The text of a manual · part 5 of 13
FLEX I/O PROFIBUS Adapter (Cat. No. 1794-APB) User Manual: 2 - How Communication Takes Place and I/O Image Table Mapping, pages 28 to 37
Pages 28 to 37 of 90, from FLEX I/O PROFIBUS Adapter (Cat. No. 1794-APB) User Manual
The original document is the PDF (924 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1794-IB16
Page 28
How Communication Takes Place and I/O Image Table Mapping
2–11
1794-IE8 Range Selection Bits Channel No.
Channel 0
Channel 1
Channel 2
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
F0
C0
F1
C1
F2
C2
F3
C3
F4
C4
F5
C5
F6
C6
F7
C7
Decimal Bit
00
08
01
09
02
10
03
11
04
12
05
13
06
14
07
15
0–10V dc/0–20mA
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
4–20mA
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
-10 to +10V dc
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Do Not Use1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
C = Configure select bit F = Full range bit 1 Do not use this configuration. Individual channels revert to 4–20mA if bit selection is all zeroes.
1794-IE8 Word/Bit Descriptions Word
Decimal Bit
Definition
Bits 00–14
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 0 analog data sign bit.
Bits 00–14
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 1 analog data sign bit.
Bits 00–14
Channel 2 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 2 analog data sign bit.
Bits 00–14
Channel 3 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 3 analog data sign bit.
Bits 00–14
Channel 4 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 4 analog data sign bit.
Bits 00–14
Channel 5 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 5 analog data sign bit.
Bits 00–14
Channel 6 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 6 analog data sign bit.
Bits 00–14
Channel 7 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 7 analog data sign bit.
Read Word 1
Read Word 2
Read Word 3
Read Word 4
Read Word 5
Read Word 6
Read Word 7
Read Word 8
Publication 1794-6.5.6 – April 1996
Page 29
2–12
How Communication Takes Place and I/O Image Table Mapping
Word
Read Word 9
Decimal Bit
Definition
Bits 00–07
Underrange bits (U) for individual channels (4-20mA current input only)– Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on. When set (1), indicates either a broken or open input wire, or input current below 4-20mA.
Bits 08-14
Not used – set to 0.
Bit 15
Power Up bit – included in series B modules only. This bit is 0 in series A modules. This bit is set to 1 when all bits in the configuration register are 0 (unconfigured state). The configuration register can be cleared by either of the reset inputs, or by the user writing all zeroes to it.
Bits 00–07
Full range bits (F) for individual channels – Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on. Refer to range selection above.
Bits 08–15
Configure select bits (C) for individual channels – Bit 08 corresponds to input channel 0, bit 09 corresponds to input channel 1, and so on. Refer to range selection above.
Write Word 2
Bits 00–15
Not used – set to 0.
Write Word 3
Bits 00–15
Not used – set to 0.
Write Word 4
Bits 00–15
Not used – set to 0.
Write Word 5
Bits 00–15
Not used – set to 0.
Write Word 6
Bits 00–15
Not used – set to 0.
Write Word 1
1794-OE4 – 4 Output Analog Module Image Table Mapping I/O Image Input Size Read
0 or 1 Word
Module Image PU
Not used
Diagnostics
Analog Data Channel 0 Analog Data Channel 1 Analog Data Channel 2 Analog Data Channel 3 Not used Output Size Write
1 or 6 Words
Not used
Config. Select
Not used
Not used Not used Not used Not used Not used Not used Not used Not used
Publication 1794-6.5.6 – April 1996
OE Full Range
Page 30
How Communication Takes Place and I/O Image Table Mapping
2–13
1794-OE4 Memory Map Decimal Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Size
Oct. Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read Words
W3
W2
W1
W0
Read Word 1
PU
Not used – set to 0
S
Analog Data – Channel 0
Write Word 1
S
Analog Data – Channel 1
Write Word 2
S
Analog Data – Channel 2
Write Word 3
S
Analog Data – Channel 3
Write Word 4
Not used – set to 0 Not used – set to 0
C3
C2
C1
C0
Not used – set to 0
OE3 OE2
OE1
OE0
Write Word 5
F3
F1
F0
Write Word 6
F2
Write Words 7 thru 14
Not used – set to 0 Where: PU = Power up bit – included in series B modules only. W = Diagnostic bits for current output wire broken or load resistance high. (Not used on voltage outputs.) S = Sign bit (in 2’s complement) OE = Output enable bits (bit 00 corresponds to output 0, bit 01 corresponds to output 1 and so on. ATTENTION: These bits must be set to 1. C = Configure select bit F = Full range bit
1794-OE4 Range Selection Bits (Write Word 6) Channel No.
