The text of a manual · part 6 of 13
FLEX I/O PROFIBUS Adapter (Cat. No. 1794-APB) User Manual: 2 - How Communication Takes Place and I/O Image Table Mapping, pages 38 to 45
Pages 38 to 45 of 90, from FLEX I/O PROFIBUS Adapter (Cat. No. 1794-APB) User Manual
The original document is the PDF (924 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1794-IB16
Page 38
How Communication Takes Place and I/O Image Table Mapping
2–21
1794-IT8 – Thermocouple Input Module Image Table Mapping Module Image Reserved Input Data Channel 0 Input Data Channel 1
I/O Image
Input Data Channel 2
Input Size
Input Data Channel 3
1 to 11 Words
Input Data Channel 4 Input Data Channel 5 Input Data Channel 6 Input Data Channel 7 Overrange
Underrange Calibration Status
Output Size Configuration
Calibration Mask
0 to 3 Words
Thermocouple Type Thermocouple Type
1794-IT8 Read Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
CJC over
CJC Under
Read Word 1
Reserved
Read Word 2
Channel 0 Input Data
Read Word 3
Channel 1 Input Data
Read Word 4
Channel 2 Input Data
Read Word 5
Channel 3 Input Data
Read Word 6
Channel 4 Input Data
Read Word 7
Channel 5 Input Data
Read Word 8
Channel 6 Input Data
Read Word 9
Channel 7 Input Data
Read Word 10 Read Word 11
Overrange Bits 0
0
0
0
0
Bad Cal
Underrange Bits Cal Done
Cal Range
0
Diagnostics
Pwr Up
Bad Structure
Publication 1794-6.5.6 – April 1996
Page 39
2–22
How Communication Takes Place and I/O Image Table Mapping
1794-IT8 Write Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Octal Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Cal Clk
Cal hi Cal lo
FDF
Data Type
Write Word 1
8-Bit Calibration Mask
Filter Cutoff
Write Word 2
Thermocouple 3 Type
Thermocouple 2 Type
Thermocouple 1 Type
Thermocouple 0 Type
Write Word 3
Thermocouple 7 Type
Thermocouple 6 Type
Thermocouple 5 Type
Thermocouple 4 Type
Where:
FDF = fixed digital filter bit
1794-IT8 Word/Bit Descriptions Word
Decimal Bit (Octal Bit)
Read Word 1
00–15 (00–17)
Reserved
Read Word 2
00–15 (00–17)
Channel 0 Input data
Read Word 3
00–15 (00–17)
Channel 1 Input data
Read Word 4
00–15 (00–17)
Channel 2 Input data
Read Word 5
00–15 (00–17)
Channel 3 Input data
Read Word 6
00–15 (00–17)
Channel 4 Input data
Read Word 7
00–15 (00–17)
Channel 5 Input data
Read Word 8
00–15 (00–17)
Channel 6 Input data
Read Word 9
00–15 (00–17)
Channel 7 Input data
Read Word 10
00–07 (00–07)
Underrange bits – these bits are set if the input signal is below the input channel’s minimum range.
08–15 (10–17)
Overrange bits – these bits are set if 1), the input signal is above the input channel’s maximum range, or 2), an open detector is detected.
Read Word 11
Description
00 (00)
Cold Junction sensor underrange bit. – this bit is set if the cold junction temperature is below 0oC.
01 (01)
Cold Junction sensor overrange bit. – this bit is set if the cold junction temperature is above 70oC.
02 (02)
Bad Structure – this bit is set if there is an invalid thermocouple type selected.
03 (03)
Powerup bit – this bit is set (1) until configuration data is received by the module.
04–06 (04–06)
Critical Fault bits – If these bits are anything other than zero, return the module to the factory for repair.
07 (07)
Unused – set to 0
08 (10)
Calibration Range bit – set to 1 if a reference signal is out of range during calibration
09 (11)
Calibration Done bit – set to 1 after an initiated calibration cycle is complete.
10 (12)
Calibration Bad bit – set to 1 if the channel has not had a valid calibration.
