User manual for the Allen-Bradley 1794-APB FLEX I/O PROFIBUS adapter, including image table mapping for the 1794-IB16 input module.
What this file really is
The old site listed this file as a manual for the Allen-Bradley 1794-IB16. This is the user manual for the 1794-APB FLEX I/O PROFIBUS adapter, not a 1794-IB16 manual; the 1794-IB16 appears only in its image table mapping.
Filed under · 1 model
Filed under these models in the old catalog
Summary
What is in it
Allen-Bradley's user manual for installing and configuring the FLEX I/O PROFIBUS adapter, cat. no. 1794-APB. It describes the FLEX I/O system, backplane communication and how data from each FLEX I/O module (including the 1794-IB16 16-point discrete input module) is mapped into the image table, connecting and terminating the PROFIBUS DP network, master/slave configuration, troubleshooting with the indicators, adapter specifications and the device data base (GSD) file.
Its parts
- Preface
- Overview of FLEX I/O and Your PROFIBUS Adapter Module
- How Communication Takes Place and I/O Image Table Mapping
- Connect the Adapter to the PROFIBUS DP Network
- Configure the Adapter for Master/Slave Communication
- Troubleshooting
- Specifications
- Device Data Base File
From the manual
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley user manual (publication 1794-6.5.6, April 1996) for the 1794-APB FLEX I/O PROFIBUS adapter, which links up to eight FLEX I/O modules to a PROFIBUS DP master. The manual is about the adapter; it covers the 1794-IB16 16-point 24V dc sink input module only in its image table, delay time, module key and default tables. It explains mounting, network cabling and termination, configuration, troubleshooting and specifications.
- 1794-IB16
- 1794-IB16: FLEX I/O 16-point 24V dc sink input module p. 21, 44
- IB16 delay times
- 1794-IB16: input delay set for inputs 00-11 and 12-15: 512µs (default), 1, 2, 4, 8, 16, 32 or 64ms p. 23
- IB16 image table
- 1794-IB16: input data D0 to D15 in read word 1; delay time settings in write word 1 p. 21, 22
- IB16 module key
- 1794-IB16: module identification number 0281h (four-word module) p. 56
- IB16 data sizes
- 1794-IB16: default 1 input and 1 output word; optimal 1 input and 0 output words p. 44
- Adapter
- 1794-APB: PROFIBUS DP slave adapter for FLEX I/O, up to 8 modules p. 14, 70
- Adapter power
- 1794-APB: 24V dc nominal, 19.2V to 31.2V dc, 400mA maximum p. 70
- Flexbus current
- 1794-APB: 640mA maximum at 5V dc to the modules p. 70
- Baud rates
- 9.6, 19.2, 93.75, 187.5, 500 Kbit/s and 1.5M bit/s p. 46, 70
- Network
- RS-485 shielded twisted pair, up to 32 stations, 100 to 1200m line length depending on baud rate and cable p. 46
- Network connector
- 9-pin D-shell: shield pin 1, Signal + pin 3, Signal - pin 8 p. 16, 50
- Node address
- 01 to 99, set with a 2-position thumbwheel switch p. 16
- Accessories
- 1794-CE1 (0.3m) or -CE3 (0.9m) extender cable; 1794-NM1 panel mounting kit p. 11, 12
- Configuration software
- PROFIBUS Manager Software 1785-PFBMGR, required with a 1785-PFB/B coprocessor master p. 44
What this manual walks you through
- Mounting a FLEX I/O system on DIN rail or panel p. 11, 12, 13
- Setting the adapter node address p. 16
- Mapping 1794-IB16 and other module data into the image table p. 21, 22, 23
- Choosing line A or line B network cabling p. 46, 47, 48
- Wiring the drop cable to the adapter p. 50
- Terminating the PROFIBUS network p. 51
- Entering module keys in the user parameter data p. 56
- Troubleshooting with the STATUS and PROFIBUS indicators p. 68
- Reading adapter diagnostics from the master software p. 69
Good to know
- The extender cable goes only between I/O modules, never between the adapter and a module, and only one per system. p. 12
- A changed node address takes effect only after the adapter is powered down and up again. p. 21
- Allow a 1.0 in (25.4 mm) air gap on all four sides and secure the DIN rail every 200mm. p. 13
- When line A and line B cable are combined, the maximum lengths are halved. p. 46
Questions this manual answers
What input delay times does the 1794-IB16 support?
512µs by default, or 1, 2, 4, 8, 16, 32 or 64ms, set separately for inputs 00-11 and 12-15. p. 23
What is the module key for the 1794-IB16 on PROFIBUS?
Its module identification number is 0281h. p. 56
How many FLEX I/O modules can the 1794-APB adapter handle?
Up to 8 modules. p. 70
What does a flashing red STATUS light on the 1794-APB mean?
A recoverable fault: a bad or wrong FLEX I/O module, or a node address changed since power up. p. 68
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1794-6.5.6, Allen-Bradley FLEX I/O PROFIBUS Adapter User Manual1
- Preface3
- 1 - Overview of FLEX I/O and Your PROFIBUS Adapter Module10
- 2 - How Communication Takes Place and I/O Image Table Mapping18
- 3 - Connecty the Adapter to the PROFIBUS DP Network46
- 4 - Configure the Adapter for Master/Slave Communication52
- 5 - Troubleshooting68
The whole text · 13 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 61-6
- Table of Contents7-9
- 1 - Overview of FLEX I/O and Your PROFIBUS Adapter Module10-17
- 2 - How Communication Takes Place and I/O Image Table Mapping, pages 18 to 2718-27
- 2 - How Communication Takes Place and I/O Image Table Mapping, pages 28 to 3728-37
- 2 - How Communication Takes Place and I/O Image Table Mapping, pages 38 to 4538-45
- 3 - Connecty the Adapter to the PROFIBUS DP Network46-51
- 4 - Configure the Adapter for Master/Slave Communication, pages 52 to 5952-59
- 4 - Configure the Adapter for Master/Slave Communication, pages 60 to 6760-67
- Pages 68 to 7168-71
- B - Device Data Base File72-77
- Glossary78-85
- Index86-90