Channel 0
Channel 1
Channel 2
Channel 3
F0
C0
F1
C1
F2
C2
F3
C3
Decimal Bit
00
08
01
09
02
10
03
11
4–20mA
0
1
0
1
0
1
0
1
0–10V dc/0–20mA
1
0
1
0
1
0
1
0
-10 to +10V dc
1
1
1
1
1
1
1
1
Off1
0
0
0
0
0
0
0
0
C = Configure select bit F = Full range bit 1 When configured to off, individual channels will return 0V.
1794-OE4 Word/Bit Descriptions Word
Read Word 1
Decimal Bit
Definition
Bits 00-03
Current outputs only – When set (1), the wire on the output is broken or the load resistance is too high. Bit 00 corresponds to channel 0, bit 01 corresponds to channel 2, and so on.
Bits 04-14
Not used – set to 0.
Bit 15
Power Up bit – included in series B modules only. This bit is 0 in series A modules. This bit is set to 1 when all bits in the configuration register are 0 (unconfigured state). The configuration register can be cleared by either of the reset inputs, or by the user writing all zeroes to it.
Bits 00–14
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 0 analog data sign bit.
Write Word 1
Publication 1794-6.5.6 – April 1996
Page 31
2–14
How Communication Takes Place and I/O Image Table Mapping
Word
Decimal Bit
Definition
Bits 00–14
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 1 analog data sign bit.
Bits 00–14
Channel 2 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 2 analog data sign bit.
Bits 00–14
Channel 3 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 3 analog data sign bit.
Bits 00–03
Output Enable bits. Bit 00 corresponds to input 0, bit 01 corresponds to input 1, bit 02 corresponds to input 2, and bit 03 corresponds to input 3. These bits must be set to 1.
Bits 04-15
Not used – set to 0.
Bits 00–03
Full range bits (F) for individual channels – Bit 00 corresponds to output channel 0, bit 01 corresponds to output channel 1, and so on. Refer to range selection above.
Bits 04-07
Not used – set to 0.
Bits 08–11
Configure select bits (C) for individual channels – Bit 08 corresponds to output channel 0, bit 09 corresponds to output channel 1, and so on. Refer to range selection above.
Bits 12-15
Not used – set to 0.
Write Word 7
Bits 00–15
Not used – set to 0.
Write Word 8
Bits 00–15
Not used – set to 0.
Write Word 9
Bits 00–15
Not used – set to 0.
Write Word 10
Bits 00–15
Not used – set to 0.
Write Word 11
Bits 00–15
Not used – set to 0.
Write Word 12
Bits 00–15
Not used – set to 0.
Write Word 13
Bits 00–15
Not used – set to 0.
Write Word 14
Bits 00–15
Not used – set to 0.
Write Word 2
Write Word 3
Write Word 4
Write Word 5
Write Word 6
Publication 1794-6.5.6 – April 1996
Page 32
How Communication Takes Place and I/O Image Table Mapping
2–15
1794-IE4XOE2 – Analog Combo Module Image Table Mapping Module Image I/O Image
Input Data Channel 0
Input Size
Input Data Channel 1
0 to 5 Words
Read
Input Data Channel 2 Input Data Channel 3 Underrange & Diag.
PU
Output Data Channel 0 Output Data Channel 1 OE
Not used Not used
Output Size Write
Full Range and Configure Select Not used
0 to 4 Words
Not used Not used Not used Not used Not used
1794-IE4XOE2 Memory Map Decimal Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Size
Oct. Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read Words
S
Analog Value Input Channel 0
Read Word 1
S
Analog Value Input Channel 1
Read Word 2
S
Analog Value Input Channel 2
Read Word 3
S
Analog Value Input Channel 3
Read Word 4
PU
Not used – set to 0
W1
W0
U3
U2
U1
Read Word 5
S
Analog Data – Output Channel 0
Write Word 1
S
Analog Data – Output Channel 1
Write Word 2
Not used – set to 0 Not used
C5
C4
C3
C2
C1
C0
0
0
F5
F4
F3
F2
OE1
OE0
Write Word 3
F1
F0
Write Word 4
Not used – set to 0 Where:
U0
Write Word 5 thru 10
PU = Power up bit – included in series B modules only. W = Diagnostic bits for current output wire broken or load resistance high. (Not used on voltage outputs.) U = Underrange bits for 4-20mA inputs OE = Output enable bits (bit 00 corresponds to output 0, bit 01 corresponds to output 1). ATTENTION: These bits must be set to 1. S = Sign bit (in 2’s complement) C = Configure select bit F = Full range bit
Publication 1794-6.5.6 – April 1996
Page 33
2–16
How Communication Takes Place and I/O Image Table Mapping
1794-IE4XOE2 Range Selection Bits Channel No.