11–15 (13–17)
Publication 1794-6.5.6 – April 1996
Unused – set to 0
Page 40
How Communication Takes Place and I/O Image Table Mapping
Word
Decimal Bit (Octal Bit)
Write Word 1
00–01 (00–01)
Description Module Data Type Bit
Bit 02 (02) 03–05 (03–05)
2–23
01
00
Definition
0
0 oC (default)
0
1 oF
1
0
Bipolar counts scaled between –32768 and +32767
1
1
Unipolar counts scaled between 0 and 65535
Fixed Digital Filter – When this bit is set (1), a software digital filter is enabled. This filter settles to 100% of a Full Scale step input in 60 scans. A/D Filter First Notch Frequency Bit
05
04
03
Definition
0
0
0
10Hz (default)
0
0
1
25Hz
0
1
0
50Hz
0
1
1
60Hz
1
0
0
100Hz
1
0
1
250Hz
1
1
0
500Hz
1
1
1
1000hZ
06 (06)
Calibration High/Low bit – This bit is set during gain calibration; reset during offset calibration.
07 (07)
Calibration clock – this bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to initiate calibration.
08–15 (10–17)
Calibration mask – The channel, or channels, to be calibrated will have the correct mask bit set. Bit 8 corresponds to channel 0, bit 9 to channel 1, and so on.
Publication 1794-6.5.6 – April 1996
Page 41
2–24
How Communication Takes Place and I/O Image Table Mapping
Word
Decimal Bit (Octal Bit)
Write Word 2
00–03 (00–03)
Description Channel 0 Thermocouple Type Bit
Write Word 3
03
02
01
00
Thermocouple Type – Range
0
0
0
0
Millivolts (default)
0
0
0
1
B
300 to 1800oC
0
0
1
0
E
–270 to 1000oC (–454 to 1832oF)
0
0
1
1
J
–210 to 1200oC (–346 to 2192oF)
0
1
0
0
K
–71 to 1372oC
(–95 to 2502oF)
0
1
0
1
R
–50 to 1768oC
(–58 to 3214oF)
0
1
1
0
S
–50 to 1768oC
(–58 to 3214oF)
0
1
1
1
T
–73 to 400oC
(–99 to 752oF)
1
0
0
0
C
0 to 2315oC
(32 to 4199oF)
1
0
0
1
N
–270 to 1300oC (–450 to 2372oF)
1
0
1
0
Reserved
1
0
1
1
Reserved
1
1
0
0
Module reports cold junction temperature for channels 00–03
1
1
0
1
Module reports cold junction temperature for channels 04–07
1
1
1
0
Reserved
1
1
1
1
No sensor connected (do not scan)
04–07 (04–07)
Channel 1 Thermocouple Type (see bits 00–03)
08–11 (10–13)
Channel 2 Thermocouple Type (see bits 00–03)
12–15 (14–17)
Channel 3 Thermocouple Type (see bits 00–03)
00–03 (00–03)
Channel 4 Thermocouple Type (see word 13, bits 00–03)
04–07 (04–07)
Channel 5 Thermocouple Type (see word 13, bits 00–03)
08–11 (10–13)
Channel 6 Thermocouple Type (see word 13, bits 00–03)
12–15 (14–17)
Channel 7 Thermocouple Type (see word 13, bits 00–03)
Publication 1794-6.5.6 – April 1996
(572 to 3272oF)
Page 42
How Communication Takes Place and I/O Image Table Mapping
2–25
1203-FM1 – SCANport Module Image Table Mapping I/O Image
Module Image 0 Connection StatusChannel 2 Connection Status Channel 1
Read
Logic Status Channel 1
6 Words
Analog Feedback Channel 1 Logic Status Channel 2 Analog Feedback Channel 2 1 Word Connection Enable Channel 2
Connection Enable Channel 1
Write
Logic Command Channel 1
5 Words
Analog Reference Channel 1 Logic Command Channel 2 Analog Reference Channel 2 Not Used
Connection Status Word Definition Bit:
Connection Status Channel 2
Connection Status Channel 1
15 14 13 12 11 10 9
7
Not Used V2
ID2
8
6
5
Not Used
4
3
2
V1
1
0
ID1
Description
V1
SCANport channel 1 valid data bit. When high (1), the Logic Status and Analog Feedback values are valid and can be used. When low (0), the values should not be used.
ID1
SCANport channel 1 connected peripheral port ID number. This three bit field contains the port number that channel 1 is connected to on the SCANport device. It should contain a value between 1 and 7. If this field is 7, then the channel is not connected to the SCANport device, or the SCANport device may not be powered.
V2
SCANport channel 2 valid data bit. When high (1), the Logic Status and Analog Feedback values are valid and can be used. When low (0), the values should not be used.
