to 1.5Mbit/s: 9.6, 19.2, 93.75, 187.5 and 500 Kbit/s and 1.5M bit/s. p. 46, 70

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1794-6.5.6, Allen-Bradley FLEX I/O PROFIBUS Adapter User Manual1
    1. Important User Information2
  2. Preface3
    1. Purpose3
    2. Vocabulary3
    3. What this Manual Contains3
    4. Related Publications4
    5. Conventions4
    6. Compliance to European Union Directives5
  3. 1 - Overview of FLEX I/O and Your PROFIBUS Adapter Module10
    1. What this Chapter Contains10
    2. The FLEX I/O System10
    3. Mount and Remove your System Easily11
    4. Optional Accessories11
    5. Mounting Dimensions and Spacing Requirements13
    6. Purpose of the 1794-APB FLEX I/ O Adapter14
    7. PROFIBUS Adapter Components15
  4. 2 - How Communication Takes Place and I/O Image Table Mapping18
    1. What this Chapter Contains18
    2. Communication Over the I/ O Backplane18
    3. Polled I/O Structure19
    4. Mapping Data into the Image Table21
    5. Defaults44
  5. 3 - Connecty the Adapter to the PROFIBUS DP Network46
    1. What this Chapter Contains46
    2. The DP Physical Layer46
    3. Cabling and Equipment Required for Line A Type47
    4. Cabling and Equipment Required for Line B Type48
    5. Connect the Adapter to the Network49
    6. Terminate the Network51
  6. 4 - Configure the Adapter for Master/Slave Communication52
    1. What this Chapter Contains52
    2. How Master/Slave Communication Takes Place52
    3. Entering User Parameter Data53
    4. Entering Check Configuration Data59
    5. Read Configuration Response Data61
    6. Configuration Example Using PROFIBUS Manager Software62
  7. 5 - Troubleshooting68
    1. What this Chapter Contains68
8 more lines, from page 68 on
  1. Troubleshooting with the Indicators68
    1. Viewing Status from the Master’s Configuration Software69
    2. What this Chapter Contains72
  2. A - Specifications70
  3. B - Device Data Base File72
    1. What this Chapter Contains72
  4. Glossary78
  5. Index86

From the PDF’s own bookmarks.

The whole text · 13 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 61-6
  2. Table of Contents7-9
  3. 1 - Overview of FLEX I/O and Your PROFIBUS Adapter Module10-17
  4. 2 - How Communication Takes Place and I/O Image Table Mapping, pages 18 to 2718-27
  5. 2 - How Communication Takes Place and I/O Image Table Mapping, pages 28 to 3728-37
  6. 2 - How Communication Takes Place and I/O Image Table Mapping, pages 38 to 4538-45
  7. 3 - Connecty the Adapter to the PROFIBUS DP Network46-51
  8. 4 - Configure the Adapter for Master/Slave Communication, pages 52 to 5952-59
  9. 4 - Configure the Adapter for Master/Slave Communication, pages 60 to 6760-67
  10. Pages 68 to 7168-71
  11. B - Device Data Base File72-77
  12. Glossary78-85
  13. Index86-90

The file

Revision and size

RevisionPublication 1794-6.5.6, April 1996
PublisherAllen-Bradley
Pages90
PDF924 KB
TextText from the PDF itself; page 1 is a scan, read by OCR, which may hold reading errors.

The first pages · 3 of 90

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 90
Page 2
Page 2of 90
Page 3
Page 3of 90