Input Channel 0
Input Channel 1
Input Channel 2
Input Channel 3
Output Channel 0
Output Channel 1
F0
C0
F1
C1
F2
C2
F3
C3
F4
C4
F5
C5
Decimal Bit
00
08
01
09
02
10
03
11
04
12
05
13
4–20mA
0
1
0
1
0
1
0
1
0
1
0
1
0–10V dc/0–20mA
1
0
1
0
1
0
1
0
1
0
1
0
-10 to +10V dc
1
1
1
1
1
1
1
1
1
1
1
1
Off1
0
0
0
0
0
0
0
0
0
0
0
0
C = Configure select bit F = Full range bit 1 When configured to off, individual channels will return either 0V or 0mA.
1794-IE4XOE2 Word/Bit Descriptions Word
Decimal Bit
Definition
Bits 00–14
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 0 analog data sign bit.
Bits 00–14
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 1 analog data sign bit.
Bits 00–14
Channel 2 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 2 analog data sign bit.
Bits 00–14
Channel 3 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 3 analog data sign bit.
Bits 00–03
Underrange bits (U) for individual channels (4-20mA current inputs only) – Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on.
Bits 04-05
Wire Off bits (W) – Current outputs only – When set (1), the wire on the current output is broken or the load resistance is too high. Bit 00 corresponds to channel 0, bit 01 corresponds to channel 2, and so on.
Bits 06–14
Not used – set to 0.
Read Word 1
Read Word 2
Read Word 3
Read Word 4
Read Word 5
Bit 15
Power Up bit – included in series B modules only. This bit is 0 in series A modules. This bit is set to 1 when all bits in the configuration register are 0 (unconfigured state). The configuration register can be cleared by either of the reset inputs, or by the user writing all zeroes to it.
Bits 00–14
Channel 0 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 0 analog data sign bit.
Bits 00–14
Channel 1 analog data – 12-bit left justified two’s complement number; unused lower bits are zero; 4-20mA uses all 16 bits.
Bits 15
Channel 1 analog data sign bit.
Write Word 1
Write Word 2
Publication 1794-6.5.6 – April 1996
Page 34
How Communication Takes Place and I/O Image Table Mapping
Word
Decimal Bit
2–17
Definition
Bits 00–01
Output Enable bits. Bit 00 corresponds to output 0, bit 01 corresponds to output 1. These bits must be set to 1.
Bits 02–15
Not used – set to 0.
Bits 00–05
Full range bits (F) for individual channels – Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, bit 02 corresponds to input channel 3, bit 03 corresponds to input channel 3, bit 04 corresponds to output channel 1, and bit 05 corresponds to output channel 2. Refer to range selection above.
Bits 06–07
Not used – set to 0.
Bits 08–13
Configure select bits (C) for individual channels – Bit 08 corresponds to input channel 0, bit 09 (11) corresponds to input channel 1, bit 10 (12) corresponds to input channel 2, bit 11 (13) corresponds to input channel 3, bit 12 (14) corresponds to output channel 0, and bit 13 (15) corresponds to output channel 1. Refer to range selection above.
Bits 14–15
Not used – set to 0.
Write Word 5
Bits 00–15
Not used – set to 0.
Write Word 6
Bits 00–15
Not used – set to 0.
Write Word 7
Bits 00–15
Not used – set to 0.
Write Word 8
Bits 00–15
Not used – set to 0.
Write Word 9
Bits 00–15
Not used – set to 0.
Write Word 10
Bits 00–15
Not used – set to 0.
Write Word 3
Write Word 4
1794-IR8 – RTD Input Analog Module Image Table Mapping Module Image Reserved Input Data Channel 0 I/O Image Input Size 1 to 11 Words
Input Data Channel 1 Input Data Channel 2 Input Data Channel 3 Input Data Channel 4 Input Data Channel 5 Input Data Channel 6 Input Data Channel 7 Overrange Underrange Calibration Status Configuration
Calibration Mask Output Size 0 to 3 Words
RTD Type RTD Type
Publication 1794-6.5.6 – April 1996
Page 35
2–18
How Communication Takes Place and I/O Image Table Mapping
1794-IR8 Read Dec. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Oct. Bit
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read Word 1
Reserved
Read Word 2
Channel 0 Input Data
Read Word 3
Channel 1 Input Data
Read Word 4
Channel 2 Input Data
Read Word 5
Channel 3 Input Data
Read Word 6
Channel 4 Input Data
Read Word 7
Channel 5 Input Data
Read Word 8
Channel 6 Input Data
Read Word 9
Channel 7 Input Data
Read Word 10 Read Word 11
Overrange Bits 0
0
0
0
0
Underrange Bits
Bad Cal
Cal Done
Cal Range
0
Diagnostic Status Bits
Pwr Up
0
0
0
1794-IR8 Write Dec. Bit Oct. Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Cal Clk
Cal Hi Cal Lo
Enh
MDT
Write Word 1
8-bit Calibration Mask
Filter Cutoff
Write Word 2
RTD 3 Type
RTD 2 Type
RTD 1 Type
RTD 0 Type
Write Word 3
RTD 7 Type
RTD 6 Type
RTD 5 Type
RTD 4 Type
Where:
Enh = Enhanced MDT = Module Data Type
1794-IR8 Word/Bit Descriptions Word
Dec. Bits (Octal Bits)
Read Word 1
00–15 (00–17)
Reserved
Read Word 2
00–15 (00–17)
Channel 0 Input data
Read Word 3
00–15 (00–17)
Channel 1 Input data
Read Word 4
00–15 (00–17)
Channel 2 Input data
Read Word 5
00–15 (00–17)
Channel 3 Input data
Read Word 6
00–15 (00–17)
Channel 4 Input data
Read Word 7
00–15 (00–17)
Channel 5 Input data
Read Word 8
00–15 (00–17)
Channel 6 Input data
Read Word 9
00–15 (00–17)
Channel 7 Input data
Publication 1794-6.5.6 – April 1996
Description
Page 36
How Communication Takes Place and I/O Image Table Mapping
2–19
Word
Dec. Bits (Octal Bits)
Description
Read Word 10
00–07
Underrange bits – these bits are set if the input signal is below the input channel’s minimum range.
