FLEX I/O PROFIBUS Adapter (Cat. No. 1794-APB) User Manual: 3 - Connecty the Adapter to the PROFIBUS DP Network
Pages 46 to 51 of 90, from FLEX I/O PROFIBUS Adapter (Cat. No. 1794-APB) User Manual
The original document is the PDF (924 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1794-IB16
Page 46
Chapter
3
Connect the Adapter to the PROFIBUS DP Network What this Chapter Contains
This chapter describes: • the DP physical layer
• • • •
The DP Physical Layer using line types A and B equipment you need how to connect the adapter to the network how to terminate the network
The PROFIBUS network media is a balanced transmission line corresponding to the standard EIA RS-485, terminated at both ends. Both line A and line B types are available, depending on your system requirements. Specifications and guidelines for DP media: • linear bus, terminated at both ends
• drop cables (preferably no longer than .30m), no branches • shielded twisted pair • max. line length between 100 and 1200m (depending on baudrate and cable type)
• number of stations: 32 • DP baudrates: 9.6, 19.2, 93.75, 187.5, 500 Kbit/s and 1.5M bit/s Use the following table to determine what line type will best meet your needs. Bus Segments and Drop Cables Characteristic Impedance Capacity Resistance Wire Gauge Conductor Area
Maximum Length1 with a Baud Rate (bits/s) of:
v19.2k 93.75k 187.5k 500k 1.5M
Line A Requirements
Line B Requirements
135–165 W (3–29 MHz) t30 pF/m t110 W/km u0.64 mm u0.34 mm2 1200 m2 1200 m2 1000 m2 400 m2 200 m2
100–130 W (fu100 kHz) t60 pF/m – u0.53 mm u0.22 mm2 1200 m2 1200 m2 600 m2 200 m2 NA
Total Capacity of all Drop Cables v15nF v3nF v1nF v0.6nF v0.2nF
NA = Not Applicable 1 If using a combination of both line types, divide the lengths shown by two.
2 This is the sum of all bus segment and drop cable lengths.
Publication 1794-6.5.6 – April 1996
Page 47
3–2
Connect the Adapter to the PROFIBUS DP Network
Cabling and Equipment Required for Line A Type
Line A cabling can support baudrates as high as 1.5M bits/s. Cables You need a shielded twisted pair cable for your cabling (bus segments or drop cables). Any line A cable available on the market can be used to connect your adapter to a PROFIBUS network. T-junction Connectors You need t-junction connectors to connect your droplines to bus segments. You can use any t-junctions available on the market. Termination Blocks Termination blocks are only needed if the devices on the end of the network do not have built-in terminating resistors. If you need termination blocks, you can use any termination blocks available on the market. Bus Connector Connect your adapter to the PROFIBUS DP network by attaching a bus connector to the female 9 pin D-Sub connector on the front of the module. Important:
More Information...
Publication 1794-6.5.6 – April 1996
For detailed information on the topology and cabling for line A, see the PROFIBUS Standard (DIN 19245 Parts 1 & 3, Issue 1994).
Page 48
Connect the Adapter to the PROFIBUS DP Network
Cabling and Equipment Required for Line B Type
3–3
Line B cabling can support baudrates as high as 500k bits/s. Cables You need a shielded twisted pair cable for your cabling (bus segments or drop cables). Any shielded twisted pair cables available on the market can be used to connect your adapter to a PROFIBUS network, however, bus segment cables must contain wire for data ground and a cable braid shield. We recommend Sprecher+Schuh cable as shown in the table below. T-junction Connectors You need t-junction connectors to connect your droplines to bus segments. You can use any t-junctions available on the market, however, we recommend Sprecher+Schuh connectors as shown in the table below. Termination Blocks Termination blocks are only needed if the devices on the end of the network do not have built-in terminating resistors. If you need to use termination blocks, any termination blocks available on the market can be used, however, we recommend Sprecher+Schuh termination blocks as shown in the table below. Bus Connector Connect your adapter to the PROFIBUS DP network by attaching a bus connector to the female 9 pin D-Sub connector on the front of the module. Important:
More Information...
For detailed information on the topology and cabling for line B, see the PROFIBUS Standard (DIN 19245 Parts 1 & 3, Issue 1994).
Equipment Drop cable T-junction connector Bus segment cable Bus segment 1m Connector Termination Block
Type Sprecher + Schuh Sprecher + Schuh Sprecher + Schuh Sprecher + Schuh Sprecher + Schuh Sprecher + Schuh
Catalog Number PTL-2, PTL-4, or PDC-10 PTS-0 none PCB-10 none PCE-0
Part Number 87.890.282-10 87.890.276-01 299.257.001 87.890.281-10 87.890.283-01 87.890.284-01
Publication 1794-6.5.6 – April 1996
Page 49
3–4
Connect the Adapter to the PROFIBUS DP Network
Connect the Adapter to the Network
For line A or B connections, use bus segments with t-junctions and termination blocks to form the PROFIBUS media (trunk cable). Use termination blocks to terminate the line at each end of the trunk cable. Use drop cables to connect devices to the network. The maximum number of stations on the same network is 32.
= Drop Cable = Bus Segment = Termination Block = T–junction
Personal Computer with Configuration Software
PROFIBUS DP Master/Scanner Controller
Other DP Adapter/Slave
PROFIBUS Media (trunk cable) 1794-APB Adapter Slave Other DP Adapter/Slave Flex I/O System
Publication 1794-6.5.6 – April 1996
Page 50
Connect the Adapter to the PROFIBUS DP Network
3–5
Connect to the Adapter Connect your drop cable (using either line A or B) to the adapter as shown below: 1 . . 5
PROFIBUS ADAPTER
•
6 . . 9
DROP CABLE
Shield Pin #1
.01µF 500V dc
1 MΩ
Signal +
Pin #3
Signal –
Pin #8
RCV/ Xmit Data + RCV/ Xmit Data –
Earth Ground Pin #5
+5V
Pin #6
Data Ground
1. Connect the cable shield to Pin #1. The shield is connected to the FLEX I/O chassis ground through an RC circuit as shown above. 2. Connect the data signal pins on both ends (Signal + Pin #3 and Signal – Pin#8). 3. Insert the wired connector into the mating connector on the PROFIBUS adapter.
Publication 1794-6.5.6 – April 1996
Page 51
3–6
Connect the Adapter to the PROFIBUS DP Network
Terminate the Network
You must use termination blocks only if your devices on the end of the network do not have built-in terminating resistors. Terminate the PROFIBUS media (trunk cable) at both ends of the network. If you are not using a connector with built-in resistors, terminate the cable at the adapter connector as shown below.
Terminate at the Adapter Using Line A Since Line A has a higher line impedance, you must use the following termination resistors: PROFIBUS DP ADAPTER
+5V
9 . . 6
5 . . 1
6
CABLE 390 Ω (2%, - 1/4 W)
Signal +
3 220 Ω (2%, - 1/4 W)
Signal -
8 390 Ω (2%, - 1/4 W)
Data Ground 5
Terminate at the Adapter Using Line B Use the following termination resistors with line B: PROFIBUS DP ADAPTER
+5V
6
Signal +
3
9 . . 6
5 . . 1 CABLE
390 Ω (2%, - 1/4 W)
150 Ω (2%, - 1/4 W) Signal -
8 390 Ω (2%, - 1/4 W)
Data Ground 5
Publication 1794-6.5.6 – April 1996