ID2
SCANport channel 2 connected peripheral port ID number. This three bit field contains the port number that channel 2 is connected to on the SCANport device. It should contain a value between 1 and 7. If this field is 7, then the channel is not connected to the SCANport device, or the SCANport device may not be powered.
Logic Status/Analog Feedback Definition The Logic Status and Analog Feedback values are defined within the product manuals of the connected SCANport device(s).
Publication 1794-6.5.6 – April 1996
Page 43
2–26
How Communication Takes Place and I/O Image Table Mapping
Connection Enable Word Definition Bit:
Connection Enable Channel 2
Connection Enable Channel 1
15 14 13 12 11 10 9
8
7
Not Used
E2
6
5
4
3
Not Used
2
1
0
E1
Description
E1
SCANport channel 1 enable bit. When set to 1, the module will attempt to connect to the SCANport device. When reset to 0, the module stops communicating with the connected SCANport device. This usually causes the device to fault.
E2
SCANport channel 2 enable bit. When set to 1, the module will attempt to connect to the SCANport device. When reset to 0, the module stops communicating with the connected SCANport device. This usually causes the device to fault.
Logic Command/Analog Reference Definition The Logic Command and Analog Reference values are defined within the product manuals of the connected SCANport device(s).
Publication 1794-6.5.6 – April 1996
Page 44
How Communication Takes Place and I/O Image Table Mapping
Defaults
2–27
Each I/O module has default values associated with it. At default, each module will generate inputs/status and expect outputs/configuration. Module Defaults for:
Adapter Defaults
Optimal Sizes
Catalog Number
Description
Input Default
Output Default
Input Default
Output Default
1794-IB16
16-pt 24V dc Sink Input
1
1
1
0
1794-OB16
16-pt 24V dc Source Output
1
1
0
1
1794-IA8
8-pt 120V ac Input
1
1
1
0
1794-OA8
8-pt 120V ac Output
1
1
0
1
1794-IB8S
8-pt 24V dc Sensor Input
1
1
1
0
1794-OW8
8-pt Relay Output
1
1
0
1
1794-IE8
8-pt Analog Input
9
6
8
0
1794-OE4
4-pt Analog Output
1
14
0
4
1794-IE4XOE2
4 in/2 out Analog Combo
5
10
4
2
1794-IR8
8-pt RTD Analog Input
11
4
10
0
1794-IT8
8-pt Thermocouple Input
11
4
10
0
1203-FM1
SCANport Module
6
5
4
3
The default values reflect the maximum number of read/write words. You can change the I/O data size for a module by reducing the number of words mapped into the adapter module, as shown in optimal sizes.
PROFIBUS Manager Software Catalog Number 1785-PFBMGR
Optimal sizes are the settings that provide optimal data to and from the I/O module. You need a software configuration tool to change the size. If you are using the Allen-Bradley 1785-PFB/B coprocessor as a master, you must use the Allen-Bradley PROFIBUS Manager Software configuration tool. Since the FLEX I/O adapter is compatible with any master, you can use any comparable configuration tool available on the market. The optimal settings provide the fastest network time by only mapping read and write words used by the I/O modules. If you reduce your data sizes to only include optimal data, you can only change your configuration data with a software tool. If you need to change configuration information on an optimal basis, your data size must be large enough to include the necessary words.
More Information...
If you are using PROFIBUS Manager Software to configure your adapter, refer to your PROFIBUS Manager Software User Manual, publication 1785-6.5.20 for more information.
Publication 1794-6.5.6 – April 1996
Page 45
2–28
How Communication Takes Place and I/O Image Table Mapping
For additional information on FLEX I/O modules, refer to the following publications. Module Description
Publication 1794-6.5.6 – April 1996
Catalog Number
Installation Instructions
User Manual
16 Sink Input Module
1794-IB16
1794-5.4
16 Source Output Module
1794-OB16
1794-5.3
8 Sensor Input Module
1794-IB8S
1794-5.7
8 Input Module
1794-IA8
1794-5.9
8 Output Module
1794-OA8
1794-5.10
8 Relay Output Module
1794-OW8
1794-5.19
8 Input Analog Module
1794-IE8
1794-5.6
4 Output Analog Module
1794-OE4
1794-5.5
4 in/2 out Analog Combo Module
1794-IE4XOE2
1794-5.15
8 RTD Input Analog Module
1794-IR8
1794-5.22
1794-6.5.4
8 Thermocouple Input Module
1794-IT8
1794-5.21
1794-6.5.7
SCANport Module
1203-FM1
1203-5.8
1794-6.5.2