08–15 (10–17) Read Word 11
Write word 1
Overrange bits – these bits are set if 1), the input signal is above the input channel’s maximum range, or 2), an open detector is detected.
00–01
Not used – set to 0
02
Reserved
03
Powerup bit – this bit is set (1) until configuration data is received by the module.
04–06
Critical Error bits – If these bits are anything other than all zeroes, return the module to the factory for repair
07
Unused – set to 0
08 (10)
Calibration Range bit – set to 1 if a reference signal is out of range during calibration
09 (11)
Calibration Done bit – set to 1 after an initiated calibration cycle is complete.
10 (12)
Calibration Bad bit – set to 1 if the channel has not had a valid calibration.
11–15 (13–17)
Unused – set to 0
00–01
Module Data Type Bit
01
00
0
0 oC (default)
0
1 oF
1
0
Bipolar counts scaled between –32768 and +32767
1
1
Unipolar counts scaled between 0 and 65535
02
Enhanced mode select – measures voltage drop across a precision resistor in the module to compare with the unknown input.
03–05
A/D Filter First Notch Frequency Bit
05
04
03
Definition
0
0
0
10Hz (default)
0
0
1
25Hz
0
1
0
50Hz
0
1
1
60Hz
1
0
0
100Hz
1
0
1
250Hz
1
1
0
500Hz
1
1
1
1000hZ
06
Calibration High/Low bit – This bit is set during gain calibration; reset during offset calibration.
07
Calibration clock – this bit must be set to 1 to prepare for a calibration cycle; then reset to 0 to initiate calibration.
08–15
Calibration mask – The channel, or channels, to be calibrated will have the correct mask bit set. Bit 0 corresponds to channel 0, bit 1 to channel 1, and so on.
Publication 1794-6.5.6 – April 1996
Page 37
2–20
How Communication Takes Place and I/O Image Table Mapping
Word
Dec. Bits (Octal Bits)
Write Word 2
00–03
Description Channel 0 RTD Type Bit
03
02
01
00
RTD Type – Range
0
0
0
0
Resistance (default)
0
0
0
1
No sensor connected – do not scan
0
0
1
0
100 ohm Pt α = 0.00385 Euro (–200 to +870oC)
0
0
1
1
100 ohm Pt α = 0.003916 U.S. (–200 to +630oC)
0
1
0
0
200 ohm Pt α = 0.00385 (–200 to +630oC)
0
1
0
1
500 ohm Pt α = 0.00385 (–200 to +630oC)
0
1
1
0
Reserved
0
1
1
1
10 ohm Copper (–200 to +260oC)
1
0
0
0
120 ohm Nickel (–60 to +250oC)
1
0
0
1
100 ohm Nickel (–60 to +250oC)
1
0
1
0
200 ohm Nickel (–60 to +250oC)
1
0
1
1
500 ohm Nickel (–60 to +250oC)
1
1
0
0
Module data time stamp
1101 to 1111 – Reserved
Write Word 3
04–07
Channel 1 RTD Type (see bits 00–03)
08–11
Channel 2 RTD Type (see bits 00–03)
12–15
Channel 3 RTD Type (see bits 00–03)
00–03
Channel 4 RTD Type (see write word 2, bits 00–03)
04–07
Channel 5 RTD Type (see write word 2, bits 00–03)
08–11
Channel 6 RTD Type (see write word 2, bits 00–03)
12–15
Channel 7 RTD Type (see write word 2, bits 00–03)
Publication 1794-6.5.6 – April 1996